due to self-induction.
FIG. 107. Showing the Effect of Self-induction in an Alternate-current
Circuit. V is the impressed E.M.F. ; i c \, dynamic current ; ?'i mp ,
impressed current ; and 4, current due to E.M.F. of self-induction ;
per second, are given in Fig. 111.
These data have been determined by Mr. Chas. F. Scott. The
wires of the one circuit are marked by black dots, and those
of the other by rings. The volts given refer to the E.M.F.
induced by each circuit in the other, and will be positive or
negative according as the two currents are in opposite or
CHANGE RATIO OF TRANSFORMERS. 229
the same directions. The diagram is directly applicable to a
single-phase system or to a two-phase system with four wires,
and can be readily modified to suit a three-wire system.
Mr. A. E. Kennelly has given much attention to the im-
pedance of mutually inductive circuits, and has developed an
elegant geometrical treatment, which is applicable to most
practical problems, even when they involve resistance, self-
and mutual-induction, and capacity. The subject is not suit-
able for discussion here. The student is referred to the technical
Press for further information.*
~ fc / 133 no 0-006 volts.
1 60 r^ 0-0027
155 ~ ' 015
60 r^ 0-0065
(133 r^ Q-035
I 60 rv 0-016
n n * -f 133 ~ ' 070
O O \ 60 rxj 0-032
n n * -f 133 ~ ' 112 "
1 60 nu 0-050
FIG. 111. Showing the number of volts per ampere per 1,000ft, of
double circuit due to mutual-induction between two circuits in various
arrangements. The wires of the two circuits are severally distinguished
by rings and black dots.
H4. EFFECT OF CAPACITY UPON THE CHANGE
RATIO OF TRANSFORMERS.
When transformers are used for testing alternators for insula-
tion resistance, it is sometimes noticed that the pressure at the
terminals of the transformers is far in excess of that due to
the ratio of conversion. This is due to the capacity of the
alternator. The effect is of some importance in practice. The
theoretical principles on which it depends are difficult to
* Especially The Electrician, October 27, 1893 ; and the Transactions of
American Institute of Electrical Engineers for April, 1893.
230
ELECTRIC MOTIVE POWER.
express without the use of coefficients and complicated equa-
tions. But some idea of the order and magnitude of the
1UUUU
8000
5
>
4000
2000
/
\
/
V
\
\
7
\
s^
^^-^
**
Microfarads.
FIG. 112. Curves showing the Variation in Pressure in the Secondary
Circuit of a Step-up Transformer, by varying the Capacity in the Secondary
Circuit. The experiments made with a No. 2 Siemens Transformer, and
Current obtained from a Wl Siemens Machine, frequency 100 c\j . The
Exciting Current kept constant, and Alternator kept running at 750
revolutions during all the experiments.
zoo
160
120
(A
|so
40
/
\
/
\
/
'
\
?
\
X
^^
* .
\ '2 -a
Micr
4 -5 -6 -7
afarads.
FIG. 113. Curves showing the corresponding Variation in Pressure in
the Primary (Low Pressure) Circuit in the same Transformer, by varying
the Capacity in the Secondary Circuit.
increase of ratio of conversion will be gathered from the
curves in Figs, 112, 113, and 114, taken from "The Alternate-
COMPENSATING FOR DEOP.
231
Current Transformer in Theory and Practice," by Dr. J. A.
Fleming, Vol. II., pp. 396-398.
The point to be specially remarked in connection with power
work is that long concentric conductors have considerable
capacity (about O33 microfarad per mile run), and hence may
readily cause effects of the order shown in the experiments.
They will be most marked with step-up transformers of large
size. It is also important to notice (see Fig. 114) that there
is a critical value of the capacity for the given self-induction
of the circuit which will produce a maximum rise of pressure,
and that the ratio of conversion is steadily increased as the
capacity increases (to in this case 0'65 of a microfarad).
3 -4
Microfarads.'
FIG. 114. Curves showing the Dependence of the Ratio of Transforma-
tion of Pressure between Primary and Secondary Circuit on Capacity of
, -Secondary. Deduced from the experiments illustrated in Figs. 112 and 113.
It is, therefore, theoretically possible to compensate for the
drop of pressure at the far end of a feeder by putting a suitable
capacity in the circuit.
45. COMPENSATING FOR DROP OF PRESSURE IN
CONDUCTORS.
There are several methods in use at present for compensating
the variations of pressure in the feeders or in the transmission
mains. The most common consists in simply adjusting the
excitation by hand or automatically, the generators being
separately excited ; another consists m compounding the
alternators in a manner similar to that adopted with dynamos,
the alternators being either self-excited or else partly self-
excited and partly separately excited.
R2
2M ELECTRIC MOTIVE POWER.
Hand regulation by a resistance in series with the field-coiJ
circuit is easily understood, and there is no need to make any
special reference to automatic devices whose function is simply
to vary the resistance of the exciting circuit.
The Brush Company, Messrs. Ganz and Co., Messrs. Easton,
Anderson and Goolden, and others, make automatic regulators
of this description, and the author has spent much time in
designing similar devices, but in his opinion they cannot be
regarded as complete successes, and certainly are not adapted
for use in power plants where there is no skilled super-
vision. Compound winding, however, is a practical device. By
Field Coil
Field Coil.
FIG. 115. Thomson-Houston Method of Compounding Alternators.
b b, Collector rings.
means of it alternators can be made to compensate for any pre-
determined drop, and therefore to meet most of the regulation
difficulties in the feeders. The arrangement adopted by the
Thomson- Houston Compivny is to partly excite the field from
a dynamo with a steady current and to provide a variable ex-
citation by redressing a portion of the main current and passing
it through a pair of coils opposite to each other, or through
coils on each of the field poles. It is clear that, since the arma-
ture current is redressed, the excitation due to it will be
proportionate to the load.
The arrangement is shown in Fig. 115. The two main col-
lecting rings are shown at b b. The " redresser " consists of
COMPOUNDING ALTERNATORS.
233
"two circular gun metal castings, having each half as many
projections as there are pole-pieces in the field; both being
insulated. One of these is permanetly connected to one of
the collecting rings and the other to the free end of the
armature coils as shown. Two brushes, resting on projections
belonging to opposite rings of the redresser, form the terminals
of the exciting circuit. To reduce sparking at the instant of
short-circuiting the field coils when the brushes rest on the
same rings, a suitable resistance is placed in shunt to the field,
-and this serves in addition to control the proportion of current
in the exciting coils, and therefore to vary the compounding
within the limits of the design. This is a very complete and
convenient device. It is characteristic of the methods generally
Fig. 116. Kapp's Method of Regulating the Drop of Pressure at the end
of a Feeder.
adopted by Messrs. Ganz and others. Alternators thus com-
pounded will work in parallel as readily as separately-excited
machines.*
Another very simple plan is to place the primary of a
suitable transformer in series with the feeders, and to excite
the compound coils from its secondary current, redressed.
Since this current is proportionate to the armature current,
it is clear that the compounding can be arranged to any slope
of characteristic.
A device patented by Mr. Kapp is interesting in this
connection. It is shown in Fig. 116.
* See letter by Mr. E. M. Mix, The Electrician, March 23, 1894.
234 ELECTRIC MOTIVE POWER.
One coil, P, of a small transformer is placed in series with
the feeder, and the other coil, S, is coupled across the station,
mains. By inserting more or less of the coil S in the circuit
by a shifting contact, a few auxiliary volts are put into the
feeder by the inductive action of the shunt-coil. This regula-
tor may be designed to add a sufficient number of volts to com-
pensate for any desired drop. It may be applied to each feeder
independently, although all the circuits are working off one
alternator. This is a distinct advantage, and makes it a most
convenient device for power plants. The Westinghouse Com-
pany use a similar arrangement, which they call a " booster."
46. MEASUKEMENT OF PRESSURE AT THE END
OF FEEDERS.
The pressure at the termination of the alternate-current
feeders may be read by means of two transformers, without
the aid of pressure wires run back to the station. The general
FIG. 117. Diagram of Station Voltmeter Connections for Reading Pressure
at the far end of Feeder.
arrangement is as follows : The voltmeter is in series with
the secondary circuits of two transformers, one of which has
its primary in series with the feeder, and the other its
primary as a shunt across the feeder. It is illustrated in
Fig. 117.
The pressures of the two transformers are opposed to each
other. The secondary pressure of the transformer in shunt is
proportional to the station omnibus pressure, V ; and that of
the transformer in series to the primary current strength i my
and therefore to i m R, if the resistance be constant. The volt-
meter will consequently read proportionately to V-^ m R,
which is the expression for the pressure at the far end of
the feeder. This principle, with important modifications, is
employed by Messrs. Ganz and Co. Its application is shown
MEASUREMENT OF PEESSUEE IN FEEDERS. 235
in diagram in Fig. 118, the adjustable resistance in the
exciter circuit being also shown. The feeders are shown
at L! L 2 , the shunt transformer at T I} and the series
transformer at T 2 . The secondary circuit of T x is closed
through the solenoid of the regulator S, the resistances R 3 , R 1
and R 2 . The secondary of T 2 is closed through the resistance
R 2 . The transformers are joined up so that their electromotive
forces are in opposition as regards producing a current in the
Shunt
Transformer
AltarnAtor.
/WWVWA MMAM 2
Feeder. Transformers
FIG. 118. Ganz and Co.'s Method of Compensating for Drop in Feeders.
solenoid S. The terminal pressure of Tj is evidently pro-
portionate to the station pressure. The difference of pressure
between the points a and b, the terminals of R 2 , will be pro-
portionate to the feeder current ; and so the pressure between
the points e and / will be equal to V i m R, the pressure at the
termination of the feeders. The intensity of the current in the
solenoid circuit will determine the excitation, and hence the
pressure at the sub-station can be kept constant for variation
236 ELECT EIC MOTIVE POWEE.
of drop. It will be seen that a Cardew voltmeter is used to
read the primary pressure. This is made possible by a suitable
ratio of conversion in the transformers. It will be evident that
these methods of reading the sub-station pressure are only
applicable when the virtual resistance of the feeders is
practically constant, or varies according to some easily deter-
mined law, in which case the voltmeter can be specially
calibrated to include these effects.
47. COMPENSATORS, OR REGULATORS.
The Thomson-Houston Company use, in particular cases, a
compensator, whose functions are similar to those of the " re-
gulator " referred to on page 135, with two-wire continuous-
current feeders and multiple-wire distributors. This may be of
use for power work in cases where the regulation of the supply
<
ig r 9 .9
BOOv. Compensato
FIG. 119. Prof. Elihu Thomson's " Compensator " System applied to
Power Circuit.
pressure presents difficulties. The plan of connection is shown in
Fig. 119, the " compensator" being simply a choking coil, with
its circuit divided into as many parts as there are sub-circuits.
Each of the distributing circuits is assumed to be at 125 volts.
When the load is evenly divided between the circuits the
compensator will carry practically no current, owing to
the impedance of its coils, which are wound round soft
iron wire. But if the load be removed from one of the four
circuits, the compensator coil, say coil A, in parallel to it will
act as the primary of a transformer, and induce in the remain-
ing coils of the compensator, B C D, a secondary current which
will act in the outer circuit in the same direction as the
MULTIPLE WINE DISTRIBUTION. 237
main current. The coils B, C, D will supply - amperes,
i being the current for two motors (assuming the circuits to
o
be equally loaded), and the alternator will supply f i amperes.
4
If the two circuits A and B are opened, then the coils C and
D will supply *- amperes, and the alternator an equal number.
The regulating capacity of the compensator is, therefore, seen
to be in this case equal to four times the current it is designed
to carry. It is evident that small differences of load between
the various circuits are readily compensated by this ingenious
device, which may be defined as a combination of a transformer
.and a direct system of distribution.
t
200 v.
2000 v. < <^ 200 vr
1 H
200 v,
<$> i
^ SYNCHRONIZING
~Si
FIG. 122. Arrangement of Impedance Coils used in putting Thomson
Alternators in Parallel.
The impedance coil is shown separately in Fig. 123. It consists
of a laminated iron ring, with a few turns of well-insulated wire
wound round about one-eighth of the circumference. A
copper sheath is arranged so as to be capable of rotation about
the centre. The sheath is of such width as just to surround
the coil. When the winding is covered, the device corresponds
to a transformer with the secondary circuit short-circuited, and
the impedance is then very slight ; as the sheath is gradually
removed the impedance increases; when the stationary coil
is entirely uncovered the device has its maximum effect. In
REACTIVE COILS. 241
some forms the impedance coil is short-circuited when the
sheath completely encloses it. These impedance coils are
useful for balancing loads between machines and for varying
the pressure of feeders ; they generally act the same as
rheostats with continuous currents, but have the advantage of
consuming less power.
Parallel working is without doubt assisted by using a
moderate rate of frequency, say not more than about lOO'X/ ;
but there is no gain in reducing it below about 50 to 60 ^.
It is also necessary to synchronise the engines as well as the
alternators if the running is to be perfect. This points to the use
FIG. 123. Impedance Coil, or Dimmer.
of high-speed engines with flywheels and moving parts of small
inertia, so as to readily lead or lag as the conditions of
working may require. For the same reason the engine should
not be governed directly, as the better the governor the
greater the difficulty of varying the rate of speed. The station
governor should be designed to control the steam admission to
the bank of engines, and the load should be distributed pro-
portionately by varying the excitation. A "trip" governor
should be used on all engines of this class, to check racing
in the event of a belt breaking or slipping off, a fuse blowing.
or other similar accident
.242
ELECTEIC MOTIVE POWEE.
49. ALTERNATE-CURRENT MEASURING
INSTRUMENTS.
It has already been stated that the energy of an alternate-
current circuit is proportional to the ^/mean square value of
the instantaneous values of the current, and it has also been
stated that this x /mean square is equivalent to that of a con-
tinuous current that will produce the same heating effects.
Therefore, alternate-current measuring instruments are cali-
brated by direct currents, and the readings on the scales are
accordingly proportional to the ^/mean square of either con-
tinuous or alternate currents.
A few hints of a practical nature will assist engineers in
selecting suitable instruments.
Some of the most practical forms of instruments in general
use are tabulated in Table W, the names of typical designs
being given.
Table W. Examples of Practical Instruments suitable for
Power Stations.
Voltmeters.
Ammeters.
Wattmeters.
Electro-dynamic
Electro-magnetic
fElihu Thomson,
-j Evershed,Dolivo,
1 Ayrton & Perry
/Siemens' Dyna-
\ mometers
(Evershed, Elihu
1 Thomson, Kelvin,
1 Ayrton & Perry,
vDolivo
/Kelvin, Swin-
\ burne
Electro - thermal
Electro-static ...
Cardew, Holden
f Kelvin's Multi-
cellular, Swin-
\burne, Ayrton
& Mather ...
/Holden, Ayrton
\ and Perry ...
...
It is desirable, if possible, to have direct-reading pressure
instruments, which are directly applicable to the circuits,
without non-inductive resistances in series with them, both
because the details are simpler and also because the energy
wasted in the resistance is often considerable. For this latter
reason electro-thermal, or hot-wire, instruments, although very
MEASURING INSTRUMENTS. 243
convenient for reading low pressures, say up to 150 volts, are
objectionable if kept in circuit. For high-pressure work the
most practical instruments are of the electro-static type, for
they absorb scarcely any power.
If hot-wire instruments are used to read high pressures, it is
advisable to have a voltmeter transformer with a suitable ratio
between the primary and secondary. Thus, with a 2,000-volt
primary and a 100-volt secondary, a convenient ratio of con-
version will be ^j-. This transformer method is more expensive
in first cost than direct-reading with a multicellular voltmeter,
and it also wastes more power, probably absorbing about 30
watts in the hot-wire and 30 in the transformer.
Current-measuring instruments are generally kept in circuit,
and hence it is important that they should waste little power.
For reading large currents electro-magnetic instruments of low
resistance are perhaps as good as any of the other types. The
electro-dynamic method has the disadvantage of requiring
mercury contacts. The hot-wire principle is used with success
for measuring current, but the instruments are necessarily
delicate, and the author does not advise them for power work
as a rule. The electro-chemical principle is not generally
applicable for ordinary commercial purposes.
Ohmmeters are useful when erecting station plant, but they
they are not necessary for every-day work.
"Wattmeters, or power meters, are of the utmost importance
in all stations where economy of prime power is an object. One
should be placed in the circuit of each alternator, to indicate the
power given out by the machine. This enables the attendant
to divide the load between the several alternators according to
their capacity, and thus to work with the smallest excita
tion. One of the best forms of this instrument for station use
is Lord Kelvin's engine-room wattmeter. The appearance of
the interior of the instrument is shown in Fig. 124. It
has a main circuit of a double rectangle of copper rod. The
pressure coils are made of fine wire wound in the shape ol
244 ELECTRIC MOTIVE POWER.
a pair of spectacles, and are in series with a non- inductive-
external resistance.
The general arrangement of the movable shunt coils, the
suspension springs, and the gravity adjustment for calibrating
are shown in Fig. 125. Each of these shunt coils has about
1,000 turns of insulated wire of approximately 1,000 ohms
FIG. 124. Lord Kelvin's Engine-room Wattmeter. General view of instru-
ment, with case removed.
resistance. The scale has nearly uniform divisions, and is
graduated to read directly in watts or kilowatts, as required.
Siemens' dynamometer-wattmeter is also a practical instru-
ment, but as usually designed absorbs more power than
Lord Kelvin's.
If a wattmeter be made recording it answers the purpose of
an ergmeter, for the load curve is easily integrated by a
PRECAUTIONS WITH ALTERNATE CURRENTS. 245
planimeter, and thus a continuous record of the station output
may be kept without much expense or trouble.
It is not necessary to put the full primary pressure on the
terminals of the shunt-coil of the wattmeter ; a suitable trans-
former may be used to reduce the pressure to a convenient
fraction, and hence a small movable coil, carrying a mere ciace
of current, may be used, and will add considerably to the
accuracy of the instrument.
Ergmeters, or energy meters, are not yet in common use,
and are not likely to be much used for power purposes.
FIG. 125. Lord Kelvin's Wattmeter. Fine-wire Shunt Coils, showing
details of suspension. Controlling springs removed.
50. PRECAUTIONS TO BE OBSERVED IN ALTERNATE-
CURRENT WORKING.
Owing to induction and capacity effects, it is usually neces-
sary in alternate- current circuits to observe certain precautions
in starting and stopping alternators, in opening and closing
circuits, and in adding or withdrawing feeders from omnibus
bars. It must be recollected, however, that these effects are
largely the result of the self-induction of the alternators, and
that generally there will be no difficulty when the armatures
have comparatively small reactions, as is the case with the
Mordey alternator, for example.
246 ELECTRIC MOTIVE POWER.
The chief danger to be apprehended is a sudden variation of
pressure, which may be sufficiently large to break down the
insulation of the circuit at one or more points or to seriously
affect the load. This is due both to the change of conversion
ratio in the transformers and to the variations of impressed
pressure in the alternators.
The precautions to be observed are :
Never open a high-pressure circuit containing self-induction
or capacity, without first slowing the alternator or weakening
its excitation, or reducing the load by an impedance coil.
Never switch an alternator into parallel with another
machine without first adjusting its excitation so that the
coupled alternators will give the proper omnibus pressure.
Never switch an alternator out of parallel without adjusting
its excitation (and that of the remaining machines if necessary)
so as to leave the omnibus pressure unaffected.
An alternator of large self-induction requires to be excited to
a higher pressure than that of the omnibus bars before coupling
in parallel, as the terminal pressure will fall considerably when
the circuit is closed. In taking such a machine out of parallel
the excitation may be reduced until the current is nearly zero ;
or the speed may be lessened until the same end is attained.
The switch under these conditions may be opened without a
dangerous spark.
If, however, the conversion ratio of the transformers be
affected by the capacity of the circuit (as occurs with step-
up transformers and concentric mains), then the incoming
alternator with large self-induction must be under-excited, in
order to bring it into such a condition that it can be coupled to
the active machines without affecting the pressure at the far
nd of the feeders. And, conversely, in taking it out of parallel
the excitation must be raised a little, in order to avoid serious
sparking on opening the circuit. These effects have been noticed
in practice, and are explained by an alteration of the capacity
and self-induction of the circuit affecting the conversion ratio
of the transformer.
SAFETY DEVICES. 247
,51. EARTHING THE PRIMARY AND SECONDARY
CIRCUITS OF TRANSFORMERS; SAFETY
DEVICES.
In transformer work there is a chance of the primary
pressure invading the secondary circuit. If this occurs there
may be danger to life. And this is the more serious, since,
in most cases, the leakage is entirely unsuspected by the con-
sumer. To obviate this danger various arrangements have been
suggested, and some have met with the approval of the Fire
Insurance Offices and the Board of Trade. The safest plan,
perhaps, is to ground one of the primary cables close up to the
station (as is done by the London Electric Supply Corpora-
tion), and to place between the secondary circuit and earth a
device which will ground the secondary circuit the instant
the high-pressure current enters the consumer's circuit. This
will cause a large primary current to now, and hence the
primary fuses will blow and cut off the premises. The
danger to life is entirely obviated, unless the transformer or
other device has a large electro-static capacity, but this is
never the case with ordinary transformers.
There are three protective devices in general uso : Major
Cardew's " Mouse Trap," Mr. Kent's metallic sheath, and the
Thomson-Houston film cut-out.
The Cardew safety device is shown in Fig. 126. It consists
of two brass plates placed near together, but insulated from
each other. Between them is a strip of aluminium foil
attached by ebonite pins at one of its ends to the bottom
plate. One plate is connected to earth, and therefore to one
of the primary mains, and the other to the secondary circuit.
As soon as a leak occurs between the primary and secondary
circuits of the transformer there is an electro-static pressure
between the plates, and when this equals a definite number of
volts the free end of the foil is attracted and makes contact
with the top plate. This grounds the secondary circuit, and
the primary current blows the primary fuses.
Mr. Kent's arrangement consists of an earthed metal ring,
properly slit to avoid eddies, placed between the primary and
s2
213 ELECTRIC MOTIVE PuWER.
secondary windings. Any fault of insulation in either circuit
can be made to ground the coils and blow the main fuses.
The film cut-out of Prof. Thomson is merely a piece of prepared
paper between two metallic contacts. This paper is pierced
when the pressure between the contacts exceeds a predeter-
mined amount. Thus the paper insulation will easily stand
the secondary pressure of, say, 100 volts, but will break down
instantly it is subjected to the high pressure of the primary.
In practice one of these film contacts is connected to each of
the secondary mains.
FIG. 126. Major Cardew's Earthing Device, for protecting Transformer
Circuits.
Mr. Ferranti has devised a very ingenious method for pro-
tecting transformer circuits from the risk of partial earth
(always a source of danger, since a second ground on the same
circuit will cause a dead short-circuit on the secondary, and
may cause a fire). This method requires the middle of the
secondary circuit to be permanently earthed. It is perhaps
more useful at present as a testing device for partial grounds,
as the Fire Offices' regulations do not generally allow any part
of the consumers' circuit to be earthed. But for power
plants, where these restrictions do not obtain, the device is
most useful. The arrangement is shown in Fig. 127.
EARTHING DEVICES.
249
It will be seen that there are two small transformers across
the secondary mains, with a ground wire from their point of
junction. Their pressures are arranged in opposition, and
normally no current flows through them. If, however, another
earth, full or partial, is made in one of the secondary mains,
the corresponding transformer will cease to produce current,
and, the balance of pressure being upset, a current will flow in
Station.
To Station J
Fuce.
House Transformer.
VWWWVWVW^
AAAAAAA/SAAAAAA
j-AAAAAAA VWWXA-j
Safety Device Transformers.
FusKbleAVire.
To Lamps. To Earth.
FIG. 127. Ferranti " Earthing Device," for Transformer Protection.
their secondary circuit, and will melt the fuse, thereby allowing
a conical plug to drop into the split cup shown in the diagram.
This short-circuits the secondary circuit and blows the primary
fuses.
It is urged strongly by most of the leading electrical
engineers that the secondary circuits should always be earthed
250 ELECTRIC MOTIVE POWEE.
as well as the primary. If this were generally practised it
would be impossible for a plant with defective insulation to
remain in connection with the high-pressure circuit, for the
main fuses would blow out as often as the main switches were
closed. With the existing compulsory regulations, it is possible
for a bad earth to exist on an installation until a second earth
reveals its existence, possibly by a fire.
CHAPTEE VIIL
POLYPHASE ALTERNATE-CURRENT WORKING.
52. Definitions ; Two-phase Currents. 53. Three-phase Currents.
54. Relative Merits of Two-phase and Three-phase Currents. 55.
Polyphase-Current Transformers ; Diagrams of Connection?. 56.
Combination of Two- and Three-phase Circuits. 57. Synchronous
Polyphase Motors. 58. Present Practice in Polyphase Alternators
and Motors. 59. Winding ; Starting Torque ; Power Factor.
60. Combination of Polyphase and Continuous Currents ; Rectified
Currents.
52. DEFINITIONS; TWO-PHASE CURRENTS.
THE term polyphase is applied to circuits in which two or
more alternate currents, of the same wave length and direc-
tion, succeed each other at regular intervals. In practice, the
number of impulses is usually limited to two or three, and the
systems are then severally distinguished as two-phase and
three-phase. An alternate current (single or multiple), when
used to excite field magnets, produces a rotating magnetic field;
that is, the axis of the field rotates with reference to space,
though the windings are stationary. This is seen to be the case
by considering an ordinary two-pole series-wound motor which
is supplied with a single-phase alternate current. The poles
will change from north to south polarity at every half period,
and the axis of the magnetic field may be regarded as rotating,
making one complete revolution in each period. Such a motor
is, therefore, said to have a rotary magnetic field, and on the
Continent is called a Drehstrom motor. A continuous-current
motor, however, is not adapted for working with alternate
252 ELECTEIC MOTIVE POWER.
currents of the usual frequencies, since the self-induction of the
field-magnet circuit is too large.*
If two separate currents, with phase intervals of 90deg., be
supplied to a four-pole motor, in which the armature consists
of an iron core with windings short-circuited, either through
brushes or else by rings of metal at each end, a rotary
magnetic field in the stationary part will result. And
this will induce currents in the closed coils of the arma-
ture whose direction will be such as to cause a magnetic field
FIG. 128. Four-pole Two-phase Motor.
tending to stop the rotation of the main field. This will be
understood by examining Fig. 128, which represents a four-pole
two-phase motor, having neither commutator nor brushes.
There are two alternating exciting circuits, AA X and B B p
in quadrature.
* Attempts have been made, but with little success, to overcome this
difficulty by laminating the magnet?, lowering the frequency, and modify-
ing the windings, so as to reduce the self-induction as much as possible,
and to limit the hysteretic and eddy-current losses. Vide " The Distribu-
tion of Power by Alternate-Current Motors," by Albion T. Snell ; Proc.
Institution of Electrical Engineers, Vol. XXII., part 106.
TWO-PHASE CURRENTS. 253
Suppose that A and A 1 be magnetised so as to cause lines of
force to pass from A to A l through the armature C. Then B
and B x will be neutral, for there will be no current in them at
this moment.
Next, the current in A Aj will gradually die away ; and that
in B Bj will steadily rise in an equal ratio but opposite
direction until the magnetic flux is from B to Bj, and A and
Aj are neutral.
This cycle will be repeated, but with this alteration the
current in A A x will rise to a negative maximum (assuming it
to have been positive before), and the flux will be in the direc-
tion of A 1 to A, and in the next wave from B x to B. Carefully
noting these changes, it is seen that the magnetic field has
rotated once for a complete oo in each of the circuits ; and
therefore the speed of the field rotation is , where N is the
P
number of ou per second and p is the number of pairs of poles
in one circuit. In the case referred to, since p = 1, the revolu-
tions of the magnetic field will be the same as the number
of <~v .
In a two-phase dynamo the closed-circuit armature is re-
placed by a suitable electro-magnet, excited by a continuous
current. Two-phase periodic currents are induced in the two
circuits A A : and B B 15 the phase difference between them
being 90deg.
Mathematically the currents in the two circuits may be
expressed thus :
That in A A! = K sin a,
B B! = K cos a = K sin ( a - \
which shows the phase difference between the two currents.
Now K is a constant for the particular machine, and a is a
measure of the angular motion of the field. It will be seen
that the current in A A! is a maximum when a is equal to
Q
- and - TT, and is zero when a is equal to and IT. The converse
of this is the case with the current in B Bj.
254
ELECTRIC MOTIVE POWER.
Two-phase current circuits are usually worked with four
wires two for each circuit but three wires, one having a sec-
tion V41 times as great as that of each of the others, may be
used. The latter arrangement is possible because the large
wire will act as a common return for the two currents, the sum
of whose instantaneous values is 1*41 times that of either.
This will be seen on reference to Fig. 129, in which the full line
curves relate to the impulses acting in the directions A A x and
B B x ; and the dotted line curves to those in the directions
A! A and BjB.
Curves A and B show the current-fluctuations in the two
circuits, and D that in the common return. The magnetic field
FIG. 129. Diagram of Two Periodic Currents with a Common Eeturu.
Phase Difference of 90deg.
will be caused by A and B alone, and, therefore, will be pro-
portional to their sum at any instant. When A is a maximum
B is zero, and the induction at this moment is proportional to
the current in A alone, and is equal to, say, i sin - = i. When
A and B are equal, as at 135deg. of field rotation, the induc-
tion is proportional to 2 i sin 135deg. = i 1'4. Thus the current
varies in intensity between 1 and 1*4.
To illustrate the fluctuation of the field excitation the sign
of the negative curves in Fig. 129 may be changed, and they
may be plotted above the time line as if they were positive in
value (see Fig. 130).
EXCITATION WITH TWO-PHASE CURRENTS. 255
This diagram is justified by the consideration that each
circuit in the motor contains at least two coils wound in opposite
directions, and thus produces poles of different signs.
In Fig. 130 the excitation fluctuation is shown by the top
curves, which may be regarded as having reference to one of
the poles of the rotary field, say the north pole.
Since the theoretical mean variation of the exciting current
is as much as 15 per cent., it may be supposed that the
magnetic induction also varies by nearly as large a percentage,
but this is not the case. These curves are deduced upon the
supposition that the exciting circuits have no self-induction,
whereas, on the contrary, they have much. And, further,
SO 160 270 300 6O
FIG. 130. Diagram of Excitation Variation with Two-phase Current.
Phase Difference of QOdeg.
the resultant field cannot vary in intensity between such
wide limits as those indicated in the diagram. Indeed, it
is safe to assume that the field will be nearly steady as
long as the effective values of the two currents are equal and
their sum is constant. Armature reactions introduce serious
complications, for their effect depends partly upon whether
the current leads or lags the impressed electromotive force,
and partly on the amount of the phase difference between
the pressure and current. As already pointed out, when
considering single-phase alternate-current machines, armature
reactions tend to magnetise the field when the current leads
and to demagnetise the field when it lags. The effect will
be a maximum at starting, will decrease as the armature
speed increases; and will be nil if the speeds of armature
and field coincide, i.e., if the motor works synchronously.
256
ELECTRIC MOTIVE POWER.
53. THREE-PHASE CURRENTS.
Three-phase current working presents several advantages,
but entails complications in the design of the machine, and
also in the regulation of the pressure, because the three cir-
cuits are connected. This is demonstrated in the following
abstract from a paper by the author entitled " The Dis-
tribution of Power by Alternate-Current Motors," which was
read before the Institution of Electrical Engineers in the spring
of 1893.
Fig. 131 represents diagrammatically the phases of three
equal periodic currents separated by intervals of 120deg. ; the
FIG. 131. Three Equal Periodic Currents separated by Phase Intervals
of 120deg.
full and dotted lines referring to the direction of the impulses,
as already explained for Fig. 129. If A, B, C represent the three
currents, then their instantaneous values are severally given
by:-
A = K sin a,
2
B = K sin (a - - TT),
3
C = K sin (a - 1 TT).
o
o 4
Now, K { sin a 4- sin (a - " TT) + sin (a - - TT) } = 0, as is easily
3 o
proved ; and, therefore,
THREE-PHASE CURRENTS.
257
It may be seen that the algebraical sum of the instantaneous
values of the three currents is equal to zero under all condi-
tions ; for, even when one of the quantities is equal to nought,
the remaining two are equal, and, being of opposite sign, cancel
each other.
Three-phase current working is accomplished by parallel or
series coupling of the circuits, the two methods being severally
FIG. 132. Parallel, or Closed Circuit, or Triangle Three-phase
Coupling.
known as the triangle and star sj stems. In the following
diagrams large capitals are used to distinguish the mains, and
small letters to denote the windings. Suffixes are used to mark
the phase order of the circuits.
The parallel or closed circuit, or triangle coupling, is shown
in Fig. 132. Let I 1? I 2> L be the effective values of the several
FIG 133. Three-phase Dynamo coupled to a Motor.
currents flowing in the mains, and i lt i^ i 3 the corresponding
effective currents in the coils. Also, let V 15 V 2 , V 3 be the
effective pressures at the terminals of i v i z , i 3 . And assume
there is no self-induction or capacity. Then, if the load be
equally distributed between the mains, we may assume
258
ELECTEIC MOTIVE POWER.
Also, since i is in phase with v, and I lies SOdeg. removed
from i, it follows, if the mains be fed with a combined
three-phase current (as in Fig. 133), that the current in
one main will differ in phase by 30 deg. from the pressure
between it and the two other mains. This follows from the
FIG. 134. Diagram of a Three-phase Circuit.
geometrical relationship of the coils and the mains. And the
effective value of the current in each of the mains is equal
to 1*732 times the effective current in each of the coils, when
the circuits are equally loaded. In Fig. 134 let the currents in
the mains and in the coils be considered positive when flowing
FIG. 135. Diagram of a Three-phase Circuit.
in the direction indicated by the arrows. The phase and mag-
nitude relations of these currents will then be represented by
Fig. 135 ; and if this diagram be supposed to revolve uniformly
around its centre, the length of the projections of the sides
on any fixed straight line will represent the instantaneous
THREE-PHASE CURRENTS. 259
values of the corresponding currents ; for it is plain that
these projections satisfy all the necessary conditions, viz. :
^ = ^-^^1
-*n-h
:_.: -H
All instantaneous values i.e., the
lengths of the projections of the
x + 1 2 + IB = I corresponding sides of Fig. 135.
Again, the sides of the diagram are proportional to the effec-
tive values of the corresponding currents; and, if the load
be equally distributed between the three mains, then for
effective values,
I x = I 2 = I 3> ^ = i 2 = i. 3 ; and Ij = 2 i z sin GOdeg. ;
or, generally, 1 = 1*732 i.
This proof is due to Dr. W. E. Sumpner, Professor of
Electrical Engineering at the Battersea Polytechnic.
v s
FIG. 136. Diagram of Relative Position of Curves of Currents in Mains
and Coils of a Closed-type Combined Three-phase Circuit, with no Self-
induction or Capacity.
By a similar diagram the relation between the effective
pressures on the coils and mains in the open or star arrange-
ment can be shown to be V = 1'732 v. (See Fig. 137.)
The relative positions of the phases of currents and pressures
in the mains and coils of a combined three-phase circuit of the
closed type with no self-induction are shown in Fig. 136, V and e
having the same value and coinciding in phase. It will be seen
that the maxima of the currents in the mains, I, are always
260
ELECT 'RIG MOTIVE POWER.
midway between those of the coils, i, and that the phase
difference between them is SOdeg.
The series, open circuit, or star coupling is shown in Fig. 137-
As before, let there be no self-induction or capacity, and let
I 1= =I 2 = I g - i 1 = i 2 = i 3 ' and V 1 = V 2 = V 3 . Now, since the
mains, I, are in series with the coils, i, and there is by hypothesis
no self-induction or capacity, I^^, I 2 = *2> anc ^ 1$ = iy But
the pressures between the mains are not the same as those at
the coil terminals, and v will be in advance of V by SOdeg., and
will be numerically equal to , or v = , therefore,
2 sin 60 1-732
V = 1-732 v.
FIG. 137. Series, or Open Circuit, or Star Three-phase Coupling.
The phases of current and pressure in a combined three-phase
circuit of the open type are shown in Fig. 138, 1 and i having
the same value and coinciding in phase.
The conclusions thus arrived at are true only on the assump-
tions (a) that the coils themselves have no self-induction, and
(b) that both the coils and the mains are equally loaded. The
first condition is never found in practice, and the second is
only likely to obtain with small motors, and then only in an
THREE-PHASE CURRENTS. 261
approximate degree. The effect of self-induction is to cause
the current in the coils to lag behind the pressure at the
terminals.
To measure exactly the power in a three-phase system is
difficult ; but it can always be done by measuring the work
performed in each of the separate circuits, and adding the
quantities.
In Fig. 136, the power = 3 iv = 3 x V -i-_ = V x I x 1-732, if
the three circuits be equally loaded and there be no self-
induction or capacity.
FIG. 138. Diagram of Relative Position of Curves of Pressures and
Currents in the Coils and Mains of the Open-type Combined Three-phase
Circuit, with no Self-induction or Capacity.
In Fig. 137, also, the power = 3^ = 3x1 ^ = V x I x 1-722,
on the same assumptions.
So it appears, if there be no self-induction and an equal load
in each circuit, that the number of amperes in one of the mains
multiplied into the pressure between two mains into 1-732
gives the power in watts. If there be self-induction, the above
quantity must be multiplied by the cosine of the angle of lag
between the current and the pressure. The energy absorbed
by a motor, therefore, will be expressed by
Vxlx 1-732 cos <,
where c/> is the angle of lag.
262 ELECTEIG MOTIVE POWER.
Dr. W. E. Sutnpner suggests that when the three circuits are
equally loaded the power can be measured by one wattmeter
(see Fig. 139). Put the current coil in one of the mains, say I 2 ,
and take two readings, one with the pressure coil coupled
between I x and I 2 , and one with it coupled between I 2 and I 3 .
The two readings will be found to be of the same value, and
the power will be equal to their sum.
FIG. 139. Method of Measuring Power in Three-phase Circuit, with
Mains equally Loaded.
When the load is unequally distributed, two wattmeters are
required (see Fig. 140). Place the current coils in two of the
mains, say I : and I 3 , and couple one pressure coil between I t
and I 2 , and the other between I 2 and I 3 . The power is then
the sum of the two wattmeter readings.
o
o
FIG. 140. Method of Measuring Power in Three-phase Circuit, with
Mains unequally Loaded.
This method of measuring power is applicable whatever the
law of variation of the current, and however unequally loaded
the mains may be.
It has been shown on page 258 that with combined three-phase
currents, even when neglecting the self-induction of the coils,
there is a constant phase difference between the current and
ROTAEY MAGNETIC FIELDS. 263
the line pressure. This, although not in itself a direct loss,
causes difficulty in measuring, regulating, and controlling the
currents. Hence it has been found expedient to work the
dynamo circuits unconnected and to use six or more separate
coils. The currents from these are combined by a suitable
transformer so as to convert the secondary currents into a com-
b'nel high-pressure rotary current, with phase differences of
120deg. This high-pressure current is reduced at the motor
end of the line by another transformer and subdivided as re-
quired.
It is not a simple matter to represent the intensity of the
magnetic field by a diagram, for the magnetism is not merely
the result of the exciting current in the field coils, but is also
largely affected by the magnitude of the induced currents in
the closed coils, which vary from instant to instant with the
fluctations of load. There are two periodic currents acting
in the closed coils one of high frequency, equal to the
number of the pairs of field poles multiplied into the number
of revolutions per second ; and one of lower frequency, which
depends simply on the difference of speed rotation between
the revolving field and the rotating coils.
The low-frequency current produces the torque, and is
highest at starting, when the slip of the armature is greatest.
It is expressed numerically by n , where N = the number
of revolutions of the magnetic field per minute and n = that of
the rotating coils. For example, if N = 2,400 and n = 1,920,
then the frequency will be 8 per second. In determining the
excitation for polyphase motors and dynamos it is, therefore,
necessary to make two calculations, one for full and one for
light load, just as with direct-current machines.
It is clear that it is not possible to represent the changes of
the rotary field magnetism by a general diagram. Fig. 141,
however, shows diagrammatically the relative position of the
current and pressure curves in a combined three-phase circuit,
with the resultant excitation, assuming the armature reactions
to have no effect i.e., the field and coils are supposed to
rotate at nearly the same speed. An arbitrary angle of lag of
T2
264
ELECTRIC MOTIVE POWER.
30deg. between the pressure and the current in the exciting
coils has been assumed, and the curves have been drawn to
suit the sine law. The pressure is shown in V V, and the
current in ii. The resultant excitation is indicated in curves
R R, the limits of which are 2i and 1-732*, a mean difference
of about 8 per cent.
This is true only when self-induction and armature reactions
are neglected ; if these be taken into account, it is sufficiently
clear that the field is approximately constant, and that is ail-
that is necessary in practice.
The torque will vary with the ampere-turns and the number
of lines of force in the circuit. The torque = ^ , where i &
K i
is the current in the short-circuited coils, C is the number of
120 180 240 300 360 CO
FIG. 141. Diagram of the Excitation Fluctuations in a Combined
Closed-type Three-phase Circuit.
turns, K! is a constant, and N is the magnetic flux in the
resultant field.
The magnetism is determined by the excitation, and the
number of turns of wire is, of course, fixed for a given design;
hence, to increase the torque, it is necessary that the moving
part rotate more slowly that is, the slip must be increased.
This raises the frequency, and consequently the magnitude,
of the current in the closed coils, thereby weakening the
resultant field and lowering the counter electromotive force of
the exciting coils, and allowing more current to flow in them.
But, since the resultant magnetism decreases as the current in
STAETING POLYPHASE CIRCUITS. 265
the closed coils increases, there is a point at which the torque is
a maximum. This corresponds to a definite line current, which
is not necessarily the starting current, and hence these motors
do not necessarily exert their greatest effort at starting.
To obtain maximum torque at starting, it is necessary to
insert resistances in series with the closed-circuit coils. The
function of the resistances is to determine the critical current,
thus limiting the armature reactions ; and also to regulate the
lag in phase between the currents in the closed and exciting
coils.
In order to avoid large rashes of current when closing the
line circuit, it is advisable to insert variable resistances in
FIG. 142. Combined Series and Parallel Three-phase Couplings.
series with the closed windings. This is specially necessary
with large machines (see 59, p. 293).
In order to obtain a more constant exciting current than that
given by the arrangement shown in Figs. 132 and 137, Mr.
Dobrowolski has devised a very pretty combination of the open
and closed type windings, which reduces the mean variation of
the excitation to 3 '5 per cent. The winding is shown diagram-
matically in Fig. 142, and is known as the double-linked
winding. The coils indicated by the symbols i' v i' v i' ?j , are
severally wound in two parallels, 15deg. removed from the
closed coils i v i 9 , i y The complications involved are consider-
able, and the gain perhaps not commensurate with them ; yet
for large machines the device may prove useful.
266
ELECTRIC MOTIVE POWER.
There are some important differences to be noticed between
the series and parallel connections. It has been shown that with
the series coupling v = - (see Fig. 137), and that the cur-
1 i o2i
rents in the coils and mains are the same ; and in the parallel
device (see Fig. 132), that each coil carries a current equal to
, and that the pressure at the coil terminals corresponds
T732
to the pressure between the mains. These differences are
suggested by the terms parallel and series, which are in this
respect more apt than those of triangle and star.
FIG. 143.
Diagram showing Ampere-
turns with Parallel Coupling.
FIG. 144.
Diagram showing Ampere-turns with
Series Coupling.
Now, the magnetising effect exerted by a given number of
turns of wire, and a definite effective current in the mains, will
be different with the two kinds of windings.
Consider Figs. 143 and 144, which severally represent the
parallel and series couplings, and the direction of current at
the instant when it is entering by one main and returning
equally by the two others. Let n be the number of turns of
wire in one coil. Then the total ampere-turns in the parallel
o
device is n I, and in the series arrangement - n I. Therefore,
2i
the magnetising effect, and also the self-induction, of the series
TWO-PHASE AND THREE-PHASE CURRENTS. 267
device is greater than that of the parallel for a given current
and a fixed number of turns. The total power absorbed by the
two circuits may be made the same by a proper adjustment of
pressure.
54. RELATIVE MERITS OF TWO-PHASE AND THREE-
PHASE CURRENTS.
Experts differ as to the relative merits of two- and three-
phase currents. As regards the alternators and motors there
is, perhaps, not much to choose between them. Machines
designed for similar outputs, whether synchronous or non-
synchronous, are found to have about the same efficiencies,
starting torque, weight, and apparent watt consumption. The
three-phase machines, however, are the better, according to
FIG. 145. Single-phase System.
xx' = Effective Pressure of 3,550 volts (see Table X, p. 268).
yy' = Maximum Pressure of 5,000 volts.
experiments made by Mr. Kolbein, the chief engineer of the
Oerlikon Works. As regards the winding details, perhaps the
two-phase type is the simpler. The main difference between
the two systems lies in the relative weights of copper required
in the conductors for given conditions, and the ease with which
the currents may be handled, regulated and controlled.
The first experiments with three-phase working brought to
light difficulties in the regulation of pressure between the
three mains at the points of supply, when the currents in the
three circuits were not approximately the same. These, though
since to S)me extent overcome, are greater than those with two-
phase currents. The difficulties lie chiefly with the design of
pa.iapisuoo si
A\.V\ OHUOU009
( 263 )
TWO-PHASE AND THREE-PHASE CURRENTS. 269
alternators and transformers. Two-phase currents, if worked
with two separate circuits, are as easily dealt with as single-
phase currents, and serve readily most purposes to which
single or poly-phase currents are usually applied. They are
specially convenient for distribution. It may be safely inferred
that two-phase currents are better adapted for a combined
service of light and power work than three-phase currents,
which are better adapted for running with equally loaded
ircuits, and therefore are not generally so suitable for lighting
work.
For simple transmission of power between two distant points,
however, the requirements are different, and the three-phase
current system is generally cheaper than either a continuous-
current or a one-phase or two-phase alternate-current system.
FIG. 146. Two-phase System. Three Wires.
x x' = Effective Working Pressure of 3,550 volts.
yy' = Maximum Working Pressure of 5,000 volts.
z z' = Maximum Component Pressure of 7,100 volts.
This interesting and important problem may be considered
in three ways, each of practical value :
(1) On the basis of maximum difference of pressure between
conductors ;
(2) On the basis of effective pressure at the distributing
station (or motor terminals, perhaps) ;
(3) On the basis of the economic law.
270
ELECTRIC MOTIVE POWER.
The ratios of the weights of copper under these conditions
are stated in tabulated form in Table X, p. 268, in which, to give
a practical character to the figures, a definite power has been
selected for transmission to the receiving station. Constant
line loss and constant fall of pressure have also been considered.
In the final column the economic law has been considered
to the exclusion of both a definite line loss and line drop, the
equivalent current being taken as in column 3. In practice,
the weights will be modified by local considerations ; but the
main ratios will hold good, and the figures given form,
therefore, a reliable guide between the relative merits of the
systems as affected by the weight of copper.
FIG. 147. Two-phase System. Three Wires.
xx' = Effective Working Pressure of 2,500 volts.
yy' = Effective Component Pressure of 3,550 volts.
z z' = Maximum Component Pressure of 5,000 volts.
The significance of the difference between effective and
maximum pressure is at once apparent if Figs. 145, 146, 147 r
and 148 are examined.
In these figures the electrical centre of gravity is shown
graphically. In any electrical circuit of good or bad insulation
there is a datum pressure with reference to the variations of
pressure in the circuit. For example, in a continuous-current
circuit the absolute pressure of the negative pole of the
dynamo will have a constant ratio to that of the earth's
surface at the particular site, and the difference of pressure
between it and the positive pole will simply affect the absolute
pressure of the positive pole. And, if the negative pole be
EARTHING THE MIDDLE WIRE.
271
grounded, the datum pressure will be that of the earth's
surface.
Again, with an alternate-current circuit, with both poles
insulated, the cyclical changes will alternately raise and lower
the absolute pressure above and below zero pressure, which
corresponds to that of the earth's surface. Thus, in a circuit
carrying a current of 5,000 effective volts pressure, the maxi-
mum pressure between any two points of the circuit will be
5,000 ^2 = 7,050 volts, while the absolute pressure will be
only 3,525, positive or negative. The stress through the
insulation to earth will, therefore, be only 3,525 volts.
But if the circuit be grounded, say, at one of the main
terminals, the absolute pressure between the other terminal
FIG. 148. Three-phase System.
x x = Effective Pressure of 3,550 volts.
y y' = Maximum Pressure of 5,000 volts.
and earth will be 7,050 volts, and therefore the insulation all
over the high-pressure circuit will be subjected to this stress,
although the effective working pressure will remain as before.
This possible change in the stress upon the insulation of a
circuit carrying an alternate current has led to the general
practice of earthing one of the primary mains, usually at both
the generating and distributing circuits. The maximum stress
is thus accepted, and suitable precautions adopted to safeguard
against accidents; and, as already pointed out in 51, p. 247,
additional security is gained because a fault in the other main,
at any point, at once blows the fuses and disconnects the faulty
section.
272 ELECTRIC MOTIVE POWER.
With two-phase three-wire circuits it is permissible to earth
the middle wire at the generating station, which then is at
zero pressure. The same precaution is observed with the
"star" coupled three-phase system (see Fig. 155, p. 277). With
the " triangle " three-phase system it is not permissible to
earth either of the mains, since the earth would then form
part of the circuit.
It appears, then, that, from considerations affecting prime
cost of line, the three-phase system is cheaper for long-distance
transmission than either single-phase or double-phase ones ;
and that continuous-current systems are the cheapest of all,
but are not admissible for extra high pressures.
The selection of a system for long-distance transmission
of power will mainly depend upon the maximum permissible
pressure. If it be possible to work at such pressures as are
feasible, in the engineer's judgment, for continuous-current
dynamos (coupled in series or otherwise), then there can be
no doubt, from considerations affecting the line, that this
will be the cheapest and best system. But if extra high pres-
sure be deemed advisable, then the three-phase system will
generally prove the cheapest.*
In connection with this question it is important to notice
that the engineers responsible for the electric power plant
being laid down at Niagara have finally, after mature con-
sideration, decided upon a four-wire two-phase system. The
reasons for their choice have been given by Prof. George
Forbes, in a Paper entitled " The Electrical Transmission
of Power from Niagara Falls," read before the Institution of
Electrical Engineers on November 9, 1893. The details of
the scheme have been strongly criticised by English experts,
and the choice of two-phase currents is open to doubt.
When it is considered that Buffalo, the nearest large city, is
* The generating plant may perhaps be a two-phase one, with suitable
step-up two-to-three-phase transformers, as proposed by Mr. Scott, of the
Westinghouse Company. And it may also prove economical to transform
the phase again at the receiving station. The ingenious proposals of
Mr. Scott, however, have not yet been verified in practice ; but there seems
to be no doubt of their feasibility and usefulness (sec 56, p. 278).
POLYPHASE TRANSFORMERS.
273
fifteen miles distant, it is clear that the weight of copper will
be a very important item in the cost of the whole plant, and,
in the author's judgment, a three-phase system would prove
more economical in first cost and give as good pressure regula-
tion as the two-phase. For it must be recollected that there
is a line difference of pressure of 20,000 volts, and hence step-
down transformers will have to be used at every point from
which power is taken. The main line drop will, therefore, be
as difficult to regulate with two-phase as with three-phase
currents ; and variation of pressure of submains of the distri-
buting systems can be as readily controlled by using indepen-
dent secondary circuits from three-phase transformers as from
independent secondary circuits of single or two-phase trans-
formers. Prof. Forbes's argument that two-phase currents are
I
I (
( f L
FIG. 149. Four- wire Two-phase Circuit with two Ordinary Transformers,.
Tj, To, one being Coupled to each of the Circuits, A, B.
more easily redressed than three-phase currents is probably
sound, but the fact that for large powers no form of alternate
current has yet been made unidirectional in a practical manner
cannot be ignored.* The use of a frequency of 25 c\> per
second is a departure from the best practice of to-day
(see 58, p. 284).
55. POLYPHASE-CURRENT TRANSFORMERS ;
DIAGRAM OF CONNECTIONS.
The principle of polyphase-current transformers is the same
as that of single-phase transformers. With two-phase currents
* See 60, p. 297.
274
ELEGTEIG MOTIVE POWER.
it is usual to couple single-phase transformers across each of
the circuits, as shown in Fig. 149, in which there are four con-
ductors of equal section. If three were used, the middle one
having 1 f 4 times the area of each of the outer ones, the trans-
formers could still be coupled as above; but the pressure
FIG. 150. Dobrowolski Three-phase. Transformer.
variation would be greater than with the separate arrange-
ment, especially if they, or the conductors, or the machines,
possessed much capacity or self-induction.
'With three-phase currents it is usual to employ combined
transformers, as it is important to balance the load on the
CONNECTIONS OF POLYPHASE TEANSFOEMEES. 275
three circuits, but three separate single-phase transformers
may be used. Various forms are in use, such as that shown
in Fig. 150, which shows the Dobrowolski type. One of the
methods of coupling the connections is given in Fig. 151.
This figure also illustrates one method of winding the primary
and secondary circuits. Owing to the phase differences between
the currents in the coils of the inter-connected circuit and the
pressure between the mains, there is a loss of pressure of r*:x>ut
13 per cent, in the ratio of conversion as compared with a
single-phase transformer. Hence the number of turns in the
FIG. 151. General Diagram showing one of the Methods of Winding the
Coils of a Three-phase Transformer. A, B, C : High-pressure mains and
coils. 1, 2, 3, 1', 2', 3': Low-pressure circuits, which may be combined or
separate. The phases are the same in opposite coils. The iron core
is indicated by the dotted lines.
primary circuit must be increased in this ratio. The efficiency
is, perhaps, not quite so high as that obtainable with the best
designed single-phase transformers, but it certainly exceeds 96
per cent, at full load, and the curve can be made to any slope
by suitably proportioning the weights of iron and copper as
already explained in 37, p. 205, when considering ordinary
transformers.
A three-phase transformer weighs less than three separate
single-phase transformers of an equal aggregate power, the
276
ELECTRIC MOTIVE POWER.
POLYPHASE CUREENT CIRCUITS.
277
ratio of weight being about 3 : 4. This increase of weight
efficiency is partly due to the magnetic flux dividing in a
similar manner to the current. The flux in one leg is in the
opposite direction to that in the other two. But the flow in
one of the two increases, while that in the other decreases.
The cycle is thus continually changing, each leg in succession
becoming the return for the magnetic flux in the other two.
FIG. 154. Diagram of Connections of a Three-phase Circuit.
A, Alternator. M, Motor. T l5 Step-Up Transformer. T 2 , Step-Down
Transformer.
The weight is also reduced to some extent, because the design
permits of the framing and yokes being made lighter in pro-
portion to the cores than is possible in the single-phase type.
In high-pressure transformers the high-pressure coils are
generally inter-connected, and the ends are usually protected
by glass tubes to a considerable height above the level of the
coils. The low-pressure coils have separate terminals to permit
of coupling up to separate circuits.
FIG. 155. Diagram of Connections of a Three-phase Circuit.
A, Alternator. M, Motor. T 1} Step-Up Transformer. T 2 , Step-Down
Transformer, e, Earth Plates.
Table Y, p. 285, gives some interesting data of Oerlikon
three-phase transformers, designed to work at line-pressures
up to about 5,000 volts.
Three-phase transformers work in parallel just as effectively
as single-phase ones. The general schemes for a transmission
plant with polyphase currents, with and without step-up
278 ELUGTRIC MOTIVE POWER.
transformers, is shown in Figs. 152 and 153. The details
are clearly illustrated. In the high-pressure system only one
transformer is shown, but a bank of transformers might be
arranged if necessary.
Two methods of arranging the connections of three-phase
circuits with step-up and step-down transformers are given in
Figs, 154 and 155.
56. COMBINATION OF TWO- AND THREE-PHASE
CIRCUITS.
It has already been shown that three-phase currents present
advantages for transmission as distinguished from distribution,
and that two-phase currents are specially adapted for serving
sub-divided circuits. A combination of the two systems is
thus suggested and necessitates a phase conversion at the
A
B o c
FIG. 156. Two- to Three-phase Diagram.
distributing centre. Various inventors have worked at this
problem, and some have attempted to change the frequency as
well, for this is also of great importance in long-distance trans-
mission of power. A solution of the latter has not yet been
published in a practical form, although it is in the air. But
the former has been apparently solved by Mr. Chas. F. Scott,*
the chief electrician to the Westinghouse Company. The
method is simple and practical, and is an ingenious application
of the fact that two alternate pressures of different phase in
series with each other do not give a combined pressure equal
to the sum of the components.
Thus, if in Fig. 156, AO and OB severally represent in
phase and magnitude two pressures in quadrature to each
* Prof. S. P. Thompson has independently developed the same idea.
See British Association Paper entitled " Some Advantages of Alternate
Currents" (The Electrician, August 24, 1894, p. 481).
PHASE CONVERSION. 279
other, and also in series, the resultant pressure will be repre-
sented in direction and magnitude by the hypothenuse A B of
the right-angled triangle A B. If A and B be so pro-
portioned that the angle ABO is GOdeg., the relationship
is evidently unaffected. The triangle A B, Fig. 156, is con-
structed to suit these conditions, and forms the half of the
equilateral triangle ABC, whose sides severally represent in
magnitude the t-hree pressures acting in a three-phase circuit.
Now, from the construction, and from what has already been
demonstrated in 52 and 53, it is evident that the pressures
represented by the lines A and C B may be combined to
give the two pressures represented by the lines AC and AB
or vice versa.
The three-phase diagram ACB may also be drawn as in
Fig. 157, in which A is the resultant of A C and A B. If the
B
FIG. 157. Two- to Three-phase Diagram.
ooils producing the pressures A and B C be supposed to be
each wound on separate ordinary type single-phase transformers,
and if there be two separate coils wound outside each of them,
ao and 6c, the arrangement may be diagrammatically
represented by Fig. 158.
Then a three-phase system may be supplied from the
terminals A, B and C, or a two-phase from those marked a, o,
and b, c. (In the diagram, the transformers may be imagined
to be feeding three-phase transmission mains at high pressure.)
The arrangement is simple and effective, involving no mechanical
details. It simply requires suitably-wound transformers at the
u2
280
ELEGTEIC MOTIVE POWER.
phase conversion station, where the pressure may be raised or
lowered as required.
FIG. 158. Diagram of Two Single-phase Transformers combined to give
Two- and Three-phase Currents.
The number of turns in the coils can be adjusted to give
any pressure between the several mains ; but if the pressure
Two Phase-
< 100 V--->
wwv
b o
.-,00V-,
1000 V
Three Phase.
FIG. 159. Diagram of Pressure Distribution in Two- to Three-Phase
Transformers.
between the three mains of the three-phase part be of the same
value, as is usual, then the number of turns in the two-phase
PHASE CONVERSION.
281
coils must be in the ratio of 2 : J3 ; the coil c b having, say,
200 turns, and the coil a o 173. This ratio is determined by
the phase difference of 30deg. between the line and coil pres-
sure (see 53, Fig. 137, p. 260).
The distribution of pressure will be seen from Fig. 159.
This system enables a three-phase line to feed three-phase
motors direct at the line pressure, two-phase motors through
transformers, and lighting circuits in two instead of three units.
These various operations are indicated in Fig. 160. If the
transformer which supplies direct from the terminals (C B, c b,
Fig. 159) be loaded and the other be on open circuit, a
single-phase current can be supplied at normal pressure,
independently of the other circuit.
3 Phase Line.
2 Phase 3 Phase
Transformers
AM AMA
olio
21 r*
2 Phase
Motor.
O]
3 Phase
Motor
FIG. 160. Diagram of Two-phase Alternators, Three-phase Line, Two- and
Three-phase Motors, and Lamps in Single-phase Circuits.
But if the transformer (A 0, a o) which supplies through
the three mains be loaded and the other be on open-circuit,
then a single-phase current can be supplied at a pressure equal
to only 87 per cent, of the normal. Two mains on one side
will be in parallel. The self-induction of the idle transformer
will not affect the circuit, for the current entering at the
middle of the winding divides equally in opposite directions
through the two halves of the coil, and thus completely
neutralises the self-induction. The ohmic resistance of the
winding has to be overcome, but this loss is^ more than com-
pensated by two of the mains being in parallel.
282 ELECTRIC MOTIVE POWER.
These conditions of running are not likely to be used under
ordinary circumstances. Yet one of them may prove of great
advantage in the case of damage to part of the system for
instance, if one side of the alternator be damaged by lightning
or other causes. This feature may be made the means of
minimising accidents, especially if the alternators are of the
single-phase type coupled rigidly in quadrature.
The efficiency of two transformers arranged for converting
from two-phase to three-phase, or rice versa, is said to be about
Y^th per cent, less than when the same transformers are used
with single-phase currents at corresponding loads.
57. SYNCHRONOUS POLYPHASE MOTORS.
Polyphase alternators make excellent synchronous motors,
and are said to keep step better than single-phase machines,
the link between the rotating magnetic field and the revolving
part being more flexible. The line current is fed to the
revolving part of the motor, and the stationary part is con-
structed of solid cast iron, with or without windings.
If there be no windings on the stationary magnets the
torque is due to induced currents in the non-laminated
pole pieces. This design is not adapted for a high efficiency
at starting, and therefore it is usual in most cases to provide
secondary windings to assist the initial torque. This need not
involve any complicated device.
Synchronous polyphase motors are specially suitable for very
large units, since the bulk of the machine consists of cast iron.
They are therefore cheaper than induction polyphase motors of
the same capacity. And, what is still more important, they
cause no lagging current in the line except at starting, and
therefore have a power factor of 100 per cent. This type of
motor is likely to be used largely in the near future. Its
general appearance is indicated in Fig. 161.
A good example of large synchronous polyphase motors is
afforded by a plant erected early in 1894 at Taftville Cotton
Mills, Conn., U.S.A., by which power is transmitted for a dis-
tance of about 4J miles.
SYNCHRONOUS POLYPHASE MOTORS.
283
There are two 250-kilowatt alternators, delivering power to
the line at a pressure of 2,500 volts. They run at 600 revolu-
tions per minute, and work perfectly in parallel. The motors
are of similar construction, and are separately excited by
3-kilowatt exciters driven by belting. They are coupled to
the main shafting by clutches, and are allowed to acquire the
FlG. 161. Diagram of Synchronous Polyphase Alternator, with
Windings on the Field Magnets.
speed of synchronism before the load is applied. In every
respect the plant is a great success.
58. PRESENT PRACTICE IN POLYPHASE
ALTERNATORS AND MOTORS.
Some of the most recent designs of polyphase alternators
and motors are shown in this section. They are typical of
present practice.
Polyphase generators for low pressure are frequently designed
to work at a pressure of 190 volts between the mains, and
284
ELECTRIC MOTIVE POWER.
are used with step-up transformers. High-pressure generators
and motors which will work at line pressures of from 5,000
to 7,000 volts are generally used for power transmission when
the line pressure need not exceed, say, 7,000 volts. The fre-
quency adopted is from 50 to 65. The lower value is being
FIG. 162. Oerlikon Low-Pressure Polyphase Alternator.
gradually adopted on the Continent, and will soon become the
standard. This frequency is too low for the most economical
conditions, and 65 or 70 ^ would be better, especially for
the transformers, but the practical consideration of slow speed
with few poles in generators and motors determines the lower
value (see Table M, p. 174).
POLYPHASE
285
FIG. 163. Oerlikon High-Pressure Polyphase Alternator, with Exciter
attached to the Shaft.
FIG. 165. Oerlikon Asynchronous Polyphase Motor.
3
Kf
* > co" ^ ^
g
8
LO O LO LO t> O
8
ggggogfeg
ro"
l^l-ssa
Q;
C5i
^
1 1
to
-'
ressure
ro"
^ 05 |j!o rH 2
2
&
1
LO 00 ^?0 P 9
O CM O rO CT) i 1 t 1
CM O IO C". r- \ rH T 1
to"
^
2
^o pLO
cc
-S
to"
g
1
I
ig^iSSS
Ci
^
^
1
i-l * CM Oi CM I> I>
i
^
s
o
ro"
g
CO
x tO LO
^
%
^cS^JS 00 "
2
^
J
1
LO J 2 ro
^i
~ri
ti
O
ro
O ro LO ^H LO ^ T 1
^
T^.
^
s-
1
s
g tO CM
LNJ O5 ,_p O IO CM
* CO O
0> ^ TH 00
^
^
S 8
x -\o ^
so
s
/V^
WH
r<
1
p tp tH o ^O O
Jt
o
LO 5^ o op
SjH
i
ft
^s
^ to
1
S^
^
\
2
J
! i 1
C><
1
<
1
1
k
Efficiency
Weight in Ibs
Primary n,732 v. between mains
amperes inl 3,464 ,,
each circuit (5,196 ,,
^2
Is
O
|
i
gj
H^
s
N
s
1
^
Kilowatts
Amperes per circuit
Horse-power absorbed
Efficiency
Revolutions per minu te
,.,,. f With exciter
Wei S htmtons (without exciter..
1
1
Kilowatts
(1,732 v. betwe
Amperes per circuit { 3,464 ,,
(5,196
Horse-power absorbed
Efficiency
Revolutions per minute
Weight, with exciter, in tons
^
POLYPHASE MACHINES.
287
In cases where power work alone has to be considered, and
the generators have to be coupled direct to slow-speed engines,
it is found convenient to decrease the frequency to even 25 or
20 Co per second ; but these are exceptional conditions.
The Oerlikon Company build excellent polyphase machines.
Their low-pressure alternator is shown in Fig. 162, and their
high-pressure alternator in Fig. 163. The performances of list
1,200
1,000
800
"5600
400
2CO
15
20
25
Oi 5 10
Amperes.
FIG. 164. Characteristic Curve of a 100-H.P. Three-Phase Oerlikon
Alternator.
machines of these types are given in Table Z and Table A A,
and a characteristic curve of a 66-kilowatt alternator, 1,040
volts per coil, is given in Fig. 164. The drop practically
follows Ohm's law, and capacity and self-induction effects, if
present, apparently cancel each other.
Types of the Oerlikon Company's normal three-phase motors
are shown in Figs. 165 and 166; and one of the Allgemeine
288
ELECTRIC MOTIVE POWER.
Electricitats Gesellschaft in Fig. 167. Some tests of the small
motors are given in Table B B, p. 289. It is seen that the
efficiency, although not equal to that of first-rate continuous-
current motors of similar output, is sufficiently high to make
the machines of great commercial value, especially when the
FIG. 166. Oerlikoti Asynchronous Polyphase Motor.
absence of commutator and brushes and all the troubles and
risks incidental to them is borne in mind. The Oerlikon
Company adopt as standards a pressure of 110 volts per coil,
equal to 190 volts between the mains (series coupling, see
Fig. 137, p. 260), and a frequency of 50 <~u per second.
TESTS OF POLYPHASE MOTORS.
289
Table B B. Tests of small Oerlikon Three-phase Motors, 50 ru.
Size of
motor.
H.P.
4H.P.
li H.P.
3 H.P.
6 H.P.
9 H.P.
Revs, per min., empty
Revs, per min., full load
Starting torque, in Ib.
feet
1,450
1,320
57
1,450
1,335
65
1,450
1,350
137
1,475
1,380
123
975
910
570
970
900
690
Torque at full load, in
Ib. feet
264
440
1 105
1 200
2700
4350
Pressure in volts
Amperes in each cir-
cuit, empty
60-5
1'3
60
4
57
7
63
7'5
61
20
67
25
Amperes in each cir-
cuit, full load
2'5
8
13'8
IS
59
86
Power absorbed at no-
load in watts
Power absorbed at full-
load in watts
105
325
670
346
1 900
404
2940
6620
10400
Output in brake H.P.
Output in watts
Efficiency
0-23
170
527
0-49
368
55 /
'l-5
1,140
60 7
2,208
757
7-1
5,300
807
11-5
8,600
83%
Weight of motor com-
plete in Ibs.
92
132
220
330
608
925
Some idea of the data of American three-phase motors may
be gathered from Table C C, which is taken from the Columbian
Exposition Supplement to the Engineering Review.
Table C C. Data of American Three-phase Motors.
4 H.P.
i H.P.
1 H.P.
5 H.P.
50H.P.
Apparent consumption in watts
Amperes ivr circuit loaded . . ,
230
1-4
518
4-0
985
8-0
4,380
36
40,200
280
60
60
60
60
60
Frequency .. ..
50
50
50
50
50
Speed (unloaded)
2,380
1,490
1,490
1,490
745
Speed (loaded)
2300
1,400
1,375
1,395
725
Efficiency
71%
75%
84%
91%
dumber of poles .
2
4
4
4
8
"Weight in pounds
396
1,386
2,068
5,390
26,400
4-5
15
150
Amperes er circuit at starting ...
50
400
5,650
50,000
Size of motor.
v ;/
290 ELECTRIC MOTIVE POWER.
Messrs. Johnson and Phillips have built for use at the Sheba
Gold Mines some two-phase alternators which embody an in-
vention of Mr. Gisbert Kapps. The construction (see Fig. 168)
is similar in general appearance to that of Mr. C. E. L. Brown's
machines, the field magnets being of similar design. The
armature coils, however, which are, of course, arranged around
the outer and stationary part of the machine, are not symmetri-
cally placed with reference to each other, but the top half of
FlG. 167. Allgemeine Electricitiibs Gesellschafo Asynchronous Polyphase
Motor.
the coils is set with an angular lead of 90 degrees with respect
to the lower half. The two form separate circuits with cur-
rents in quadature, and can be used as distinct machines if
required.
One of the advantages claimed by the inventor for this
arrangement is that an accident to one of the circuits will
probably leave the other uninjured, and so prevent a complete
KAPPS TWO PHASE ALTERNATOR.
291
breakdown of the machine. In fact, an alternator thus con-
structed is equivalent to two single-phase machines of half its
output. The design tends to decrease the cost of construction
and to economise space.
292
ELECTRIC MOTIVE POWER.
59. WINDING; STARTING TORQUE ; POWER FACTOR.
One of the chief reasons for using polyphase currents is that
they admit of motors which are both self- exciting and self-
starting ; and in many cases the costly and troublesome brushes
and collecting rings may be done away with.
To obtain the best results it is necessary to reduce tht
exciting current to a minimum. This is accomplished by
FIG. 169. Grooves for Windings of FIG. 170. Grooves for Windings of
Polyphase Machines. Polyphase Machines.
T
FIG. 171. Diagram of Construction of Polyphase Motors, showing Holes
for the Windings.
decreasing the air gap to a mere mechanical clearance by
bedding in iron the windings on the stationary and rotating
parts. The coils are sometimes laid in grooves as in Figs. 169
and 170, and sometimes wound in tunnels as in Fig. 171.
Grooves are, perhaps, the best, since they cause less magnetic-
leakage. When the motor is designed without brushes, the
line current is supplied to the fixed part. This design is chiefly
TORQUE OF POLYPHASE MOTORS. 293
applicable to small motors. For large designs it is usual to
arrange the exciting coils in the revolving part of the machine.
This necessitates brushes and rings, it is true, and consequently
simplicity of design is departed from. The chief point gained
is that the losses due to hysteresis, eddy-currents, and self-
induction are practically limited to the relatively small moving
part of the machine ; whilst the massive stationary portions
are magnetised by currents of frequency equal only to the
difference between the speed of the revolving coils and that of
the rotary magnetic field.
When large polyphase motors are designed to work with the
line current in the stationary part, it is usual to connect the
ends of the revolving coils to collector rings on the shaft, and
to close them through separate resistance coils. In this way
the speed and torque of the motor can be regulated with com-
paratively small waste of power.
In the most recent designs the resistance coils are built into
the rotating part and are thrown in and out of circuit by a
lever actuating a device similar to a friction clutch. It is
important to notice that a mere impedance coil will not
answer the required purpose, since its self-induction causes a
lag in the current, and therefore may increase rather than
diminish the starting current. A non-inductive resistance
coil must be used, the function of which is merely to regulate
the current induced in the closed coils. It is found that there
is one value of this current which corresponds to a minimum
line current for each torque, and therefore gives the motor a
maximum power-factor a point of immense importance when
a number of motors are running off a common power station.
By suitably proportioning the motor, the initial torque can
be made as large as required, but, if high efficiency and good
speed regulation are required it should not usually exceed
about three times the running torque.
The relation between torque and current is well denned in
Figs. 172 and 173, which are taken from a paper on Polyphase
Transmission* by Dr. Louis Bell.
* Electrical World (New York), March 17, 1894.
294
ELECTRIC MOTIVE POWER.
In Fig. 172 is shown the relation between the static torque-
and current for a 10-H.P. (A) and for a 5-H.P. (B) three-phase
motor.
Curve Aj shows the effect of varying the resistance in tha
short circuited coils when the pressure is kept constant.
90
60
I s0
/
20
20 40 60 80 IOO 12
Weight on Break Arm in Ibs
FIG. 173. Curve A: Relation between Current and Torque with a
Properly Adjusted Resistance in Series with the Short- Circuited Coils.
Curve B : The same, with no Resistance.
Fig. 173 shows two curves taken from a 10-H.P. motor.
They connect amperes in the line with torque. In B no
resistance is placed in the closed-coil circuits. In A a care-
fully adjusted resistance is added, with the result that the
current for a given torque is reduced to about one-half of that
x2
293 ELECTRIC MOTIVE POWER.
required in B. The importance of a starting resistance is
obvious.
The initial torque of a well-designed continuous-current series-
wound motor is about six times the running torque ; and,
therefore, a polyphase motor requires to be, relatively, of about
twice the capacity for similar starting power; yet, since the
polyphase design is the more compact, there is practically no
90
C
80
70
50
10
FIG. 174. Curves showing Relation between Power Factor and Output
in Polyphase Motors.
difference in the floor space occupied. Experience undoubtedly
shows that the polyphase machine is the cheaper to build
and the less costly to maintain in good running order. The
power factor of polyphase motors varies with the load and
within wide limits ; but at from half to full load it appears
to average from 75 per cent, to 94 per cent. There is thus
POLYPHASE AND CONTINUOUS CURRENTS. 297
no difficulty in running a number of motors upon the same
circuit.
The variation of the power factor of a four-pole 15-H.P.
motor at 50 cycles is shown in Fig. 174 by curve A; that of a
5 H.P. motor of similar design by B ; and that of a 5-H.P.
motor, specially designed to give a high power factor, by C.
It is sufficiently evident that the requirements of com-
mercial working are met in these machines.
60. COMBINATION OF POLYPHASE AND
CONTINUOUS CURRENTS; RECTIFIED CURRENTS.
It is sometimes urged that alternate currents are not
suitable for charging accumulators. In a sense this is true,
FIG. 175. Diagram of Gramme Armature, designed to work as a
Polyphase Continuous- Current Converter.
A, B, C, Polyphase Mains, a, 6, Continuous-Current Mains, coupled for
charging accumulators. The field magnet coils may be excited separately,
or in shunt to the accumulators.
but there are two ways in which they can be utilised for this
purpose. They possess some interest in a transmission of
power plant. Most batteries are useful for dealing with
lighting during the light load periods.
If an ordinary two-pole continuous-current dynamo have three
connections made to the armature coils at intervals of 1 20deg.
298
ELECTRIC MOTIVE POWER.
each, and these be joined to rings in connection with the
mains of a three-phase system, the armature will run as a
motor (assuming the field to be separately excited), and a
continuous current may be collected at the commutator, which
can be utilised for charging accumulators.
FIG. 176. Rectified Alternate Current.
This machine may be described as a polyphase continuous-
current converter. It is a practical device. Most dynamos can
be readily adapted for this purpose, but if a high efficiency
of conversion be required it will be necessary to make a special
design. A general idea of the arrangement may be gathered
from the diagrammatic sketch in Fig. 175.
FIG. 177. Ferranti Rectifier, as used at Portsmouth.
Another method of using an alternate current for charging
batteries is to " rectify " the negative waves. The resultant
current may be diagrammatically represented as in Fig. 176,
in which the dotted curves below the time line have been
EECTIFIEES. 299
rectified. The curves show the instantaneous values of the
current (or pressure), and the effective value is J- of that
of the maximum ordinate.
The reversal of sign is accomplished by a two-part commu-
tator running synchronously with the alternator, and driven
by a small synchronous alternate-current motor. (See the
'Thomson-Houston self-exciting alternator. Fig. 115, p. 232.)
Fig. 177 shows one of the Ferranti rectifiers used at Ports-
mouth for running arc lamps in series on a 10-ampere circuit
having a frequency of 50 r ^> per second.
A rectified current appears to be admirably adapted for
serving arc lamps, because the rhythmical waves of which it is
composed assist the feeding of the carbons.
It is possible that rectifiers may prove to be useful details of
a power plant.
CHAPTER IX.
ELECTEIC TRANSMISSION OF TOWER IN MINING
OPERATIONS.
61. Introduction. 62. Engine House and Equipments. 63. Shaft
Cables. 61. Underground Cables ; Junction Boxes ; Switches
and Cut-outs. 65. Uninsulated llcturns ; Safety Cables. 66.
Motors and Driven Machines ; Selection of Type of Motor ; Con-
tinuous and Polyphase Currents. 67. Safety Motors ; The Mining
Motor of the Future.
61. INTRODUCTION.
PERHAPS the most obvious field for the utilisation of electricity
in power work is to be found in mining. At all events, the
first practical plants were applied for mining purposes, and by
far the greater number of large electric motors running in Great
Britain to-day are used in this connection. The superiority of
electricity as compared with compressed air or hydraulic power
for driving dip pumps and other underground machinery was
recognised as soon as the electric motor was discovered. But
it was not until about 1885 that the new plant was well enough
engineered to be cheap and reliable. The first application of
sufficient magnitude to demonstrate indisputably the possi-
bilities of the electric motor for mining work was made at Messrs.
Locke and Go's, St. John's Colliery, Normanton, by the General
Electric Power and Traction Company (Immisch and Co.), to
the designs of the author. The motor was of about 60 brake
horse power, and worked a set of ram pumps raising 120
gallons of water per minute through a vertical head of nearly
900 feet. It was an assured success from the start, and
although modifications and improvements have since been
introduced in many of the details, the general method still
302 ELECTRIC MOTIVE POWER.
obtains for continuous-current mining work. The applica-
tion of polyphase currents has opened up fresh possibilities,
and largely extended the scope of electric power work, by
obviating the need for commutators and brushes, and there-
fore removing the chief objection to the use of motors in
collieries. The author confidently regards polyphase motors
as essentially the machines of the future for mining work.
In the previous chapters this subject has been necessarily
discussed in a general way, so as to include all varieties of
plants. This chapter is confined to the consideration of mining
work and its special requirements.
There is a wide difference between collieries and metalli-
ferous mines in the character of the work ; and, indeed, the
local conditions of different mines vary so largely as to require
special treatment in almost every case. But the main
difficulties peculiar to mining work, i.e., which do not usually
obtain with surface plants, may be classified under three
heads :
(a) "Falls" from roofs and sides, and "creeping" of the
floors.
(6) Water, either continuous or intermittent,
(c) Explosive gases.
These may occur singly or conjointly, and evidently require
properly selected plant and careful disposition of mains, junc-
tion boxes, switches, cut-outs and machines. What is suc-
cessful at one pit, or part of a pit, is not necessarily so
at other places ; and hence various methods are employed
some good and some indifferent. Only an engineer experi-
enced in this class of work is able to specify with fair
probability of success the best kind of material and most
suitable method of erecting plant for each case. Much
defective work has been done from want of practical
acquaintance with collieries and mines, although the plant
supplied has been usually good of its kind. That bugbear of
competition, the lowest tender, has also much to answer for
here as well as in other departments of electrical engineering;
ELECTRIC WORK IN MINES. 303
and the practice of asking contractors to tender to their own
specification instead of to that of an independent consultant
has largely contributed to the breakdowns, which are far more
frequent than need be. The absurdity of such a course is
rendered the more apparent when it is considered that however
up-to-date the mining engineer may be, he cannot possibly
have such a close acquaintance with the quality and classes of
electric cables, different points in dynamos and motors, and the
various details of an electric plant, as the expert who gives his
entire time to such work. And, moreover, the expert is not
hampered by patents or special types of machines, etc., as a
contractor is very likely to be, especially if he is also a
manufacturer.
It is proposed to consider here some of the chief difficulties
peculiar to mining work, and to examine the methods most in
vogue to meet them, and also to suggest, as far as possible, the
best plant and its most effective disposition for working under
various conditions.
It is convenient to treat this part of the subject under the
following divisions :
(1.) Engine House and Equipment.
(2.) Conductors, Shaft, and Underground Cables, Junction
Boxes, Switches and Fuses.
(3.) Motors and Driven Machines.
These will be considered in separate sections.
62. ENGINE HOUSE AND EQUIPMENT.
The engine-house will generally be upon the "surface,"
although in some cases, where a steam-engine is already at work
near the pit bottom, it may be necessary to erect a dynamo
below ground. Electric plant frequently plays so small a part
in the main machinery of a colliery that it is not permissible to
provide a separate house for the dynamo. In such cases the
winding-engine house or the fan-engine house will probably be
selected. If the fan-engine has a margin of power, and is kept
304 ELECTRIC MOTIVE POWER.
running at a constant speed, it may be possible to couple the
dynamo to it through a fast and loose pulley. But this is not
a common occurrence, nor is the arrangement always advisable.
The fan forms a steady continuous load, and its engine should
be carefully proportioned, both as regards size and speed, to give
the most efficient running. And further, since the safe work-
ing of a colliery depends to a very large extent upon the ventila-
tion, many mine managers very properly refuse to allow fan-
engines to be put to any other work than that of driving the fan.
It may be assumed, then, that the dynamo (or dynamos) will
be driven by an independent engine. In the early days of
electric work in mines it was frequently necessary to use any
odd engine that happened to be available at the time; and
hence some very curious combinations. The author has seen
a modern efficient dynamo coupled by belting to a large slow-
speed engine of antiquated type, rendered still more inefficient
by being supplied with wet steam at less than 401b. pressure,
so that the high efficiency of the dynamo was practically
annulled.
Managers, however, are beginning to recognise the saving in
coal and steam made by using high-pressure boilers and quick-
running engines, and the electrical engineer has now little
difficulty in arranging for suitable steam plant. Having regard
to the fact that the fuel burnt at collieries is usually the most
unsaleable there, and frequently almost dust, mechanical
stokers are of special use. Vicars, Proctors, or any of the
well-known types, answer the purpose admirably, and will be
found to effect economy in labour. The type of boilers will
depend upon the class of water and upon local circumstances.
Generally, however, Lancashire boilers, with cross tubes, give
the best all-round results, and have the advantage of being
easily set and repaired by ordinary labour. The working
pressure may vary from SOlb. to 1201b. per square inch;
whereas multitubular boilers, although admirable for raising
steam at short notice, are comparatively difficult to clean out,
and require much more careful attention and skilled labour to
effect repairs. The same remark applies to water tube boilers
in connection with this class of work.
STEAM DYNAMOS.
305
In most cases where the engineer has a free hand,
and the pressure does not exceed, say, 500 volts, he will
advise steam dynamos i.e., engine and dynamo directly
coupled (see Fig. 178). This arrangement gives a positive drive,
reduces the space occupied to the smallest dimensions, effects
considerable saving in first cost, and gives increased facility for
repairs ; while a stand-by set can be compactly placed ready
for instant use at a moderate increase in the cost of the
running plant. Granting the use of a high-speed engine, the
question of open or closed type arises. There are various argu-
ments in favour of each. The open type (see Fig. 178) has the
advantage that all the rods and bearings are in full view, and
FIG. 178. Steam Dynamo and Open-Type Engine.
can be inspected while the engine is running, and also that it is
readily got at to make repairs. But it is likely to be affected
by dust, and is to some extent liable to accidental damage from
external causes.
The closed type (see Fig. 179), on the contrary, is completely
protected from dust and chance external damage, and the crank
shaft splashes into a lubricant in the crank chamber, thus
ensuring lubrication so long as the oil is maintained at the
proper level. Messrs. Willans and Robinson supply with their
well-known closed-type engines a sight gauge, which shows
continuously the height of the lubricant in the chamber. The
speed of the engine will be selected with reference to its
306 ELECTRIC MOTIVE POWER.
dimensions and that of the dynamo to which it is to be
coupled. The number of revolutions will be large compared
with those to which mining managers are accustomed, being
from about 300 to 500 per minute. The question of single'or
double-acting engines is an open one, and both sides are admir-
ably championed. Perhaps both types, if properly made, are
equally good.
The type of dynamo will depend very much upon the class
of work. The discussion of the various windings compound,
series, shunt and separate excitation in 14, page 59, gives
the special features of each.
FIG. 179. Holmes-Willans Steam Dynamo and Closed-Type Engine.
The pressure, as already suggested, will not be much higher
than about 500 volts. A number of manufacturers build
excellent machines, and it is easy to select a suitable dynamo
or motor if a fair price be paid.
The conditions governing the choice of steam and electric
plant are similar to those detailed in 1, page 7. In plants where
the work comprises pumping, hauling, coal-cutting and lighting,
the generators should be capable of parallel working, feeding
omnibus mains. But if there are only large motors, each
coupled to, say, pumps or other independent machines, then
it may be advisable to run separate pairs of mains to each
SHAFT CABLES. 307
motor, and to have a separate generator to each circuit. If
the loads permit of one type of motor and one type of gene*
rator, a couple of spare machines will be sufficient to cover
all. For driving pumps series winding is usually preferable
for both dynamos and motors if a continuous-current system
be adopted.
If polyphase currents be used, the same suggestions are
applicable, with suitable reservations. The pressure at the
generating station may be restricted to about 500 volts, and then
transformers will not be necessary for stationary motors of from
10 B.H.P. and upwards. But in coal-cutters and rock-drillers
this pressure is too high for the men to handle the machines-
with comfort, and it will be advisable to use step-down trans-
formers to reduce it to about 50 volts. At this pressure a
" shock " will be impossible, and the machines can be safely
worked even in the dampest places.
In some cases of long-distance transmission it may be advis-
able to use a much higher pressure in the " line " between the
generating station and the step-down transformers. The ques-
tion then arises whether the line pressure should be reduced
to, say, 500 volts at the pit bank, be supplied at this pressure to
large stationary motors, and be further reduced for small or port-
able machines. These are questions, however, which must be
decided for each case upon its merits, and a mine manager will
do well to take the opinion of an independent expert before
signing a contract for plant.
63. SHAFT CABLES.
The classes of conductors suitable for the severe conditions-
of mining work are not very numerous, and differ chiefly in the
kind of insulation, and the means employed to protect them
from mechanical injury and from the effects of water,
Broadly, there are two kinds of insulation which have stood
the test of time, viz., vulcanised rubber and bituminous com-
pounds.* The former is costly and is thus better adapted for
the lighter classes of cables, say up to strands of 19/15 S.W.G.,
These are fully discussed in 18, p. 84.
308 ELECTRIC MOTIVE POWER.
which, owing to their position, do not require to be covered
with a coating of lead or armoured with steel strip or galvanised
iron wire. The latter class is cheaper and hence is more suitable
for large trunk mains ; but, since it rapidly loses its insulating
properties if in contact with water, it is necessary to encase
the compound with lead, which should be armoured to protect
it from injury. The best form of bituminous cable is made
concentric (see Fig. 180). The centre conductor is doubly
guarded, so that if the metal sheathing be cut through, only
the outer conductor is earthed, and the cable as a whole is
workable until an opportunity occurs for repairing the injury.
FIG. 180. Armoured Concentric Cable, with Lead-Covered Bituminous
Insulation
The author finds it expedient, even in large plants, to limit
the sizeof each conductor to, say,a cable of 19/14 S.W.G. strands;
and, if this be of insufficient cross-section for the current, to
duplicate the conductors and connect them to omnibus bars.
With this provision, an accident to one conductor does not
cause a complete stoppage, for the damaged cable can be
disconnected until the fault is localised and repaired. (It is
oftentimes a matter of impossibility to make repairs during
the drawing of coal, and hence the importance of providing
spare conductors.) Another advantage is that small mains
are relatively light, and are, therefore, easily handled and
SHAFT CABLES. 309
fixed in position. And, further, the cost of repairs to the
smaller sizes of cables is generally much less than to the larger
ones, owing to the greater ease with which the joints can be
made.
The methods of running cables down shafts and fixing them
in position differ in almost every case. Pit shafts are usually
of circular form, sometimes driven through the live rock, some-
times built round at intervals with courses of brick or stone laid
on cast-iron cribs, sometimes faced with heavy timber walls,
and occasionally lined with cast-iron sections through quick-
sands or strata heavily charged with water. If wooden
" conductors " are used to guide the cages, heavy cross bearers
of timber are built into the sides of the shaft at intervals to
carry them. When iron rope guides are used the shafts are
practically void of timbering.
These different conditions evidently demand different
methods of supporting the cables.
In the first place, it is absolutely essential to guard against
falling coal and stones, either from the cages or from the sides
of the pit. The best position for placing the cables will,
therefore, be largely determined by the shape of the cage, and
whether its sides are covered up so as to restrict the falling of
pieces of coal to the open ends. Again, stands of iron pipes
already placed may limit space still further. In general it is not
advisable to run electric cables near to pipes, because work-
men repairing the latter may damage the cables. Another con-
sideration of importance is whether the up-cast or down-cast
pit is the better adapted for the purpose. If the " winding "
be done from the down-cast, as is usual, it may be convenient
to use the up-cast. But care must be taken that the up-cast
air is not laden with any erosive vapour, such as is sometimes
the case when the exhaust from an underground engine and
the gases from a furnace burning coal containing a large per-
centage of sulphur, are turned into the up-cast. The author
knows of one case in which a pair of lead-covered cables
run in such a pit were corroded through in dozens of places in
the course of a few months. In some soils there are found
erosive agents that attack iron and rapidly rust it away, and
310 ELECTRIC MOTIVE POWER.
in others a similar action takes place with lead. Generally
it has been the author's practice to use the down-cast shaft ;
but there is no rule, and in all cases it is possible to ensure
success by making suitable arrangements.
The plans adopted for supporting cables in shafts differ
widely. In all cases, however, where it is desired to give the
work a permanent character, the cables must be entirely
encased in wood, run in iron pipes, or heavily armoured. These
three methods are not always equally applicable, for local con-
ditions may make one of them the cheapest or most desirable.
If there is a set of, say, 4in. pipes already erected in a shaft,
and it is desired to run a pair of, say, 19/16 S.W.G. cables
down them, and the depth is not great, a pair of vulcanised
rubber mains may be suspended in them from earthenware
insulators. The weight on the supports will not usually be
great, for the cable will generally bend from side to side, and
thus may sometimes nearly carry its own weight if sufficient
slack be allowed. In running cables down pipes it is advisable
to insert a small flexible iron rope, and use this to haul in the
insulated conductor, which should be payed out from the drum,
perpendicularly into the centre of the pipes, over a wheel of
sufficient radius. This method prevents damage to the covering
of the cable. The interior of the pipes should be scoured to
clean off sand from the cores, or the insulation will inevitably
be abraded during the hauling-in.
If the pipes be of large diameter, and the depth too great
for the mechanical strength of the cable, it must be sup-
ported at intervals. This may be done in several ways, but
it will be necessary to break the continuity of the iron pipes
in order to insert wedges, clamps, or similar devices.
It may be better, then, to adopt a wooden casing which will
support the cable along its whole length. In using wood, how-
ever, care must be taken that the section is of sufficient strength,
and that the " lengths " are spiked firmly to the pit sides. The
grooves may be cut in the face, as shown in Fig. 181; or in
the sides of the casing, as in Fig. 182, which illustrates a method
used most successfully by the author in a number of mines.
SHAFT CABLES.
311
The covering boards may be held in position by coach screws.
This enables an examination of the cables to be made at any
spot which is oftentimes a convenience. The grooves should
be cut an easy fit for the cable, which will then be perfectly
K 10
FIG. 181. Wood Casing for Pit Work.
supported, and only a light attachment at the top will be
necessary. It is always advisable, however, to loop the top
ends securely round earthenware insulators firmly carried at
or near to the surface.
FIG. 182. Wood Casing for Pit Work.
Concentric cables lead-sheathed and armoured are so stiff
that they may be clamped directly to the pit sides, and then
form strong compact work. As they are very heavy, there is
need for strong brake gear on the surface to pay them out by,
Y2
312
ELECTRIC MOTIVE POWEE.
as they cannot be fastened in position until the whole length
is down the pit. It is advisable with very heavy cables to
lash ropes at intervals, and pay them out at the same rate,
thus relieving the top end of the cable of part of the weight.
This class of cable is steadily finding favour for pit work.
The Electrician,
Sectional Elevation. One-third full size.
Plan (part section). One-third full size.
FIG. 183. J. Davis and Son's Junction Box, for use in Mines.
On no account should joints be permitted in new shaft
cables, although it may be necessary to make repairs in old
ones. A cable with continuous insulation is much more likely
to stand the wet and exposure of a pit than one with joints
made with a different dielectric from the rest of the insulation;
UNDERGROUND CABLES. 313
the more so as the joints will probably be defective from the
beginning. And it should be recollected that jointing is an
extremely difficult operation in a shaft, owing to falling water,
the cramped position, and the strong draught of air which
together render soldering an impossibility in many cases, and
often make the insulation uncertain owing to the presence of
moisture. Of course it is possible, assuming time to be allowed,
to provide special apparatus which, in the hands of skilled men,
will enable excellent work to be done ; but breakdowns usually
occur unexpectedly, and frequently have to be made good by
the resident staff with such simple materials and facilities as
may be at hand.
In most cases the author prefers to arrange junction boxes at
the top and the bottom of shafts, so that the shaft cables can
be severally tested independently of the surface and underground
work. These boxes must be housed in dry places, secure from
mechanical injury. For this purpose there should be sufficient
free length of cable at top and bottom to allow the boxes to be
placed well away from the drawing decks and pit bottom. An
effective junction box manufactured by Messrs. J. Davis and Son
is shown in Fig. 183.
64. UNDERGROUND CABLES; JUNCTION BOXES;
SWITCHES AND CUT-OUTS.
Each " district " is usually supplied from an independent pair
of conductors coupled at the pit bottom to an omnibus bar or to
a separate pair of shaft cables.
These conductors are, therefore, of small size, not often ex-
ceeding 19 strands of No. 16 S.W.G. They are carried on the
"sides" or "roofs," being supported by wooden cleats or
earthenware insulators, or buried in the " floor." The choice
of the three methods will be determined by the peculiarities
of the "level" in which they are run. The class of insu-
lation will depend both upon the method of erection and the
difficulties to be dealt with.
In dry roads, well supplied with timber props and cross
bearers, a light vulcanised rubber cable, carried in wooden cleats
314 ELECTRIC MOTIVE POWER.
or on insulators, will prove to be cheap and efficient. An occa-
sional fall of roof or sides will not as a rule cut it if a little
slack be allowed between the supports ; and " creeping " of the
floor will not affect it. Indeed, in the majority of cases where
long lengths of small conductors, about 7/16 S.W.G., have to
be carried to the " faces," this is the only practicable method,
from the simple consideration of first cost.
Wood casing is out of the question for " road-work," except
for the lighting circuit near the pit bottom, not only because
of its cost, but also because of the instability of most of the
" roads."
In main engine planes which have no " weight " upon them,
permanent work may be made of the erection ; and it will
generally pay to bury the cables beside the metals and to
cover them loosely. But a rough wooden trench with a cover-
ing board should be laid to receive the cables, unless they are
armoured, for otherwise an unlucky blow from a pick may cause
a breakdown. If heavily armoured concentric cables, as shown
in Fig. 179, p. 308, are used, it is sufficient to bury them from
about Gin. to 12in. below the surface of the road, well to one
side, where they will not be disturbed during repairs to the
metals and roads. If conductors are carried along "travelling"
roads, it is specially necessary to secure them from damage
at the hands of the miners, who are sometimes inclined to get
" lightning " from them by means of their picks. If the road be
dry and in a fairly settled condition cables may be laid in fine coal
dust, covered by rough boards lin. thick, and then protected by
a layer of coal dust of about 6in. deep. This forms a very safe
and cheap bed for hemp-braided vulcanised rubber cables, or
for lead-covered cables served or braided with hemp. It is
specially serviceable in travelling roads, or where the con-
ductors are laid for a temporary purpose.
Whatever the class of cable or the method of laying it, how-
ever, the conductor should not be in continuous lengths of more
than about 500 yards, in order that a fault may be readily local-
ised. At the junctions of sections cast-iron boxes (see Fig. 183,
p. 312) should be placed, with screw terminals on porcelain bases,
through which the necessary connections can be quickly made or
UNDEEGEOUND CABLES. 315
unmade. On no account should cut-outs be placed at these
points unless special provision be made to enclose them in flame-
tight boxes ; they should be confined as far as possible to the
generating station and pit bottom.
At the far ends of the levels where the distributing mains
are joined to the feeders, it is good practice to place cast-iron
junction boxes in the "gates," so that any or all of the
distributors may be coupled up according to requirements. It
is imperative, if cut-outs be used here, as is sometimes
necessary, that they be placed in flame-tight boxes, for this
position is close to the coal faces, from which gas may be given
off at any time.
The "distributors " are necessarily of a temporary character
and will be shifted as the work progresses. They must therefore
be light and flexible. If convenient they may be carried upon the
props, and in the absence of timber may be laid beside the roads,
unless they are hung on rough iron spikes driven into the rock.
In any case they will often be subjected to rough usage. For
attachment to movable machines, such as coal cutters and
rock drills, it is usual to provide either concentric or twin cables,
insulated with vulcanised rubber and braided with steel wires.
Either of these can be made sufficiently flexible, and they are also
strong enough to stand being hauled across rough shale and
coal.
If a distributor feed a dip pump it should be erected in a
semi-permanent manner ; since such pumps are liable to be
drowned-out, and the plant may have to be withdrawn several
hundred feet or yards at short notice. In such cases the con-
ductors should be brought back with the motor, and not cut.
They should be coiled and hung up at the pumping station,
being uncoiled again as the water recedes. The best insulation
for this work is vulcanised rubber well braided with hemp and
ozokerited over all.
For a polyphase current system it is necessary to run three
or four conductors in place of the two required for a continuous-
current or single-phase alternate system. For permanent work
three conductors may be built into a concentric cable, which
316
ELECTRIC MOTIVE POWER.
may be lead-covered and armoured. With a four-wire system
two concentric cables of two conductors each are preferable.
The method of erection is in no respect different from that
adopted with continuous-current working. The three wires are
carried practically as readily as two.
FLAME-TIGHT SWITCHES, ETC.
317
The use of switches and fuses below ground in places likely to
contain explosive gas requires careful regulation, and is likely to
become the subject of special legislation in the future. The
author states emphatically that, in his opinion, no switch, cut-
out, junction box, or resistance frame that is not absolutely flame
and dust-tight should be allowed in a coal mine where naked
318
ELECTRIC MOTIVE POWER.
lights are prohibited. It is madness to forbid the use of a naked
light and yet to allow the types of switches and'cut-outs some-
times found in pits.
To ensure absolute freedom from firing gas with a continuous-
current motor is perhaps impossible, but nojsuch difficulty
should be found with small stationary devices, such as switches,
cut-outs, and junction boxes. It is merely a matter of expense,
and proper precautions should be insisted upon in all permanent
plants.
(D
CD
[CD
CD
CD
CD
SLATE
0)
CD
0)
CD
'|OD
CD
FIG. 184B. Showing Plan of Slate Base and Attachments to the Resistance
Coils in Figs. 184 and 184A.
In Figs. 184, 184A and 184s are shown various views of Davis's
Mining Switch with resistance coils attached. It is used for
starting and regulating motors. The whole is enclosed in an
iron case, and the switch contact pieces break circuit in a gas-
tight compartment.
65. UNINSULATED RETURNS; SAFETY CABLES.
It has been the custom at some pits to use old iron ropes
as returns. These are simply laid along the roads or hung up
by hooks to the side props. The practice, however, is not to be
recommended in pits where there is any chance of gas, and in
a large plant, with a pressure of 500 volts, it would in any case
be impossible. The author coupled a return in this manner at
Andrew's House Pit, Durham, in 1887, the arrangement being
UNINSULATED RETURNS. 319
adopted simply from considerations of first cost. The pressure
at the dynamo terminals averaged 225 volts, and the po\\ er in
this part of the circuit never exceeded 8 E.H.P. The rope lay
for a considerable part of its total length of 1*25 miles in
water. The leakage of current, inevitable in a pit, decomposed
water at various places, and the iron corroded rapidly at the
junction to the copper return near the motor, and small
sparks could often be obtained between the rope and the tram
metals near the pit bottom, thus showing that the iron rope,
although lying on the wet ground, did not make good " earth."
The danger was recognised and caused no difficulty ; but if the
pit had been gaseous, it is probable that an explosion would
have resulted.
A bare separate return, if justifiable at all, can only be so on
account of cheapness ; but the apparent saving is in most cases
more than counterbalanced by after troubles.
If, however, a system of concentric mains be used with the
outer conductor in metallic contact with iron or steel wire
armouring,* the conditions are altogether different ; and prob-
ably as great an immunity from the danger due to a broken
conductor can be obtained by this arrangement as by any
of the patented safety cables.
There are two classes of bare return concentric cables in use.
They are shown in Figs. 185 and 186. The former has a lead
covering, which is squirted around a copper conductor, the two
together forming the outer or return circuit. Armouring can
be applied outside, and this adds to the conductivity while pro-
tecting the soft lead, whose chief function is to keep water
from the insulation between the centre and outer conductors.
The second class is cheaper, and the return circuit is formed
simply by the armouring, which is placed directly upon the
insulation. It is only suitable for use in dry places, where it
will give good results.
The chief advantages offered by these cables, in con-
nection with mining work, is the security they give against
* For example, the concentric cable system of Messrs. Mavor and Coulson.
320 ELECTRIC MOTIVE POWER.
external sparking, and their mechanical strength, owing to
which they may be stapled to rough walls, like gas piping.
There are also conductors which may be collectively classed
as " safety cables." In all of them the object is entirely to
FIG. 185.
Concentric Cable with uninsulated outer conductor consisting of a spiral of
sheet copper under the lead, the lead, and the steel armouring.
obviate sparking at the point of rupture when an active con-
ductor is cut in two. The general method is to provide a
small auxiliary cable in parallel to the main conductor. This,
J n the event of a fall cutting the cables, is arranged to break
FIG. 186.
Concentric Cable with uninsulated outer conductor, consisting of a spiral
of sheet copper under the steel armouring no lead.
either before or after the main conductor is broken; and in each
case actuates a magnetic cut-out which opens the main circuit.
The idea will be best understood by reference to some of the
better known solutions of the safety-cable problem.
SAFETY CABLES. 321
Mr. LI. Atkinson, of Messrs. Easton, Anderson and Goolden,
was the first to patent a cable of this class. It was not
designed for concentric wiring, and hence two wires are
required for each circuit. The cable (see Fig. 187) consists of
two concentric conductors in parallel, insulated from each other,
excepting at the main terminals of the circuit to be protected.
The current therefore is in the same direction in each conductor.
The outer, which is designed to carry the larger part of the
current, is of any ordinary make. The inner is constructed
of fine wire in the form of a continuous cylindrical coil, the
outer diameter of which is covered by insulation, and forms
the core around which the main conductor is laid. It is
assumed that when a stone falls on the cable the outer con-
FIG. 187. Atkinson Safety Mining Cable, showing the outer conductor
cut through and the inner one drawn out.
ductor, offering much resistance, may be cut through; but the
loosely-coiled centre conductor will be simply drawn out of
the insulation. The entire current will then pass through the
fine wire, and blow a magnetic cut-out in the engine-room or
other convenient place; the arc being thus transferred from
a possibly dangerous spot to a safe one. The efficient action
of this cable depends upon two conditions :
(1.) Perfect insulation between the inner and outer con-
ductors.
(2.) The continuity of the fine wire circuit being preserved
during the fall.
322 ELECTRIC MOTIVE POWER.
In order to prevent an accidental contact between the two
conductors interfering with the working of the cable, the in-
ventor provides a resistance in series with the fine wire at
its negative end, so that the fall of pressure is less along the
inside than along the outside. The result is that there is
always a difference of pressure between the inner and outer
conductors at each part of the cable. And a short circuit
between the two at any point causes an increase of current
in the fine wire which operates the magnetic cut-out.
Generally it is found that cables hung lightly, with plenty
of slack, are dragged down and buried without suffering any
damage other than slight surface abrasion ; but if they are
firmly fixed they may be cut through as if with a knife.
It, may, therefore be reasonably questioned whether a fall which
is sufficiently heavy to cut a stout cable in two will not sever
the fine conductor before the spirals have time to draw out.
In recent installations a small separated insulated wire has
been hung (beside the main conductor) with a few spirals
twisted at intervals so as to allow a ready increase of length in
the event of a fall or of any undue strain. This is found to
be cheaper than the compound cable, and to give equally good
results. It should be mentioned that Mr. Atkinson regards
the cable as of more importance as a preventive against firing
timber from arcs than as an absolute means of preventing
sparks. The author is in accord with this view. For the time
taken to move the detaching mechanism on the surface will
chiefly determine the spark at the break in the cable, though
its effect is limited by the resistance of the unbroken fine wire
in parallel with the main wire.
The Charleton cable, patented by Messrs. R. J. Charleton, of
Newcastle-on-Tyne, is of similar make, but the inner conductor
is merely a small wire, about No. 18 S.W.G. The currents in
the two conductors are in the same direction. The action
depends upon the fine wire breaking before the large one, when
a magnetic cut-out is designed to open the main circuit. Suc-
cessful working depends upon the maintenance of the insula-
tion between the two circuits, and also upon the time required
SAFETY CABLES. 323
to move the magnetic cut-out levers. If this is not consider-
ably less than the period of time elapsing between the cut-
ting of the two cables it is doubtful whether sparks will not
occur almost simultaneously at the break and the cut-out. The
problem is complicated by self-induction and capacity, which
under suitable conditions may seriously affect the time required
to open the cut-outs after the breakage of the main conductor.
It will be easy, however, to experiment for any particular case.
FIG. 188. Sectional View of Met Safety Cable.
A, Armouring ; C, Main Cable ; C 1 , Auxiliary Conductor.
Another interesting safety cable is the invention of M. Nolet,
engineer of the Cockerill Company, Seraing, in conjunction
with M. Jasper, of Liege, and has been applied to several coal
mines in Belgium. It provides for a small wire insulated
and built into the cable, as in the Charleton cable, but the
currents in the two circuits are in opposite directions.
FIG. 189. Diagram of Connections of Nolet Safety Cable.
C, Main Cable ; Ci, Auxiliary Conductor ; E and E 1} Magnetic Cut-outs ;
M, Motors. Large arrows show direction of main current ; small arrows
that of the shunt current.
A sectional view showing the method of construction is given in
Fig. 188.
The fine wire is coupled up as shown in Fig. 189. The
function of the small wire circuit is to close the main circuit
through the two magnetic cut-outs (one to each of the mains).
324 ELECTRIC MOTIVE POWER.
Therefore, in the event of a breaking of the fine wire, the cut-
out will operate and open the principal circuit.
M. Nolet has recognised that repairs to cables, as generally
constructed, cannot be properly carried out without the use of
soldering irons, which are inadmissible in a mine. To pro-
vide for this contingency his cable is made in short lengths,
each section being provided with metal couplings for both
of the conductors, as shown in Fig. 190. The rings for the
subsidiary wire are shown at C', and those for the main con-
ductor at C. The couplings are made to fit together with
easy friction, and are so arranged that a sliding movement of
about one quarter of an inch is sufficient to open the auxiliary
circuit, while a considerable displacement is required to un-
couple the outer conductor. The joints are protected by
india-rubber tubes.
The construction appears to admit of a certain time interval
between the opening of the main circuit and the lifting of the
FIG. 190. Sectional View of Nolet Safety Cable, showing the Method of
Coupling-up.
magnetic cut-out, and also provides a ready means of repairing
a damaged section. But the cable must be costly, and a slow
movement of the measures, throwing weight on the cable,
might interrupt the auxiliary circuit unnecessarily. It may
be questioned whether the device would have time to act in
the event of a fall shearing the cable instantaneously, as some-
times occurs.
In the author's judgment, none of these safety conductors
gives more security than that obtainable with an armoured con-
centric one buried in the floor, or suspended loosely with plenty
of slack between the supports. If a fall occurs, it will be
brought down and buried. If the armour and outer conductor
are cut through, the incision must first take plaee on one side,
and then most probably the severed strands of the outer
conductor will be pressed against the inner conductor, and so
SAFETY CABLES. 325
blow the magnetic cut-out without opening the circuit;
because the bottom half of the outer conductor cannot be
cut through until the top half is brought into contact with the
inner one. The truth of this can be easily demonstrated by
cutting the cable through with a cold chisel and hammer.
Success lies in hanging the cable so loosely that it cannot be
cut through instantly. If this occur, it is doubtful whether the
two conductors would always be jammed into good contact by
a sudden blow, and so a spark might occur coincidently with
the blowing of the magnetic cut-out.
Another solution of the safety cable problem has been pro-
posed by Mr. Frederick Hurd. The conductors are run in iron
pipes, through which a current of fresh air is forced by a blower,
the motors and regulating devices being protected in a similar
manner. The plan is good, and, if properly carried out, would
seem to afford safety against a large variety of risks. But there
is no provision for opening the electric circuit when the pipes
are broken.
Messrs. R. B. Pownall & Son have carried the method a step
farther. In a patent dated December 2, 1893, they provide
means by which the maintenance of the electric circuit is made
to depend directly upon the air pressure in the pipes ; so that,
in the event of damage to the pipes, resulting in a leak or
in total breakage, the escape of air lowers the plenum and
opens the magnetic cut-out controlling the particular circuit.
The details of the system have not yet been made public ; but
the author is in a position to assert confidently that the scheme
is a very practical one, and meets the varied requirements of
colliery work in a most complete manner.
The danger of firing gas through a broken cable is, how-
ever, very remote. There is, so far as the author knows, no
authentic instance of this having occurred, although the possi-
bility is sufficiently evident.
The fact is that, for obvious reasons, cables are not usually
run in roads with "weight" on them, and, where this is un-
avoidable, sufficient slack is allowed to prevent the nuisance
326
SELECTION OF TYPE OF MOTOR. 327
of frequent repairs, quite irrespective of the risk of an explo-
sion, and, therefore, broken cables are rare.
With the gradual extension of electric work in coal mines for
driving portable as well as stationary machines, the risks from
this cause will be increased, and it is wise to recognise the danger
and to adopt the simple and efficacious remedies suggested by
experience. This is specially desirable with new plants.
66. MOTORS AND DRIVEN MACHINES; SELECTION
OF TYPE OF MOTOR; CONTINUOUS AND POLY-
PHASE CURRENTS.
The selection of the type of motor for any special work is
generally not difficult. An approximate estimate of the power
is easily arrived at, and a small error in its determination is
of little importance; the crux lies in estimating the average
and maximum torque. The cogency of this will be apparent
on reference to the equations for torque of motor (11, p. 43),
and to the mechanical characteristics of motors ( 14, p. 59).
For example : Suppose it is required to drive a main pump,
as shown in Fig. 191, on a continuous-current circuit at 500 volts
pressure at the motor terminals. The theoretical power in the
water is known, and the losses in rising main, pumps, gearing
and motor, are easily determined. The maximum torque will
occur at starting, when the motor has to overcome the statical
friction of the pumps and set the column of water in motion.
The average torque will be simply that due to the constant
load with full delivery of water. To meet these conditions, it
is necessary to have a motor with a magnetic field sufficiently
strong to give the necessary starting torque without undue
sparking or an excessive quantity of current ; and to give the
working load at the designed speed with the highest possible
efficiency consistent with a fair margin of power.
The motor winding should, preferably, be in series (see 14,
p. 60 ; also 23, pp. 1 16 and 121).
The chief constructional point is sufficient strength in the
armature shaft and bearings to start the pumps safely. If this
( 328 )
ELECTRIC HAULAGE. 329
be attended to the motor will be mechanically strong enough
for the running load.
Again, assume it is required to erect an endless rope hauling
plant as illustrated in Fig. 192 on the same circuit. The
various losses must first be determined, the weight of tubs,
loaded and unloaded, debited and credited according to the
grades, and a suitable allowance made for tub-wheel and
rope friction. From these data the starting and the average
torque can be determined. If the running load is fairly
constant as is generally the case with an endless rope the
series-wound motor is the most suitable, and the suggestions
made with reference to the main pumping motor are equally
applicable. The margin of power, however, requires to be
greater than with pumps, as the load may be largely
augmented at times by tubs leaving the rails. There is not
much fear of overloading during busy periods, because an
increase of torque will slow the motor and so decrease the
actual power ; but, since the current will be temporarily in-
creased, a margin for the heating effect in the windings must
be provided.
If, however, the system of haulage be a main-and-tail one,
as indicated in Fig. 193, where the motor has to be frequently
stopped, and to deal with a continually varying load, good
speed regulation and perfect control of the motor become of
more importance than efficiency. In this case a specially
designed cumulative compound motor (see 14, p. 65) may be
used, with a switch and starting resistance designed to keep
the shunt coils always in circuit during work time, and to
introduce a variable resistance in series with the armature
and series windings. Reversals of motion should be made by
means of friction clutches and gearing, and not by the motor, as
this would introduce complications which are better avoided in
pit work. The maximum torque in this case is generally that
at starting, but not necessarily, as the load may start on the
level and afterwards have to climb a steep grade.
The best arrangement for working main-and-tail rope systems
is to run the motor continuously, and to give forward or back-
ward motion to the rope drums through friction clutches
( 330
0>
I
a
H
( 331 )
332 ELECTRIC MOTIVE POWER.
mounted on an intermediate shaft. If the motor be designed
in accordance with the above suggestions, no trouble will be
experienced.
The preceding remarks are also generally applicable to
single-rope haulage, although in some cases, where the load is
small and the pressure low, a series motor with a large starting
resistance may prove satisfactory. A suitable arrangement for
single rope haulage or winding is shown in Fig. 194.
For main winding gear, which is worked practically con-
tinuously during a shift, the author prefers a cumulative
compound motor having a large regulating resistance, the
motor running in one direction only, and the reversals being
made through friction clutches as already described for main-
and-tail hauling. But if the winding be used only occa-
sionally, as frequently occurs with staple-pits, then a series
motor with a large regulating resistance is preferable. The
time occupied in raising the load is so short that the question
of speed regulation does not enter into the problem. What is
required is a large power at starting, gradually yet quickly
applied, and perfect control over the cage at all parts of the
run, but especially when stopping. It is also necessary to be
able to raise or lower the cage a few inches. For such work
the author has found series motors give excellent results.
He finds it convenient to couple the brake lever to the friction
clutch, so that when the brake is applied the circuit is opened,
and the motor is then ready for raising or lowering as required.
Dip pumps should invariably be driven by series-wound
motors* if continuous currents be used.
Several typical designs are shown in Figs. 195 and 195A.
The first is a view of the Goolden-Atkinson pump, which has
been largely used for draining dip areas. The second design
is that of the pump made by the Jeffrey Company in America.
It is permanently mounted on a trolley with removable wheels,
and is a light and efficient pump.
* See remarks on main pumps, p. 326.
( 333 )
334
ELECTRIC MOTIVE POWER.
Centrifugal pumps have generally a limited use in mines on
account of their requiring to be " primed " before they will suck
water, and also because there is always a risk of the pum}<
ceasing to act if air gets into the suction pipe ; in fact, they
require frequent attention. These pumps are not suitable for
working against higher heads than 28ft. or 30ft. of water unless
special precautions are provided for starting. They are suit-
able for a low head and a large volume, and will be found useful
in cases where the water is too " dirty " for a force pump. A
usual arrangement is shown in Fig. 196.
CENTRIFUGAL AND ROTARY PUMPS.
335
Fig. 196A refers to an American double rotary force pump,
having a capacity of from 50 gallons to 75 gallons per minute.
The design forms a very compact combination of pump and
motor, which can be easily wheeled about a pit by one man. The
I
cu
C c
.~ bo
II
H
a
^
rotary type of pump doea not find much favour with English
mining engineers. It has the disadvantage of requiring to be
primed like a centrifugal pump, and is not adapted for working
with dirty water. It has, however, practically no slip, and can
be worked at varying speeds without seriously affecting the
336
ELECTRIC MOTIVE POWER.
efficiency. Both centrifugal and rotary pumps give the best
results for dip working when the level of the suction pipe is so
arranged as to charge the pump.
Fans, either main or auxiliary, should also be driven by
series motors, if run off a continuous-current circuit. The
electric motor is peculiarly adapted for running fans, and it is
somewhat surprising that this has not been recognised more
fully. The author designed a 25-H P. main fan plant for a tin
FIG. 196A. Jeffrey Double Rotary Dip Pump, mounted on a Trolley.
mine at Eger, in Bohemia, in 1889, the dynamo being driven by
water power at a distance of about half a mile from the motor.
Stamp batteries and ore crushers should be driven by shunt
or compound-wound motors, if continuous-currents are used.
Coal cutters and rock drills have hitherto, with few exceptions,
been run on continuous-current circuits. In order to avoid
gracing " when running light, both differential compound and
POLYPHASE CUREENTS IN MINING. 337
shunt windings have been tried with indifferent success com-
parative regularity of speed has been gained at the expense of
torque. After numerous experiments, the author has found
series-wound motors to give the best results for driving coal
cutters and drills. He prefers to control the speed by an
external resistance. Other workers in this field have arrived at
the same conclusions. But the success attained has not been
sufficient to warrant the hope that coal will be cut largely in the
future by machinery driven by continuous-current motors.
The future appears to lie with the polyphase systems. The
polyphase motor, having neither collector nor brushes, obviates
the danger from sparking at the brushes a defect always
present with continuous-current motors. And, since the speed
can never exceed that of synchronism with the generator, racing
is impossible. The regulation of polyphase currents can
generally be accomplished in a small space by means of
impedance coils without any possibility of sparking, for no part
of the circuit need be opened or shunted (see Impedance Coil,
p. '241), as is necessary with a continuous-current resistance
regulator. (See 59, p. 293, for method of obtaining a large
starting torque.)
The sole point on which continuous-current motors are
superior to polyphase ones, and then only with series winding,
is as regards the starting torque. From this point of view
they are undoubtedly the best and most efficient motors that
can be built. The three-phase motor at starting is roughly
comparable to a shunt motor ; it requires a starting resistance.
(See Tables BB and CC, p. 289 ; also curves in Figs. 172 and
173, p. 294.)
It is always possible, however, to start a motor before
coupling it to the load if the initial torque be too great for the
maximum motive effort. With drilling machines the drill car
be slackened if necessary, and with coal-cutters the initial
torque of the motor can be made sufficiently great to start the
cutter against the friction of the debris, which is all that is
necessary. A " fall " should be cleared away by hand.
In driving large pumps and hauling gear, it will generally
be advisable to use friction clutches, through which the load
338 ELECTRIC MOTIVE POWER.
can be gradually applied after the motor has acquired it
proper speed. The clutch does not entail extra expense in
most cases, since its use is generally advisable, and often abso-
lutely necessary even with continuous-current motors.
.67. SAFETY MOTORS ; THE MINING MOTOR OF THE
FUTURE.
Attempts have been made to design a continuous-current
motor perfectly free from the risk of firing gas from
sparks at the commutator or from short circuits in the
coils. It is admitted on all sides that so long as brushes
and commutators (sliding contacts) are used it is impossible to
work without sparks, which, under certain conditions, may fire
explosive gas. It is, indeed, found experimentally that the
small blue sparks occasionally seen on even the best continuous-
-current motors are able to fire gas if the metal of the com-
mutator becomes heated, as it will at times. It is, therefore,
necessary to confine the explosion area to as small a space as
convenient, in order to limit the effects and prevent communi-
cation to the outer air.
The first attempts were made in the direction of enclosing
the entire motor in a metal case. It was soon found, however,
that the quantity of air enclosed was too great to be safely
tired, and this method has been abandoned by the majority of
motor builders.
Messrs. Mavor and Coulson have, however, devised a com-
pletely enclosed motor (see Fig. 197) of admirable mechanical
design, which is by far the best illustration of this class.
Whether it may be classed among the " Safety " motors is
perhaps a matter for experiment ; but there can be no doubt
about the security it affords from accidental damage from any
outside cause, and it is thoroughly dust-proof.
The next obvious course was to enclose only the armature,
commutator, and brushes. By suitable arrangements this can
be done in a very effective manner, and the space so enclosed
can be made small enough to limit an explosion to the protected
area. But other difficulties are introduced. The design of the
STEEL-CLAD MOTOR.
339
340
ELECTRIC MOTIVE POWER.
brush gear is complicated, and the adjustment of the brushes
is rendered exceedingly difficult, especially to unskilled hands.
The author has built motors for coal cutting in this manner,
and Messrs. Easton, Anderson and Goolden have patented
various devices with a similar object.
In Fig. 198 is shown a perspective view of the excellent
safety mining motor made by Messrs. Easton, Anderson and
SAFETY MOTORS.
341
Goolden. The general arrangement is easily understood. The
armature, commutator, and brushes are encased in a metal
compartment, the free space of which is small. The makers
say that an explosion of gas within it cannot be communicated
to the outer atmosphere. The author has had no opportunity
of testing this important statement, but from his knowledge of
the motor it appears to be correct, always assuming that the
FIG. 199. Sectional view of Davis and Stokes' Inverted Commutator as
used on their Safety Mining Motor.
casing is in good condition and the inspection doors properly
fastened. (See remarks on this subject on page 342.)
Messrs. Davis and Stokes, of Derby, have also invented
a " safety motor," a sectional view of part of which is
shown in Fig. 199. It will be seen that the commutator is
inverted, and the brushes placed inside of it, instead of on
the outer perimeter, as is usual. The brush arms are attached
342 ELECTRIC MOTIVE POWER.
to a movable ring, sliding upon the bearing parallel to the
shaft, and arranged to lock in the proper running position
through a screw collar. The brushes are thus placed in a
small circular space inside the commutator, the cubic con-
tents of which in small motors is about the same as that of
a safety lamp ; and which, even in large machines, can always
be made sufficiently small to render an explosion within it
quite harmless. It should be noticed that the brushes can only
be got at by the attendant when the motor is standing, and }
therefore, when there is no chance of danger. Motors of this
make have been tested in an explosive mixture of air and gas
by Mr. John Rhodes, at Aid war k Main Colliery, who found
that, although the gas continually flashed inside the com-
mutator, it did not communicate flame to the outside. This
is, perhaps, the safest form of continuous-current motor yet
invented, and has been successfully used for the past four years
in. connection with a variety of underground work.
It is questionable, however, whether all these designs are
not chiefly important as dust protectors. (It is absolutely
necessary that a motor worked on a coal face should be dust-
proof.) Though the cases may fit well when new, they probably
soon get loose and defective from the rough usage inseparable
from the class of work, and thus become useless as safety
devices ; indeed, they may then be a positive source of danger
from the apparent security attached to them.
The only real safeguard against explosions from sparking at
brushes and commutators (sliding contacts) is to do away with
them altogether, and the only way in which this is practicable
at present is by the use of polyphase motors. The mechanical
simplicity and excellent speed regulation of these machines
have already been urged. These advantages, in combination
with their safety, must gradually tell. They will necessarily
take the place of all other types of motors for driving coal
cutters, rock drills, and other machines which have to be
driven in a dusty atmosphere liable at any moment to be
charged with gas.
In the author's judgment the mining motor of the future
will probably present the appearance of a circular iron box.
MINING MOTOR OF THE FUTURE. 343
The revolving part will have no electrical connection with the
supply mains, and will resemble an iron cylinder with closed
ends and steel shaft. A breakdown of the insulation inside
the cylinder will simply affect the efficiency ; it will not cause
sparking. The windings in connection with the mains will be
few in number, laid in recesses, and be entirely protected from
external damage by means of the outer framework. The
conductors will be of the concentric type ; and in permanent
plants it is probable that the Pownall Safety Mining System,
or some development of it, will be largely adopted. The
junction boxes, switch, cut-outs, and regulating devices will be
all flame-tight, and be protected by oil or by air under pressure.
An explosion from an inadvertent spark will then be a more
remote contingency than one from a safety lamp.
AA2
CHAPTER X.
COAL-CUTTING AND ROCK-DRILLING BY ELECTRIC
POWER.
68. Introductory. 69. Rotary Bar Coal-Cutters : Goolden- Atkinson,
Jeffrey, &c. 70. Rotary Side Wheel Coal-Cutters : Gillott and
Copley, Yorkshire Engine Co., Snell-Waterhouse Coal-Cutters, &c.
71. Electric Power Drills : Rotary and Percussive Types ; Jeffrey,
Marvin, and Van Depoele Drill.
68. INTRODUCTORY.
THERE has always been a certain fascination about the appli-
cation of electric power to coal-cutting and rock-drilling. It
is easy to appreciate this feeling when one has had some
experience of coal-getting. Indeed, it has been felt for a long
time that a mechanical means of hewing coal is desirable
from all points of view. Yet, strange to say, the problem
has presented so many difficulties that its successful solution
on a large scale still belongs to the future, although coal has
been got by mechanical means in isolated cases for a long time
past.
The difficulties are well known, and may be regarded under
two heads, each of considerable importance. The first refers
to the mechanical side of the question, and hence properly
belongs to the present discussion. The second relates to the
system of working and the general management of mines, and
cannot be treated here at length. But reference must be made
to some of the obstacles thrown in the way of mechanical coal-
getting by the men and the masters. The use of a coal-cutting
machine may seem to be simply a question of the price of coal
346 ELECTRIC MOTIVE POWER.
hewn by it in comparison with the cost of hand-hewn coal;
and this is undoubtedly the case. But the cost of machine-
won coal is at present necessarily based on figures resulting
from the use of one or two machines, instead of on figures from
a dozen worked on " faces " specially laid out for the purpose.
It should be noted that the cost of the prime power for two
or three machines is practically as great as that required for a
dozen, and that the system of mains need not be proportionately
increased for the larger number, because the power does not
'ncrease in direct proportion to the number of machines, as it
is not possible to keep them all running at the same time. It
is important, too, that machinery should be run as nearly con-
tinuously as possible, which suggests the employment of several
shifts of men. And this is only practicable, even if the men's
union permit it, when the conditions are such that the coal
can be carried away sufficiently quickly. In the majority of
faces, as arranged to-day, this is impossible, and a machine
cannot be kept at work continuously for even a shift of eight
hours ; so that, from causes which are quite independent of the
working capabilities of the machine, its theoretical output is
never reached. This fact points to the necessity for a coal-
cutter of smaller capacity than those now in use say a machine
which would hole from 5 to 10 yards an hour, working under
normal conditions and allowing the necessary time for clearing
away the coal. Hitherto the aim has been rather to produce
machines which, under favourable circumstances, will cut from
20 to 40 yards of face per hour. Bat a very casual inspection
of a coal mine will demonstrate that such a rate cannot be
maintained for any length of time, simply from the difficulties
of clearing away through gates two chains apart, even neglect-
ing for the moment the difficulty of keeping the face clear
from falls of roof during the time necessary for removing the
coal.
If mechanical coal-getting is to be carried out on a large
scale with the long-wall system, it will be necessary to modify
the number and position of the gates in order to increase the
facilities for clearing away. The question belongs to mining
managers, and not to electrical engineers ; and this is, perhaps,
one of the chief reasons why mechanically-driven coal-cutters
, ELECTRIC COAL-CUTTING. 347
have not made as much progress as their undoubted utility
appears to warrant. A colliery is being opened out (October,
1894) near Eckington, in which the whole of the work will be
done electrically, even to the driving of the fan. The coal will
be worked on the pillar and stall system by Jeffrey coal-cutters.
This undertaking is due to American enterprise, and will be
watched with the highest interest.
It does not lie in the province of the present work to discuss
the question of machines versus hand coal-getting. But it may
be remarked that one of the best electric coal-cutters, with two
men to work it, will easily hole as much as from 20 to 30
hewers; thus largely reducing the number of men required
below ground. And since the number of accidents necessarily
bears some direct proportion to the number of men employed,
the introduction of machinery should have the effect of largely
reducing the loss of life.
The number of mechanical principles applied to coal-getting
machines is astonishing, and the ingenuity displayed by many
inventors, who evidently have not been in close touch with the
principles of mining, is equally surprising. All conceivable
methods of cutting, drilling, boring, shearing, and picking coal
have been designed, on paper at least, and many of them have
been applied to more or less practicable machines. The earliest
attempts were made in the direction of a mechanical pick. As
might be expected, the pick with the man at the back of it
directing each blow did much the better work, and this method
was soon dropped. The drill and the circular saw have given
the most successful models upon which to work out a cutter,
hence a variety of machines embodying these principles.
The machines which have survived the initial stages and
give some hope for future success are divisible into three main
classes :
(a) Bar cutters.
(6) Rotary wheel or disc cutters.
(c) Drills.
348 ELECTEIG MOTIVE POWER.
69. ROTARY BAR COAL-CUTTERS: GOOLDEN-
ATKINSON, JEFFREY, ETC.
Under the first head may be included all those machines
which have a cutter-bar revolving either at right angles or
parallel to the face of the coal. This type has so far proved
the most successful in this country and in America, the best
known being the Goolden-Atkinson bar cutter of English inven-
tion, and the Jeffrey machine of American origin.
The essential feature of the Goolden-Atkiuson machine is a
tapered rotary bar, which is fitted with a series of cutters
driven into tapered holes. They are arranged in a spiral form,
the object being to clear out the cuttings and prevent the
jamming of the bar. The shape, size, and general arrange-
ment are the result of long and careful experiment by Messrs.
Llewellyn and Claude Atkinson, the staff of Messrs. Easton,
Anderson and Goolden, and the Electrical Coal Cutting Cor-
poration. The main idea is shown in Figs. 200 and 200A.
The cutter-bar (see Fig. 201) is usually geared to the armature
shaft by a pair of cast steel double helical wheels running in
oil, and makes from 300 to 500 revolutions per minute,
according to the material being cut. The motors are always
wound in series, and hence the speed varies inversely as the
resistance ; which is exactly the best condition for work
of this kind, since it prevents undue shocks to the motor,
and tends to keep the power absorbed within safe limits. It
will be seen that the motor is thoroughly protected from
mechanical injury either from falls of roof or sides, and that
the armature and commutator are fitted into a dust-tight
and flame-tight compartment of dimensions as small as are
consistent with the safe and effective handling of the brushes.
The cutting mechanism as a whole is made to swing through
an arc of rather more than 90deg. on the turntable which
carries it (see Fig. 20lA). This gives facilities for shifting
the machine from point to point in the mine, and also enables
the bar to cut its way into the coal until it is at right angles
to the face and ready for holing. Fig. 201 A gives a view of the
machine as arranged for work. In the early machines of this
GOOLDEN-ATKINSON ELECTEIC COAL-CUTTER. 349
350
ELECTRIC MOTIVE POWER.
class the coal was always picked out to give the bar a start.
Since the bar has to be carried by bearings it may be thought
that coal cannot be cut level with the floor by the bar type of
machine; but this difficulty is successfully met. By arranging
ELECTRICAL COAL-CUTTING CORPORATION. 351
the seats of the turntable at a proper angle, and causing it to
revolve in an inclined plane, the makers contrive to keep the
bar nearly horizontal, and below the level of the rails when at
right angles to the face in the cutting position, and yet to
lift over the rails when turned parallel to the face. In this
way a flooring of regular slope is made at every cut, and
forms the floor for the rails during the next cut. In the
majority of cases it is not found necessary to level the floor,
although when cutting in coal it may pay to do so. The feed
is made by a hand winch as in Fig. 20lA, or is worked auto-
matically from the motor shaft. The author believes that
hand feeding is found to be the more satisfactory method
with this machine.
The Electrical Coal Cutting Corporation have for some years
been working coal at a contract price per ton hewn or per linear
yard undercut to a specified depth. They supply the whole
of the plant and the men to work the machine, while the col-
liery proprietors find the labour for clearing away the coal
from the faces, leaving them ready for the machines. This
system, on the whole, has worked well, and, were it not for
the difficulties already referred to, the machines would turn
out a, much larger tonnage and, of course, return a larger
interest on the capital outlay.
The experience of the Corporation, whilst it has demon-
strated that nearly every mine, working long-wall, can be suc-
cessfully operated by electric coal-cutting machines, has also
brought into further prominence the essential difference
between hand and machine working, and the great difficulties
of getting the owners and managers to appreciate the differ-
ence, and to lay themselves out to apply to mining the discip-
line and regularity obtaining in manufacturing industries.
A modification of the Goolden-Atkinson machine has lately
been introduced by Mr, Frederick Hurd, who for some years was
on the staff of Messrs. Goolden and Co. No particulars of its
performance have yet been published. A general idea of the
machine may be gained from Fig. 202. There is a scoop built
at the back of the bar to assist the clearing of the cuttings
352
ELECTRIC MOTIVE POWER.
from the hole. This may or may not be an improvement;
experience alone can determine; but the author believes its
use has been abandoned after a few trials. It should be
noted that the Goolden bar is claimed to clear itself by
virtue of the spiral arrangement of the cutters. There are
also some interesting devices for ventilating the motor and safe-
guarding it against the risk of exploding gas. These consist of
an elaborate system for circulating fresh air under pressure
EIRTLEY ELECTRIC COAL-CUTTER.
353
along the conductors, which are encased in pipes for the
purpose, and through the interior of the motor, the starting
resistance and switch-board boxes, &c. The object in view is,.
'S -
J> -4-3
O 2
1-g
3
3 o
O o
of course, most desirable ; but the expense necessary to execute-
the system described in Mr. Hurd's patent specification is
probably too great for ordinary requirements.
354
ELECTRIC MOTIVE POWER.
Another bar cutter has been patented quite recently by
Messrs. T. Heppell and Patterson, which embodies some novel
features. One of these machines, built by Messrs. Ernest Scott
6 S
I
and Mountain, is shown in Figs. 203 and 204. The case is re-
,moved to show the motor and gearing. One of the special points
is the endless chain used to clear away the cuttings. This is
BIETLEY CUTTER-BAR. 355
shielded by a strong guard. The gearing consists of cast steel
bevelled wheels and pinions. The machine is propelled by
means of a steel rope which passes round a drum geared to the
armature shaft by worm gearing, an eccentric, rod, pawl and
ratchet. The design is very compact, and appears to be
capable of being worked into a less height than the type of bar-
cutter adopted by other makers ; but this remains to be proved,
for many alterations may be required before the machine gets
into regular work. The author believes that at present one of
these machines is at work in the Cannock Chase district. Mr.
Heppell says that one of these cutters at the Pilner Main
Collieries is doing good work, cutting at the rate of about 20
yards per hour, 3ft. under. A sectional view of the cutter-bar
is shown in Fig. 205. It is arranged to swing about the centre
of supports, which permits of the cutters being readily examined,
FIG. 205. Section of Birtley Cutter-Bar.
and also facilitates the moving of the machine about a coal
pit. It has three dovetailed grooves cut along its length.
The cutters have corresponding dovetails, and are distanced
by suitable pieces of steel. The cutters can obviously be
arranged spirally or otherwise, as may be required.
The Jeffrey coal-cutter is of different construction from any
machine of English origin, and was, no doubt, first designed to
meet the conditions of the American coal seams. Special
machines are built to suit the conditions obtaining in British
mines. The method of working will be readily grasped on an
inspection of Fig. 206. The details of construction are shown
in Fig. 207.
It will be seen that the bar lies parallel to the coal face when
in the cutting position. It is designed to hole as deep as 7ft.
356
ELECTRIC MOTIVE POWEE.
Deep undercutting is an especial advantage in pillar and stall
working with an average roof. This machine consists of a bed-
frame, occupying a space 3ft. wide by 7ft. 2in. long, built up of
O
_o
I
I
two steel channel bars firmly braced, the top plates on each
carrying racks with the teeth downwards. Mounted upon and
engaging with this bed-frame is the sliding frame, consisting
JEFFREY ELECTRIC COAL-CUTTER.
357
BB
358 ELEOTEIC MOTIVE POWER.
mainly of two steel bars, well braced, upon which is mounted
at the rear end an electric motor. Upon the front end of this
sliding frame is mounted the cutter-bar, held firmly by two
solid steel shoes with brass bearings. The cutter-bar receives
motion through an endless steel or bronze chain from the
driving shaft, and as it revolves is fed forward by means of
straight-cut gear and a worm and wheel. The bar is usually
36in. wide. In America the seams are generally much thicker
than those in this country, and the roofs are sufficiently good
to enable the face to be kept open for the distance necessary
with a 6ft. or 7ft. holing, and pillar and stall working is chiefly
practised. But in England the conditions of long-wall working
rarely permit of such deep undercutting, and from 4ft. to 5ft.
is, as a rule, the deepest cut advisable. At the Cannock and
Rugeley Collieries, where two of the Jeffrey machines are at
work, one holes 4ft. and the other 7ft.
The electric motor occupies a space of about 20 inches square.
It is designed to absorb a maximum of 15 E.H.P., and in some
veins of coal does not require more than 7 '5 H.P. The American
standard pressure is 220 volts, but this can be altered to suit
circumstances. The armature is designed to run at 1,000
revolutions per minute, and the cutter-bar at 200. The
momentum of the moving parts is such that the machine over-
comes ordinary obstacles without difficulty, and, since the
motor is not coupled rigidly to the bar, the vibrations are
not transmitted to it, and the machine runs steadily and
comparatively quietly. Two men are required to work it
one at the switch at the back and the other as helper to clear
the debris and to assist in shifting. The machine is taken
from stall to stall on a special truck, shown in Fig. 208. When
at work it is slid on to two boards or bars of iron in front of
the coal, and fastened firmly by means of the front and rear
jacks against the face and roof of the coal, which is thus sup-
ported to some extent during the under-cutting. When the
full depth of the cut is reached the feed is thrown off, and the
cutter bar is returned to the starting position by means of
reversing gear. The machine is then moved sideways for a
distance equal to the length of the cutter bar, and another cut
is made in the same manner. Each cut is made in ordinary
JEFFREY ELECTRIC COAL-CUTTER. 359
BB2
360 ELECTRIC MOTIVE POWER.
working in from three to six minutes. The output depends to-
a great extent upon the skill of the men in moving and jacking
the machine, and also upon the hardness of the coal, and
whether the cut is made in coal or " dirt." In some seams
these machines are said to cut from 40 to 66 linear yards of
face to a depth of 6ft. in a shift of 10 hours. Since the depth
of the undercut is roughly twice as great as that usually made
with a bar machine of the Goolden-Atkinson type, this is
equal to a length of face of from 80 to 130 yards, in com-
parison with the performance of the latter. Assuming these
figures to be correct, it would appear that although the Jeffrey
machine has to be shifted after every cut, yet it may cut a
greater area of coal than the Goolden-Atkinson machine, which,
the author understands, does not average more than from 80 to
100 yards of face in this time.
In comparing the two, stress must be laid on their relative
suitability for different kinds of work. The Goolden-Atkinson
machine requires a space between the face and the props at
the goaf of not more than four feet at the outside, whereas
the Jeffrey machine cannot be worked in a smaller space than
six feet; but with the latter the depth of undercut may be
nearly double that with the former, though, of course, the
total length of roof unsupported will be then nearly twice as-
great. It is, therefore, obvious that the side cutter-bar can
be used in places where the front cutter-bar cannot possibly be.
It must be remembered also that the Jeffrey coal-cutter makes
a capital heading machine, while the side cutter cannot be used
for this purpose. The two machines are not, therefore, rivals
for the same work in all cases. They cost in the first instance
about the same, the motors are of the same rated capacity,
and the actual power required in practice appears to be about
the same. Hence there does not seem to be much to choose
between them as regards the question of cost, but it is rather
a matter of suitability for any particular case.
The English agents for the Jeffrey mining machines are
Messrs. John Davis and Son, who are placing these useful coal-
cutters in various mines in England, Wales, and Scotland.
TESTS OF ELECTEIC COAL-CUTTERS. 361
Mr. Williamson, of Cannock and Rugeley Collieries, who is
using one of the Jeffrey machines with a 36in. bar, holing 4ft.
in a 5ft. seam, says that the output of round coal is increased
15 per cent. that is to say, hand cutting makes 75 per cent, of
round coal and the Jeffrey cutter 90. And that one machine,
working single shifts, has increased the output by at least 60
tons per day.
In Table DD are given a few results from a series of exhaus-
tive trials of electric coal-cutters in mines in Ohio, U.S.A.,
made in 1890 by Mr. R. M. Haseltine, Chief Inspector of Mines.
This gentleman found that the only electric coal-cutter in
general use was the Jeffrey machine, and, therefore, most of
his tests refer to this type. The Leichner and Thomson- Van
Depoele machines (see the end of the series) are of com-
paratively small output, and do not seem to have made much
headway since the date of the report, so far as the author is
aware ; while, on the other hand, the use of Jeffrey machines
has steadily increased in American mines, and is now gaining
a hold on mining engineers in this country.
The figures are not directly comparable with those now
obtaining in England, for the conditions are very different, and
the machines have been since improved in many respects;
but the results, taken collectively, may prove instructive to
future users of electric coal-cutting plant, as they show, on the
authority of an independent official and expert, what was
being done in this direction as far back as 1890.
The General Electric Company of America have built a
modification of the front-cutter type machine, which is of
interest. In it the cutter-bar is made to revolve in such a
direction that the coal is cut upwards. It is claimed for this
method that it assists the holding down, and hence there is
less need for careful fastening by jacks and braces. In this
machine there are four chains instead of the single one used
with the Jeffrey machine. The Stine-Smith coal-cutter is also
similar in design, and appears to be a soundly built machine.
The author has no information about performances of either
of the two last-mentioned machines.
Table DD. Showing Results of Experiments made with Electrical Coal-C utters in Ohio, 1890, ly R. M. Haseltine^
Chief Inspector of Mines.
"3
CO
IN!
. . . . . . . . .
1 : : : : ;
co
uiiu i tn reoo -<}j -bs \ ^no
-aapun o-j p9.mib9.i -j-jj
ssl
00 1C 00 OS (?0 CO CO
CO 05 rH rH CS CS
rH i i T-H
osTf p r~t~rt<
O O " r- 1 r-t CO
CO -H O t>-
O5 OS CS CO
Sajwno in paunb
m ocs
Of- *3 CO others
<^ co oo oom
O5 CO p p
co as cs oo
OS OS CO
r-i r>i yr yj rr ro CO
co i i o ^D rfi 10
Ilsl
CO ^0
^ -^ ^ _H -tn ^ ^H
rH I r-l r-l 1C in
******
rH.-l.-l
ooobbbo
000000
0000
Electric h
power requi
overcon
frictional
fl
n o - t- t-. GO OO
SiSS
rl 5 !
2SS
CO CO CO *^O CO CO CO
in in m 10 m m ib
>n p >o ip >p p
t- t>- t^- t>- 1~ ts.
pppp
3pi3q Sumuru
III p9SU 'd'l[ 9.o1?J9AV
.OS
O -HCSt^CO ~t*OS
O 00 t^ t (C (M
Tjl^tlrHCO
OSrHOSOOOOO
OS OrH O r-^OS
00 COCSOO
Electric horse-
power used
in cutting.
41
sss
CO Tf Ci t- 7^ <>
h- 00 CO ^-1 O5 C5 00
rH rH CM CO r-c r-i r-H
cp cp * b
CO 1- CO 00 rH -^
OOt-?>r-
CO -* TT< IM
rH rH rH 1
'x S
Is
i-l O O
1^ SO CO iO O t^ C5
co t^ t-. co o m
CO b-O -^
^S^
slisssss
CO CO CO CM CM CO
SSSS
.S P-
o
V2S
^^2^8
o o oio oo
CO CO O * COrH
i?SS8
III 1
S
**-*-
ic in ic i> t^" to t^
-^^
ic in in m
Sl|
S
CQ
1C O t^
TJH CO JO
T}H O >0 O ^ O 00
IQ O CO CO CO O CO
o in co co o cs
in ococoo-*<
o *** in co
.S
CO t^t^
n m 10
o ic m m o o
in m in o
|ol
5
CC COCO
CO CO CO CO CO CO CO
CO COCO CO CO CO
CO CO CO CO
fa
CO CO CO
CO CO CO CO CO CO CO
coco coco coco
co co co co
H
&e 6 * *
3
fS t s s s
(>
5B^O " " *
Sm^s9^ 9tn(A^ .u 'O T3
apBiu s^no jo jgqumjv i r^ c^ co
T3 ^
.-. CM eo -v m t-
^^rrj^^^j
5 CM CO ^ in O
3111
S
2
jl
'0*3
11
03
: d
:0 :
_
T-H
00
1
( 362 )
;;; 1
i i ;
PI
|S-|
:::}
i ; ;
:
! ;
; ; ; ;
""
coco
bb
TH
OCMOS
THT-lrH
:
OCM
oo
COM rfCO
(NO
s ll
: :
.0000
IS
i ( TH iH
:
ooo
TH H
<*l CO (M OO
l-J r-l rH T 1
r-i rH iH i 1
O CO CM
b bb
Is!
(N CM CM CM
bbbb
CM CM
bb
bob
;
(M CM
iH '
bbbb
CO O
CO CO CO
b bb
|p
: :
coco coo
o o o *
oo
o o
pop
boo
;
ss
!?!!
g
co co co
p|
CpOOTtH
OOOO
o o
00 00 00
o bo
CM -
11s
CM
CMO
O O
CMrH
* COCM 00
O COCM
b COCM
|i|
1-H Tfl
Ocptpt-
OOOO
S3
THOO
00
000
' O
HTH TH
oo
oo o
CO CO
b-OOO
00
> a'o
I 1
CO CO CC CC
coco
H^ -M Tfl
-H iH TH
3
THr^
CO CM CM CO
rH rH rH i 1
o o o
T 1 TH
Hga
O
b-b^b^t^
CNCM
000
00
COCM CM b^."
^SM
5-^2
>o o
oo^oo
^^
Tf^
^
iC
^H^^H^
CO CO CO
^ c
coco
CO CO CO CO
CO CO
CO CO ^O
CO
COCO
OOOO
00
S^S
coco
CO CO CO CO
CO CO
CO CO CO
co
coco
CO CO CO CO
CO COCO
^5
f-.
CO O
.^(M (M
> .
2
I 1
sJ
I 1
Shawmut, Elk
County, Pa.
Shawrnut, Elk
County, Pa.
(rt) The sixth
machine No. 1,027 mac
made three cuts before
mine second cut made i
( 363 )
364 ELECTRIC MOTIVE POWER.
70. ROTARY SIDE-WHEEL COAL-CUTTERS. GILLOTT
AND COPLEY, YORKSHIRE ENGINE CO., AND
SNELL-WATERHOUSE COAL-CUTTERS.
A number of patents have been taken out for machines with
side wheels. In a few the wheels have been designed to cut
vertically, or even at any angle, but in the majority the aim
has been simply to make a horizontal cut as near the bottom
as possible. The diameter of the wheel determines the depth
of the undercut, which is limited in practice to from 39 to
55 inches, the latter being found to be as deep a cut as is
desirable. If this depth be exceeded there is a strong proba-
bility of the coal shearing at the back and fouling the wheel
before it is clear of the cut, and if the cut be shallower the coal
will not break readily by its own weight, but requires wedging
down.
Passing by the early inventors of these machines and coming
to modern history, the firm of Messrs. Gillott and Copley
stands in the front rank ; but from some cause, which is not
very apparent, they have not shown a disposition to apply
electric motors to their machines, preferring to continue the
use of compressed air.
The Yorkshire Engine Company have also built some
excellent machines of this type, embodying several improve-
ments on those of the former firm. They also have confined
themselves to compressed air, although they have built to
order a few electrically-driven machines. An illustration of
one of their machines is given in Fig. 209, in order to show
the general requirements of this type of plant, and also because
the author has found from actual experience that the machines
do excellent work.
Fig. 210 is an enlarged view of the cutter- wheel, showing the
method of supporting it in bearings. The design is arranged
to hole at a few inches above the rail tops.
Owing to the success which this class of coal-cutter has
obtained when driven by compressed air, no radical change has
SIDE- WR EEL COAL-CUTTER,
365
366
ELECTRIC MOTIVE POWER.
been attempted by inventors when applying electricity. They
have accepted the main principle, and have simply changed the
motive power.
On referring to Fig. 209 it will be seen that the side wheel is
fitted with two kinds of cutters. Every alternate one has
Y-shaped teeth, while the remainder are straight. The function
of the latter is to tear out the centre of the cut, while the
former clears it out to the desired width, usually about Sin.
In air-driven machines the speed of the wheel varies from 15 to
30 revolutions per minute, according to the kind of dirt and
its resistance. This speed is found to be too slow for the
electric motor, since the reducing gear is costly and cumber-
some ; therefore all who have tried to apply electricity have
FIG. 210. Cutter-Wheel : Yorkshire Engine Company.
endeavoured to raise the cutter-wheel speed as much as possible.
This has necessitated strengthening the machine as a whole,
and has increased the dead weight from about 25cwt. to about
35cwt. The increased speed, however, has caused no trouble
in working. In fact, the momentum of the moving parts is so
great that obstacles which caused serious shocks at the slower
speed are scarcely felt at the higher speed of from 70 to 100
revolutions per minute. And the increased weight tends to
prevent derailment.
While upon the subject of weight, it may be remarked
that if it is desirable to limit the weight of a coal-cutter
to, say, lOcwt., which is about as much as any one man
can shift about a pit with the aid of crowbars, it may be well
worth while to pay special regard to the making of a light
machine, But if it be necessary, from any cause, such as the
need for a machine of greater capacity, to increase the weight
SNELL-WATERHOUSE ELECTEIC COAL-GUTTER. 367
much beyond the limit just mentioned, then it appears to the
author to be a matter of little importance whether the machine
weighs 20cwt., SOcwt., or even 40cwt. In each case it is toe-
heavy to be handled without special tools, and a screw jack is
as much a part of its equipment as it is of a locomotive's. In
fact, with the larger type of electric machines the increase of
weight is by no means an unmixed evil, for it gives increased
stability, and, no matter how rough the road, or uneven the
dirt, the machine rides steadily through it all.
The advantage of the wheel machine compared with the
rotary bar lies in the low head room required, and perhaps in
the enormous capacity of the wheel on long walls where the
conditions are favourable.
The author has, however, never seen a machine at work which
had anything like a chance of working continuously, and so
reaching the theoretical output. The majority of pits are so
laid out that continuous working is practically impossible, and
the most useful machine is that which, under the given con-
ditions of normal working, will give the largest average output,,
and not a maximum output for a short time under the best
conditions.
A number of patents have been taken out for side-wheel
coal-cutters ; but perhaps the first practical machine was
designed by the author and Mr. Major Waterhouse, of Glass
Houghton Collieries, about four years ago. The general con-
struction of this machine will be readily seen on an inspection
of Figs. 211, 212, and 213, which are plan, longitudinal, and
end views. Much detail is left out in order to show up the
main features. It will be noticed that the design roughly
resembles that of the Yorkshire Engine Company's compressed
air machine. But, in fact, the whole of the details have been
modified to suit the increased rate of speed and to accommodate
the gearing. The machine was built to hole 3ft. Gin. in a seam
24in. in height, on a level with the floor, this being the first
machine so designed. The maximum height above the rails
was 22in. The cutter made from 80 to 100 revolutions per
minute in various kinds of shale and coal, no difficulty being
368
ELECTRIC MOTIVE POWER.
experienced either from their hardness or from iron pyrites.
The weight was about 35cwt. At least two men were neces-
sary to work the machine, and in soft coal with a rapid feed
a third was required to keep the wheel from being fouled by
the coal. The wheel was designed to run in either direction,
but the inventors always arranged the cutters to feed out the
cuttings at the back of the machine, instead of at the front, as
is frequently done in air machines. It was found, however, that
SNELL-WATERHOUSE ELECTRIC COAL-CUTTER. 369
the wheel did not sufficiently clear itself, and that a man was
required to shovel out the loose coal at the front from time to
time. The power absorbed did not vary so much as was
expected. The automatic feed, actuated by a worm and wheel
from the first cross shaft, nicely adjusted the speed of the
machine to the resistance of the cut. The motor was wound
370
ELECTRIC MOTIVE POWER.
in simple series, and thus the current varied in proportion to
the torque. And, since the pressure decreased slightly as the
load increased, the tendency was to equalise the power absorbed
and to vary the rate of feed with the degree of resistance to
the cutters.
The chief difficulties met with at Glass Houghton were due
to the peculiar formation of the seam, which is 22in. in height
with a thin parting near the middle. The holing was made on
the level of the floor in the fireclay, and presented no serious diffi-
culty. But the lower coal broke away from the parting, leav-
ing the tops in position, and frequently fouled the wheel before
a cut could be made sufficiently long for the introduction of
Under these conditions the time wasted in clearing
FIG. 213. Snell-Waterhouse Coal-Cutter. End View.
the wheel more than counterbalanced any gain from the high
rate of speed at which the machine holed when the coal
remained firmly in position. A bar-cutter might have suc-
ceeded here if more head room had been permissible, for it
is obvious that the fall of coal behind the bar, or even on the
top of it, would not be so serious as with a side wheel. But in
this case the large number of iron balls in the clay were held
to be an obstacle in the way of the bar-cutter, and, in addition,
the bar could not be made to cut perfectly level with the floor-
ing, as was desirable. The power absorbed varied from 10 to
17 E.H.P. The motor was designed to give 15 B.H.P. at about
800 revolutions, and was of the armoured type adopted by
Messrs. Lahmeyer and other Continental firms, but not much
known in England. The design is well adapted for use on a
ELECTRIC COAL HEADER.
371
coal-cutting machine, as the massive field-magnets protect the
field windings and the armature from damage by falls of roof or
accidental injury during working.
At present there are running in Yorkshire collieries a few
electric side-wheel machines which have been developed from
the Glass Houghton one, but no particulars of their working
have been published. Under suitable conditions, however, they
must give economic results.
FIG. 214.-
- Wan tling- Johnson Electric Coal- Cutter and Heading
Machine.
FIG. 215. Plan of Cutter-Wheels of Wantling-Johnson Electric
Coal- Cutter.
A smaller type of wheel machine of American origin is
shown in Fig. 214. It is the invention of Messrs. Wantling
and Johnson, and was shown at the World's Fair, Chicago,
1893. The author has no particulars about its performance,
but it seems to be a practical machine. It is adapted
for making vertical or horizontal cuts, but cannot be set to
cut level with the floor. It appears to be especially suitable
for heading work. The cutter-wheels are shown in plan in
Fig. 215. There are two wheels revolving in opposite directions.
372
ELECTRIC MOTIVE POWER.
ELECTRIC POWER DRILLS. 373
Their diameter can be made to suit requirements. The sketch
in Fig. 214 shows the machine arranged for heading, in
which case it is always parallel with the rails. For long-wall
or pillar and stall working the motor and cutter would be at
right angles to the rails and the coal. The method of steadying
the cutter is clearly indicated in the figure.
The Thomson-Houston " Mowing Machine " coal-cutter,
shown in Fig. 216, presents several features entirely different
from those of the preceding machines. It may be regarded
as a modification of the Baird coal-cutter. The cutters are
carried on a chain which passes round an overhanging arm
capable of rotation through an arc of nearly ISOdeg. The
illustration shows most of the working details. It appears to
be suitable for long-wall working. There does not seem to
be any definite information published with respect to its
performances.
Messrs. Mavor and Coulson have adopted Baird's design,
but with several modifications ; the principal one being the
use of worm gear for driving the cutter-chain. Their machine
is designed to cut at the rate of one foot per minute through
ordinary soft Scotch coal, the chain-wheel revolving at 60
revolutions per minute.
The Jeffrey Company are also trying a cutter-chain on one
of their special English machines, and expect it will effect a
saving in power, since the width of the cut is reduced to 2'5in.
71. ELECTRIC POWER DRILLS: ROTARY AND PER-
CUSSIVE TYPES; JEFFREY, MARVIN, AND VAN
DEPOELE DRILL.
In spite of the obvious advantages to be derived from the
application of electric power to rock and coal drills, much pro-
gress does not seem to have been made in this direction. The
reasons for this are probably partly the same as those, already
referred to, which have hindered the introduction of mechanical
coal-getting, and, in addition, the cost of the conductors, which,
no doubt, has been in many cases prohibitive. But there are
also some difficulties peculiar to the work.
c c
374 ELECTRIC MOTIVE POWER.
Driving stone drifts is about as rough work as can be
imagined, and the men employed are as rough as the work.
But even more important than the rough treatment is the
question of ventilation. Obviously, when driving a heading,
there is a tendency for the air to stagnate, and there is diffi-
culty in removing the fumes of powder after shots are fired
unless fresh air can be brought up to the face. Now the com-
pressed air drill exactly meets this requirement. The exhaust
from the drill causes a steady draught, which cools and purifies
the air, and powder fumes can always be cleared away by turn-
ing on a little air. The electric drill, on the contrary, tends, if
anything, to increase the difficulty, for the power wasted in the
drill raises the temperature of the air at the face of the head-
ing. This disadvantage is probably sufficient, in many cases,
to render the use of electric drills impracticable, the mere
question of cost of boring (gauged, usually, by work done in
well-ventilated spots) being altogether subordinated to other
considerations. Of course, for a variety of purposes, such as
quarrying, working in well-ventilated spots, &c., these objec-
tions have no weight. But even under the most favourable
circumstances the electric drill does not seem to have made
much progress.
There are two main principles upon which rock drills are
designed : the rotary and the percussive.
The rotary type is usually driven through gearing from a
small motor. The percussive type is sometimes worked by a
motor winding up a coiled spring, which at the proper moment
uncoils and spends its energy upon the drill shaft. In other
types the principle of magnetic attraction is used, the drill
shaft being attached directly to the iron core of a solenoid.
Hitherto the motor-driven drills have proved to be the more
successful in general work. Several firms build these machines,
each having a different way of gearing the motor to the drill shaft,
but the general principle is the same. The best known in this
country, as well as in America, is the Jeffrey drill. It is chiefly
used for working in hard coal, and is found to give satisfactory
results. In general the makers design the motors to work at a
ELECTRIC COAL-DRILL. 375
pressure of 220 volts ; but this can be varied to suit special
requirements. The rated output of the drills for 2in. holes is
2 H.P., but a factor of safety of two is allowed. They are stated
to drill, in the hard "boney " found in anthracite mines, a 2in.
hole, 6ft. deep, in from 2min. to 2Jmin., while in the coal they
will cut a similar hole in less than a minute. One of these
FIG. 217. Jeffrey Rotary Electric Rock and Coal Drill.
drills is in use at Newbattle Colliery, Dalkeith. The manager,
Mr. John Morrison, reports that it makes, in the hard splint
coal, a 2in. hole, 4ft. deep, in the space of 5min., including the
time taken to set the drill. (This, he adds, is equal to the
work of four men, while the Jeffrey drill requires only one man.
cc-2
376 ELEGTEIG MOTIVE POWER.
A good idea of the general shape of the drill, and of the
method of fixing it in position, will be gathered from Fig. 217.
It will be seen that the motor is protected from mechanical
injury by an iron shield. Any type of motor can be fitted to
the drill, and probably a polyphase machine will ultimately be
adopted.
Various English firms have built electric drills for mining
work, but, judging from the number in use, none of these has
been so successful as the Jeffrey drill. The designs are usually
heavier than that shown in Fig. 217.
The reciprocating action of a solenoid is apparently well
suited for actuating percussive drills. Yet the solenoid, energised
by a continuous current, is the least effective means of using
magnetic power through comparatively long distances. Its
proper function is to attract an armature through a very short
range, or to hold it firmly in position.*
However, in spite of this manifest disadvantage, solenoidal
action offers so many advantages in the design of percussive
drills that it appears highly probable that this type of drill
will ultimately come into more general use than the motor
type. Therefore, a brief reference to the subject may be
useful.
The earliest attempts to utilise the principle were made in
accordance with the diagram shown in Fig. 218. The current
was supplied to the centre of two coils forming the solenoid,
and was passed through them successively; the changing being
controlled by means of a two-way switch, indicated at a and c.
The iron shaft of the drill formed the core, and was attracted
first by one coil and then by the other. This is a very waste-
ful design, for the power absorbed during the instroke is the
* Prof. S. P. Thompson has recently demonstrated that an alternate-
current magnet possesses very different properties from those of a con-
tinuous-current one. He shows that by means of an alternate current
the pull of an electro -magnet on its armature may be extended through
comparatively long distances, and may be even greater at, say, three inches
than when closer. This important fact probably opens up a new field,
and may, therefore, assist in the development of percussive drills.
ELECTRIC PERGUS&IVE DRILLS.
377
same as that during the outstroke. An additional objection la-
the trouble given by the contacts at the switch points.
An improvement is possible by the use of a single solenoid
drawing in a plunger against a strong coiled spring. The blow
given by the recoil of the spring is very rapid, and resembles-
the impact of a hammer if the bit be at the right striking dis-
tance ; and, further, the instroke is made comparatively slowly,
and does not shake the drill carriage. In case the stroke is
too short to strike the work a spring cushion is provided to
receive the blow. A two-way switch is required, however,
and this practically renders the design useless.
FIG. 218. Diagram of Electric Percussive Drill, with two-way
switch at a c.
A distinct advance is made by the use of pulsating or
alternate currents, or a combination of them. There are
many methods, but they all embody the following conditions :
No switch is necessary, three or more wires are required, and
also, in some cases, a special dynamo. The first is an absolute
gain, for there is no trouble from sparking, and the last two
are not serious difficulties when it is considered that these
drills are only likely to be used in mines and places where it
will pay to provide a suitable dynamo if the use of electric
drills is deemed advisable. The simplest drill of this class is
one coupled to a two-phase circuit, as shown in Fig. 219; but
this has the disadvantage that the power used on the instroke
is nearly as great as that on the outstroke. The number of
blows given by drills of these types corresponds with the fre-
quency of the alternator, and they are therefore adapted for
378
ELECTRIC MOTIVE POWEE.
delivering many quick light blows per minute rather than a few
heavy blows. A frequency of from four to ten per second is
found to give the best results.
A still better device is that applied in the Marvin drill.
This is of the double solenoid type, and is one of the most
FIG. 219. Diagram of Electric Percussive Drill, for use on
circuit. No Switch required.
two-phase
successful in America. It is run off a special dynamo giving
pulsating currents in two circuits. The connections are shown
in Fig. 220. The dynamo armature, in its simplest form, has
only one coil. One end of this is fixed to a continuous metal
ring d lt on which rubs the brush Bjj the other is joined to a
metal segment, d z , extending for 180 deg. and concentric with
FIG. 220. Diagram of Marvin Electric Percussive Drill.
r/ l5 (/o, rings on dynamo ; B 1? Bo, B 3 , fixed brushes.
d r Two brushes, B 2 and B 3 , placed diametrically opposite to
each other, rub against it. Three conductors are required ;
one from the middle point of the solenoid is coupled to B I}
and those from the ends of the coils are respectively joined
to B 2 and B 3 . The two coils successively carry a current, and
so give reciprocating motion to the drill.
ELECTRIC PERCUSSIVE DRILLS.
379
The best results with reciprocating drills are likely to
be obtained by the use of a combination of pulsating and
alternating currents ; for the instroke can then be made
without much waste of power, and yet a very effective blow
can be delivered at each outstroke. This principle has been
applied in the Van Depoele electric percussive drill. One form
of the arrangement is shown diagrammatically in Fig. 221.
The dynamo may be of any continuous current make, with an
ordinary commutator, and the two usual fixed brushes at F x
and F 2 ; but it requires the addition of two revolving brushes,
R x and R 2 , separated by 180 deg. The coils in the solenoid
are three in number, 1 and 3, coupled in opposition to each
FIG. 221. Diagram of Van Depoele Electric Percussive Drill.
R 1? R,, revolving brushes ; F 1} F 2 , fixed brushes ; 1, 2, 3, coils of drill.
other, having few turns relatively to the main coil 2. The con-
nections are made as follows : Coils 1 and 3 are in series
with each other, and are coupled to the revolving brushes, R x
and R 2 ; these coils are, therefore, traversed by an alternate
current. Coil 2 is coupled to the fixed brush F l at one end,
and at the other to the junction of coil 3 with the rotat-
ing brush R x ; it is, therefore, energised by a pulsating current,
and exerts the chief effect on the plunger with a polarity
always in the same direction. The blow is made mainly by the
action of the centre coil, the end coils practically neutralising
each other. The return stroke is chiefly due to the resultant
pull of the two end coils, as the centre one varies between zero
and a maximum. At a first glance there seems to be in this
design a departure from simplicity without any compensating
380 ELECTRIC MOTIVE POWER.
gain, but on a closer examination it will be seen that it marks a
considerable advance, and that the chief difficulties referred
to in the early part of this section are to a great extent over-
come.
The instroke can be made as light and the outstroke as
heavy as required, both of these desirable ends being attained
without the use of any switch or complicated gear in the drill.
Also only three small conductors are required, and the dynamo
gives a continuous current, and can be used for lighting or
motor work.
The chief difficulty likely to be experienced with the Van
Depoele drill appears to lie in the heating of the iron cores from
hysteresis and eddy currents. This, however, will be gradually
overcome as experience suggests better methods of building the
core and framing.
APPENDIX.
LONG-DISTANCE TRANSMISSION OF POWER.
The distance through which power may be economically
transmitted by electricity depends upon so many varying con-
ditions that it is not possible to give a definite limit, although
one can be found for any particular case.* The theoretical
considerations affecting the losses in the line are discussed
fully in 16, pp. 70-79, and the practical difficulties in 17 to
20. The data given there are sufficient to enable a complete
investigation to be made for any case likely to occur in
practice. It may be useful, however, to have a table of the
relative costs of continuous-current power plants for the usual
pressures, and for such distances as are likely to commend
themselves for ordinary practice. It will be obvious, however,
that the figures must necessarily be but approximations, and
in some cases may be even misleading, unless the require-
ments of the problem are determined by one who has a prac-
tical knowledge of the work.
The author has prepared Table E E, in which the costs are
all expressed in terms of per H.P. delivered by the motor.
The line is supposed to be of bare sicilium bronze, erected on
wooden posts, with oil insulators. The dynamo cost includes
a proportional share of station instrument?, and that of the
motor includes switches and starting frames, whilst the line
cost is inclusive of posts, insulators, lightning arresters, and
other details.
The prices, which allow a slight margin for market fluctua-
tions, include packing. The erection cost is a variable
quantity, and must be determined for each case.
* See page 132.
382
ELECTRIC MOTIVE POWER.
Table E E. Cost of Continuous- Current Plants for Trans-
mission of Power.
-p 2
s
OD
t 0)
5
3^
Per H.P. delivered by Motor.
a II
l|
p^ 5
__
|||
^1
f
ll
6^
CL *'*
I i
D ^ na -!Wire. Motor.
Total
Electrical
O 8
H
h ti
M ^** ~
mo.
equip-
t 1 ) _Q
^
11
i
ment.
5,000
500
1-62
75
1-33
14-595 4-331 9'975
28-901
10,000
500
1-62
65
1-54
16-891 ! 7-218 9-975 I 34 084
15,000
5,000
500
800
1-62
1-013
50
80
2-00 21-945 7-166 9'975
1-25 |l5-763 3-715 10-972
39-086
30-450
10,000
800
1-013
75
1-33
16-773 6-825 10'972
34-570
15,000
800
1-013
70
]-43
18-033 9-187 10-972
38-192
20,000
800
1-013
65
1-54 19-411 10-828 10'973
41-211
25,000
800
1-013
60
1-67 21-052 i 13-072j 10-972 45 '096
30,000
800
1-013
55
1-82 :22-955 14-437 10-972 48'364
35,000
800
1-013
50
200 25-22615-2510-972 51423
10,000
1,000
0-81
80
1-25 16-405 9-515 11-471
37-392
15,000
1,000
0-81
75
1-33 17-456 9-89611-471! 38'823
20,000
1,000
0-81
70
143 118-768 '10-500 11-471 40'739
25,000
1,000
0-81
65
1-54 20-212 11-356 11-47 L: 43'049
30,000
1,003
0-81
60
1-67 21-918 12-022 11-471! 45-411
35,000
1,030
0-81
55
1-82 23-88712-52111-471 47879
40,000 1.000
0-81
50
2-00 2V250 12-678 11-471 50399
45,000 1,000
081
45
2-25 29-531 11-812 11-471 52'814
50,000
1,000
0-81 45 2-25 29-531 14-765 ll'47i
55767
In many of the problems brought before the electrical
engineer the distances are far greater than those assumed in
Table E E, and much higher pressures are necessary. The
author is of opinion that for extra long distances the best
way to deal with power transmission is by polyphase currents
{see Chapter VIII., especially 54, p. 267). If the pressure at
the alternators can be kept below 7,000 volts, it will not be
necessary to use step-up transformers ; but if the pressure
exceeds this it will generally be advisable to use them.
The cost of the alternators and transformers rapidly de-
creases as the output is increased. The cost of alternators
of, say, 100 kilowatts capacity is about <7 per kilowatt, in-
cluding station apparatus; while it has been estimated in
connection with the Niagara plant that, with outputs of 4,000
APPENDIX.
383
kilowatts, the cost will not exceed '2. Transformers of 100
kilowatt capacity average 5 per kilowatt, and in very large
sizes are offered by manufacturers at 1 per kilowatt. These
figures are so far apart that it is not possible to give any
general data for the generating plant, or even for the motors ;
but with the line a fair approximation is possible, since the
cost of copper may be taken as fairly constant within the
limits of the quantities required. Table FF has been pre-
Table FF. Cost of Line and of H.P. delivered, with Three-phase
Circuits, for various Distances and Pressures.
Distance
Area of
each
Effective
pressure
Current
Efficiency
of con-
Total
cost of
Cost per
H.P.
in
conductor
between
ductors
line at Is.
delivered
Feet.
in square
mains in
main in
in
per Ib. of
by
inches.
volts.
amperes.
per cent.
copper.
motor.
For 100 brake horse-power.
s.
25,000 0-0067
5,000 8-75 97-0
200
2
50,000 0-0067 7,000 6'25 \ 97'0
400
4
100,000 \ 0-0067 10,000
4-375
97-0
800
8
150,000 l 0-0067
10,000
4-375
95-5
1,200
12
250,000 ! 0-0067 10,000
4-375
92-5
2,OCO
20
375,000 0-0067 10,000
4-375
89-0
3,000
30
500,000 0-0067 10,000
4-375
86-0
4,000
40
For 200 brake horse-power.
1
25,000 i
0-0067
5,000
17-50
94-0
200
50,000 '
0-0067
7,000
13-5
92-5
400
100,000
0-0067 i 10,000
8-75
94-0
800
150,OCO
0-0067 ; ] 0,000
8-75
91-0
1,200
250,000
0-0067 ! 12,500
7-0
90-0
2,000
375,000 1
0-0067 15,000
5-83
90-0
3,000
500,000
0-0067 20,000 4-375
92-5
4,000
s.
1
2
10
15
20
For 500 brake horse -power.
25.000
0-0134
10,000
26-25 ; 97-5
400
50.000
0-0134 10,000 26-25 94-5
800 1
100,000
0-0134 [ 10,000
26-25
92-0
1,600 3
150.000
0-0134 10.000
26-25
84-5
2.400 4
250,000
0-0134 I 1^500
21-00 ! 84-0
4,000
8
375,000
0-0134 i 15.000
17-50 I 83-5
6,000
12
500,000
0-0134
20,000
13-15 ' 87-0
8,000
16
16
1 12
4
4 16
384 ELECTRIC MOTIVE POWER.
pared to give a rough idea of the cost of copper for overhead
lines for powers of 100, 200, and 500 H.P., delivered by motors
with three-phase currents at various efficiencies and pressures
up to 20,000 volts, and transmitted through various distances.
In these calculations an allowance of 5 per cent, has been
made for the sagging of the wires, so that a distance of
5,000ft. requires 1 mile, or 5,280ft., of conductor. For first
approximations each 5,000ft. in the first column may be taken
as a mile. The size of conductor chosen in the first two series
is No. 13 S.B.W., which is, perhaps, the smallest consistent with
the requirements of mechanical stability. The line losses are
chosen arbitrarily. The most instructive thing to notice is
the cost per horse-power delivered by the motor. The necessity
for high pressures is very apparent.
Tables EE and FF should be compared with Table X,
p. 268.
It
I
GENERAL ALPHABETICAL INDEX.
PAGE
Accumulators, Use of 136,297
Aerial Lines - 79,81,93,102
Air-Blast Lightning Discharger 108
Air-Gap ... 21,29,36,292
Alternate Currents, Advantages of 211,216
Principles of 150,218,221
Transmission of Power by ... 211, 216, 245, 251, 267, 283, 297
Alternate- Current Motor, Critical Exciting Current of 176
Motors, Polyphase 251,283
Motors, Single-Phase 149,177
Transformers 187, 197, 273
Alternator, Allgemeine Electricitiits Gesellschaft .., 290
- Armatures of 156,172
Asynchronous ... ... ... ... ... ... 179, 181
Brown, C. E. L 151,176
- Compound-Wound 232
Curves of Pressure of ... ... ... ... ... ... 157
Design of 156,175,292
- Effect of Iron Cores in 172
Efficiency of ... ... ... ... ... ... ... 172
Excitation of 176,179,231
Ferranti 172
- Fields of 156
Guicher 159,172
Heating of 172
-High-Pressure 175,208,269,284,286
. Kapp 175,291
Mordey 151,172,176,178
Oerlikon Polyphase 284
- Parallel Running of 215,238
- Polyphase or Multiphase ... 251,283
Series Working not Possible with Synchronous ... ... 213
- Speed of 176
Thomson-Houston ... ... ... ... ... ... 232
- Types of
Westinghouse
Ang.eofLead 32,38
Arc Lighting Dynamos ... ... ... ... ... ... 117, 232
Armature, Bar- Wound ... ... ... ... ... ... 17, 21
Current Density of 20,175
386 INDEX.
PAGE
Armature, Design of 18,49
-Diameter of 16,26,46
Driving Horns for ... ... ... ... ... ... 45
-Drum 17,172
- Equations for 16,18,46
-Gramme 17,46,172
-Heating of 20,175
- Hole in 19
- Load of (see also Circumflux) ... ... ... ... . . 21
- Magnetic Flux in 18,29,175
- Number of Turns in ... ... ... ... ... . . 19
- Plates for 35
- Radial Depth of 19
-Reactions 37,65,179,255
Section of, for Designing Purposes ... ... ... ... 49
-Speed of 20,176
- Total E.M.F 18
Arresters (see also Lightning Arresters and Dischargers) ... ... 102
Asynchronous Motor, Single-Phase ... ... .... ... ... 181
Atkinson's, LI. B., Safety Cable 321
Average Pressure ... ... ... ... ... ... ... ... 153
Back Electromotive Force of Motor ... ... ... ... ... 18
Turns 38,55
Baird Type of Coal-Cutter 372
Banti, Mons., Test of Asynchronous Single-Phase Motor ... ... 183
Bar Armatures ... ... ... ... ... ... ... 17,21
Bearer Wires for Overhead Lines ... ... ... ... 82, 93
Birtley Coal-Cutter 354
Board of Trade Unit 218
Boilers 7,304
Bronze for Line Wire ... 80,83
Brown, C. E. L., Alternator 151,290
Motors 180
Transformers 194
Built-in Systems of Conductors ... ... ..; ... .. ... 96
Cables, Armoured ,. ...87,221,308
Concentric 70,221,308,319
in Mines 70,307,313,318
in Pit Shafts 307
Insulated 84,87,307
Lead-Covered 87,307
Safety Mining 319,321
Callender System of Laying Conductors ... ... ... 88, 96
Callender-Ra worth System of Laying Conductors ... ... ... 99
Callender- Webber System of Laying Conductors ... ... ... 98
Capacity, Electrostatic, of Circuit 167,221,225,229
- of Alternator 229
-of the Line 221,225,229
of Transformer 208
Cardew Voltmeter 242
Carter, E. Tremlett, on Economic Law... ... ... ... ... 73
Caasell, Plant at 177,209
Central Station Dynamos, Regulation of ... ... ... ... 144
Centre of Gravity, Electrical, of Circuit 270
Centrifugal Force on Armatures ... ... ... ... ... 176
INDEX. 387
PAGE
Centrifugal Governors for Dynamos and Motors ... ... ... 119
Characteristic Curves, Dynamos, Motors, and Alternators ... 59, 142, 287
- Mechanical, of Motors ... ... ... ... ... 59
Choice of Plant for Transmission of Power ... ... ... 7,306
Circumflux, Permissible, for Armatures ... ... ... ... 21
Clock Diagram 168
Coal Consumption, Economised by Use of Sub-Stations ... ... 218
Coal-Cutter, Atkinson -Goolden 345
- Baird Type 372
Birtley 354
- Kurd 351
-Jeffrey 347,355,372
- Snell-Waterhouse 367
- Thomson-Houston (The General Electric Co., U.S.A.) 361, 372
- Wan tling and Johnson ... ... ... ... ... 371
Coal-Cutters, Rotary Bar Types 348
- Side Wheel Types 364
Coal-Cutting by Electricity 336,345,360,364
at Glass Houghton Colliery .... ... ... ... 367,370
Coal-Drilling 372
Heading 360,371
Combined Polyphase and Continuous Current Circuits ... ... 297
- Two- and Three-Phase Circuits 278
Commutation of Current in Armature, Act of... ... ... ... 39
Comparison of Electrical Systems of Transmitting Power, Weight
of Copper, &c. ... ... ... ... ... ... ... 268
Compensating Turns 38,231
Compensators, Electrical ... ... ... ... ... ... 233,236
Compound Winding 63,142,232
- Wound Alternator 232
Condenser Effects (see also Capacity) ... ... ... ... ... 167
Conductor, The 10, 69, 79, 84, 94, 102, 125, 218, 225
Conductors, Number of, in Armature ... ... ... ... ... 19
Conduits for Electric Cables 94
Connections of Polyphase Circuits ... ... ... ... ... 276
Constant Current, Distribution at ... ... ... ... ... 117
- Dynamos and Motors ... ... ... ... ... ... 117
- Regulators or Governors for ... ... ... ... ... 117
- Transformers 200
Constant Pressure, Distribution at ... ... .. ... ... 122
Consulting Engineer, Necessity for, in Power Work ... ... 303, 307
Conversion. Efficiency of Dynamo ... ... ... ... ... 9
- Efficiency of Transformers 189,196
Converters (see also Transformers) ... ... ... ... ... 187
Cooling Surface of Electric Machines .. ... .. ... 20. 31
Copper for Aerial or Overhead Lines 79,81,268,382
Quality of, for Overhead Wires 81
Specific Gravity of 80
Specific Resistance of 80
Tensile Strength of 80
Weight of, Required in Different Systems ... ... ... 268
Cores, Lamination of ... ... ... ... ... ... ... 173
- Watts lost by Hysteresis per cubic inch of ... ... ... 173
Cost of Electric Plant for Long Distance Transmission 381
Counter Electromotive Force in Motor ... ... ... ... 18
- of Self-induction 203,226
of the Line - 226
388 INDEX.
PAGE
Counter Electromotive Force in Transformer ... ... ... ... 203
Coupling of Compound- Wound Dynamos m Parallel ... ... ... 143
to Engines ... ... ... ... ... ... .. 6, 10
Critical Excitation of Alternator ... ... ... ... ... 176
Cross Induction (see also Armature Reactions) ... ... ... 37
Current, Constant, Distribution with ... ... ... ... ... 116
Constant, Economy of ... ... ... ... .. 116
Effective 153
Current Density in Armature Windings ... ... ... 20,175
- in Field Windings 31,52
- in Line 125,219
Currents in Quadrature ... ... ... ... ... ... .. 252
Curves, Characteristic 59.142,287
Curves of Horse-Power in Line ... ... .. ... ... ... 47
Magnetisation ... ... ... ... ... ... 35
- Pressure 154, 157, 177
Pressure, Drop of 47,226,287
- Torque 60, 6*, 67
Cycles of Magnetisation ... ... ... ... ... ... ... 150
- Periodic Current 150,154
Demagnetising Action of Armature ... ... ... ... ... 37
Action of Eddy Currents in Armature ... ... ... 39
Ampere Turns ... ... ... ... . . 38, 55
Density, Current, Permissible in Armature Coils ... ... ... 20
- Current, Permissible in Transformer .. ... ... ... 206
- Magnetic, in Armature Cores ... ... ... ... 29, 172
Magnetic, in Air Gap ... .. ... ... ... ... 29
Magnetic, in Field Cores ... ... ... ... ... 29
Magnetic, in Yokes ... ... ... ... ... 29, 33
Depoele. Van, Electric Percussive Rock Drill 379
Depth, Maximum Permissible, of Winding ... ... ... ... 21
- Radial, of Core 19
Design of Dynamo, Practical Example of ... ... ... 45,49
- Motor 43,49
- Poly phase Alternators 283,292
Diameter of Commutation ... ... ... ... ... ... 39
Dielectrics (see also Insulating Materials) ... ... .. ... 85
Difference of Pressure at Terminals ... .. ... ... ... 18
Dip Pumping by Electric Power ... .. ... ... ... 332
Dischargers (see also Lightning Dischargers) ... ... ... ... 102
Distortion of Magnetic Field ... ... ... .. ... 37.51
Distributors 123,134
Dobrowol- ky, von Doli vo, Polyphase Winding ... ... . . ... 265
Double Magnetic Circuit Field Magnet, Advantage of ... ... 24
Calculation for ... ... ... ... ... ... 37
Doulton's System of Stone Casing for Conductors ... ... ... 100
Dowson Gas Producer ... ... ... ... ... ... ... 9
Drag 011 Wires of Armature ... ... ... ... ... ... 44
Dra wing-in Systems of Conductors ... ... ... ... 98, 100
Drills, Electric Rock 372
Driving Horns ... ... ... ... ... ... ... ... 45
Drop Curves of Transformers ... ... ... ... ... ... 198
Drop of Pressure 47, 124, 142, 226, 231, 234
Drum Armatures ... ... ... ... ... ... ... ... 17
Dynamo and Motor in Series ... .. ... ... ... ... 121
Dynamo, Bipolar ... ... ... ... ... ... ... ... 22
INDEX. 389
PAGE
Dynamo, Compound- Wound ... ... ... 65, 143
Constant- Current 116
Design of 16,45,49
Efficiency of ... 9
Equalising ... ... ... ... ... ... ... 135
Functions of ... ... ... ... ... ... ... 13
Governor for Series ... ... ... ... ... ... 117
Magnetic Leakage, Coefficient of 33
Multipolar 25
Output of 10,16,28
Separately -Excited 66
Series-Wound 60 116
Shunt-Wound 61
Steam 10 304
Transmission of Power, for 10,26,144
Dynamometer ... ... ... ... ... ... ... ... 244
Dynamotor 137,140,216
Earthing the Middle Wire 272
Economic Law of Lord Kelvin ... ... ... ... ... ... 72
E. Tremlett Carter on 73
Economy of Coal Consumption by use of Sub-Stations ... ... 218
Eddy Currents 173, 201, 206
Efficiency of Alternators 172
Dynamos ... ... ... ... ..- ... ...9, 46
Dynamotors ... ... ... ... ... ... ... 216
Motors ... 11,46
the Line 72
Transformers ... ... 188, 196
Electric Coal-Cutting 336
Coal-Cutting Corporation ... ... ... ... 348, 351
Power Plant, An ... ... ... ... ... ... ... 5
Rock Drilling 336,337,373
Electrical Centre of Gravity of Circuit 270
Electricity in Mining ... ... ... ... ... ... ...2,301
Electromotive Force, Average ... ... ... ... ... 153, 166
Condenser 167, 226
Effective 153, 166
Resultant 165, 168
Self-Induction 165,226
Square Root of Mean Square... ... ... ... ... 154
Total of Alternator 153,156
- Total of Dynamo 18
Total of Motor 18
Engine- House Equipment ... ... ... ... ... ...6,303
Equalising Dynamo ... ... ... ... ... ... ... 135
Equations of Alternator ... ... ... ... ... ... 156,163
Current in Line 124,127
Dynamo 16,20,36,38,43,52
Line, Conductor, &c. ... ... ... ... ... ... 72
Motor, Special (see also Dynamo) ... ... ... ... 43
-Transformer 188,197,198,201,206
Transmission Problems 72, 75
Ergmeters 245
Eeson, W. B., Dynamo Equations ... ... ... ... ... 21
On Asynchronous Single-Phase Motors 182
Excitation, Critical 176, 178
DD
390 INDEX.
PAGE
Excitation, Equation for Field-Magnets ... ... . . . . 52
for Field-Magnets 37, 52, 55, 59, 176, 255
for Gap Space ... ... ... ... ... ... 36
Methods of 59
Exciter, Separate, Use of ... ... ... ... .. 68
Exploding Gas in Mines 319,322,325,337,338,341
External Characteristic 60,61,64,67
Fall of Pressure on Feeders 47, 124, 142, 226, 231, 234
Fans, Electric, in Mines ... ... ... ... .. ... ... 336
Feeder System of Distribution ... ... ... ... ... ... 131
Feeders ... 123,134,136,144
Ferranti Transformer ... ... ... ... ... ... ... 191
Field, Magnetic Distortion of ... ... ... ... ... ...24,51
Field, Rotary Magnetic 251,256,263,266
Field-Magnets, Bipolar 23
Coils, Size of, for 31
Design of 22, 27, 31, 37, 41, 176
Formula) for ... ... ... ... ... ... ... 31
Heating of ... ... ... ... ... ... ... 31
Induction in ... ... ... ... ... ... ... 29
Joints in ... ... ... ... ... ... ... 34
Multipolar 25
Number of Poles 25,174
Types of 23
Figure of Merit for Conductors 81
Fleming. Prof. J. A., on Alternate- Current Transformers ... 155, 197,
199, 202, 205, 208, 231
Flux, Magnetic 18,29"
Forbes, Prof. George, on Niagara Power Plant ... ... ... 272
Foucault Currents ' 173,201,206
Frankfort Experiment ... ... ... ... ... .. ... 209
Frequency of Periodic Currents 150,167,174.185,225,284
Effect of, on size of Alternators ... ... ... 167, 173
Fringe of Magnetic Field ... ... ... ... .-. ... 159
Ganz & Co., Method of Compensating for Drop in Feeders 235
Gap-space 21,29,36,292
Gas Engines .. ... ... ... ... ... ... ... 8
Gas, Producer 9
Gauge of Wire for Line, Choice of ... ... ... ... ..46,71
Goolden- Atkinson Electric Coal-Cutter 348
Pump ... ... ... ... ... ... ... 333
Safety Mining Motor 328,341
Governing Series Dynamos ... ... ... ... ... ... 117
Series Motors ... ... ._. ... ... ... ... 117
by Steam Pressure 179
Governors, Automatic 117,145,231,236
- Steam 179
Gramme, Dynamos, Advantages of 17
Armatures of ... ... ... ... ... ... ... 17
for Transmission of Power ... ... ... ... ... 46
Grounded Wire (see also Lightning Discharges) 105
Giilcher Alternator 159
Harmonic Function, An Alternate Current as an ... ... ... 154
Haseltine, R. M., Tests of Coal Cutters by 362-
INDEX. 391
PAGE
Haulage, Electric 329,330,332
Heating of Armatures ... ... ... ... ... ... ... 20
Field-Magnet Coils 31
Hedgehog Transformer ... ... ... ... ... 190
Henry, the Unit of Self-induction ... ... ... ... ... 166
High-Pressure Alternators 175,208,269,284,286
Dynamos ... 117, 270
Insulation 194,209
- Motors .. 1'7, '-470
-Transformers 195,209
Transmission of Power at ... 76, 116, 132, 209, 263, 283, 381
Hole Armatures 292
Hopkinson's, Drs. J. and E., Curves of Magnetic Induction... ... 34
Horse-Power of Dynamos and Motors ... ... ... ... 10, 28, 30
Curves of ... ... ... ... ... ... ... 47
Hurd, F., Coal-Cutter 351
Safety Cable 325
Hysteresis . ... ... ... ... ... ... ... ... 172
Waste of Power by 173,175,201,205
Impedance 225
Coil ... 241,337
Induction, Magnetic ... ... ... ... ... ... ...29,35
-Mutual 228
- Self 165, 223
Inductive Drop of Pressure ... ... ... ... ... ... 226
Insulated Cables 84
Insulating Substances, Table of ... ... ... ... ... ... 85
Insulators, High-Pressure ... ... ... ... ... ... 92
Low-Pressure ... ... ... ... ... ... ... 90
- Oil 92
Solid 90
Internal Characteristics of Series Dynamo and Motor ... ... 121
Iron, Induction Curves of... ... .., ... ... ... ... 35
for Magnets 22,29
Proportions of, in Dynamos and Motors ... ... ... 31, 34
in Transformers ... ... ... ... ... ... 196, 207
Iron-clad Field-Magnets 27,28,339
Jeffrey Electric Coal-Cutter 355
Electric Dip Pump 334,336
Electric Rock Drill 374
Johnson and Phillips Two-Phase Alternator ... ... ... ... 290
Joints in Magnetic Circuit ... ... ... ... ... ... 34
Junction Box ... ... ... ... ... ... ... 88, 97, 312
Kapp's Regulator for Drop of Pressure at End of Feeder ... ... 233
Two-Phase Alternator 291
Kelvin, Lord, Economic Law of ... ... ... ... ... ... 72
on Increase of Resistance with Alternate Currents ... 219
Kennelly, A. E 229
Kolbein, Mr., on Polyphase Circuits 267
Lag of Current behind Pressure ..., 168, 214, 223
Lamination of Armature Conductors ... ... ... ... ... 20
Lauff en, Transmission Plant at ... ... ... ... ... ... 209
Law of Alternate Currents 153
DD2
392 INDEX.
PAGE
Law of Magnetic Induction ... ... ... ... 34,37
Sine 154
Lead of Brushes, Dynamo and Motor 32,39
Leakage, Magnetic... ... ... ... ... ... 33
Magnetic, Coefficient of ... ... ... ... ... 33
Length of Mean Turn of Wire on Field-Magnets 52
Lightning Arresters, Functions of 102
for Power Plants 108,113
Telegraph and Telephone Types 106
Lightning Conductors ... ... ... 103
Lightning Discharger, Air- Blast Type 108
Alternate-Current 112
- Blow-out Type ~ 110
Wurts Ill
Lightning Discharges ... ... ... 102
Discharging Wire ... ... ... ... 105
Limits of Magnetisation ... ... ... ... ... 29, 35
Non-Sparking Load ... .. ... ... ... 21
Output of Dynamo and Motor 21,22
Limiting Distance of Transmitting Power ... ... ... 132, 268
Line, The 10, 69, 79, 84, 94, 102, 125, 218, 225, 381
Lines of Magnetic Force ... ... ... ... ... 18,29
Load Factor 205,210,217
Locke and Co.'s, Power Plant at Messrs. 301
Lodge, Prof. Oliver J., on Lightning Discharges 102
Long-Distance Transmission of Power 132,268,307,381
Long Shunt 64
Loss in Line (see also The Line) 125,219
Machines, Driven , 11
Magnetic Circuit, Single and Multiple ... 24
Flux 18,29
Leakage 33,158
Pull on Armature ... .. ... ... ... ... 54
Magnetisation, Curves of ... ... ... ... ... ... ... 35
- Resultant, with Polyphase Current Excitation 263
Marvin's Electric Percussive Rock Drill ... ... ... ... 378
Mean Power of an Alternate Current 171
Measurement of Alternate Currents ... ... ... ... 155,242
- of Drop in Feeders 234
Measuring Instruments ... ... ... .. ... ... ... 242
Mechanical Characteristics of Motors 60,64,67
Mines, Coal- Cutting in 345
- Exploding Gas by Electric Spark in 319, 322, 325, 337, 338, 341
Fans in ... ... ... ... ... ... 336
Haulage in 329,330.332
Pumping in 327,332
Rock-Drilling in 372
Winding in ... ... ... ... 331
Mining, Central Power Station for .... ... ... ... ... 3
Electricity in 2, 70, 301, 313, 318, 327, 337
Junction Boxes ... ... ... ... ... ... 312
Motors 45,327,338,341
Pownall's Safety System 325
Safety Cables 319, 321, 325
Shaft Cables 307
Switches and Resistances ... ... ... ... 315,316
INDEX. 393
PAGE
Mining, Underground Cables ... ... ... ... 313
- Uninsulated Keturn in 318
- Use of Cut-outs (Fuses) in 315,317
Mordey Alternator ... ... ... ... ... ... ... 15L
- Transformer ... 192, 196
Motor, Alternate-Current, Asynchronous, Single-Phase 179
Alternate-Current, Polyphase, 252, 256, 263, 266, 282, 286, 289, 292
- Alternate-Current, Synchronous 149
Armature of ... ... ... ... ... ... ... 43
- Compound- Wound ... ... ... ... ... ... 6
Counter Pressure of ... ... ... ... 18
Davis and Stokes Safety 341,343
Design of Direct- Current ... ... ... ... ... 43
Function of ... ... ... .. ... ... ... 13
Goolden Safety 328,340
- Government of Constant- Current ... ... ... ... 119
Lead of Brushes 39
Mavor and Coulson Steel- Clad Mining... ... ... ... 338
Prime ... ... ... ... ... ... .. ... 6
Safety 338
Separately-Excited 68
Series-Wound 60, 116
Shaft of 45
Shunt- Wound 61
-Torque of 43,54,327,337
Transmission of Power ... ... ... ... ... ...11,68
Multiphase Currents (see Polyphase)
Multiple- Wire Systems (see also Three- Wire Systems) 237
Multipolar Dynamos ... ... ... ... ... ... ... 25
- Design of 26
Mutual Induction of Circuits 228,229
Niagara, Power Plant at 272
Nolet Safety Cable 323
Notation, Algebraic Symbols used ... ... ... ... ... 15
Oerlikon Company Alternators 284.285
Asynchronous Single-Phase Motor ... ... ... ... 184
Oil as an Insulator 194
Insulators ... ... ... ... ... ... ... ... 92.
Output of Dynamos 10,16,28,30
-Motors 10,16,28,30
Transformers 205, 210
Over-Compounding Dynamos ... ... ... ... ... ...63,65
Parallel, Coupling of Compound- Wound Dynamos in... ... ... 143
Working 122, 176, 179, 215, 246
Percussive Eock Drills 374,376
Peripheral Pull on Armature ... ... ... ... ... ...44,54
- Speed 20, 176
Phase of Alternator 178,213
Conversion... ... ... ... ... ... ... ... 278
Indicator 239
Pitch of Poles of Alternators 157
Polar Axis, Shifting of 32,39
Cavity, Arc of 21,34
394 INDEX.
PAGE
Pole-pieces 32,174
Curving of ... ... ... ... .. ... ... 49
- Number of, Effect of 174
Pole Tips, Reversing Fields at 39
Polyphase Alternators (see also Alternators) ... ... ... ... 283
- Alternators, Design of 292
Currents 251, 256, 267, 278, 292, 337, 383
Motors 252, 256, 263, 266, 282, 286, 289, 292, 337
- Motors, Starting 265,293,337
Posts for Overhead Lines ... ... .. ... ... ... 93
Power, Electric Transmission of, 3, 5, 76, 132, 210, 218, 236, 263, 272, 283,
301, 383
Factor 188,226
Mean ... ... ... ... ... ... ... ... 171
Plant, Electric 3,6,383
Product of two Factors ... ... ... ... ... ... 116
Pownall, R. B. and Son, Safety Mining System 325
Predetermination of Curves of Dynamos ... ... ... ... 34
Pressure, Constant, Distribution ... ... ... ... ... 122
- Difference of, at Terminals 18
Drop of 47, 124, 142, 226, 231, 234
- High, Transmission .. 208, iil6
Producer Gas ... ... ... ... ... ... ... ... 9
Pumps, Electric, Centrifugal ... ... ... ... ... ... 334
Dip 332,334
Main 327
Rotary 335
Racing of Motors 337
Radial Depth of Armature ... ... ... ... ... .. 19
Ra worth -Callender Conduit ... ... ... ... ... ... 99
Reaction of Armature on Field 39,179,255
Rectifiers 297
Regulating Properties of Compound Winding 65
Properties of Series Winding 59,62,121
Properties of Shunt Winding ... . ... ... 62
Properties of Separate Excitation .. .. ... ... 66
Regulation, Automatic 117, 145, 231, 236, 337
by Exciting Circuit 144
by Shifting Brushes 117
Regulators, Dynamotors as ... ... ... ... 135,137,146
Series Dynamos as ... ... ... ... ... ... 146
Relation between Effective and Average Pressure in Alternators . . . 163
Relative Merits of Two-and Three-Phase Currents 267
Resistance, Increase of, with Alternate Currents ... ... ... 218
for Regulating Pressure 231,337
- Specific Table of 80,85
Retardation of Phase of Alternate Currents 168,178,203,214
' in Transformers ... ... ... ... ... ... 203
Return, Uninsulated ... ... ... ... ... ... 70, 318
Reversal of Current at Commutator 39
Reverse Parallel System of Distribution 130,216
Reversibility of Dynamo and Motor ... ... ... ... ... 11
Reversing of Motors in Mining Operations 329,332
Rock Drills, Electric ... 372
Rotarv Currents (see Polyphase)
Magnetic Field 251,256,263,266
INDEX. 395
PAGE
Safety Cable, Atkinson- Goolden 321
Charleton 322
Devices 247
Kurd 325
for Mining 318
Nolet 323
Safety Mining System, Pownall's 325
Motors 338
Say ers, W. B., Commutator Coils ... 40
Improvement in Dynamo Design ... ... ... 39,145
Winding for Drums ... ... ... ... ... ... 42
Schwabing, Dowson Gas Plant at ... ... ... ... ... 9
Scott, Charles F 225,278
Selection of Plant 7,8,327
Self-Induction 165,221
Causing Lag ... 165,171,223
Coefficient of 166
- Decrease of Output by 166,171
Decrease of Plant Efficiency by 171
Separate Excitation for Dynamos ... ... >.. ... ... 65
Series, Coupling Dynamos in ... ... ... ... ... 116,117
Coupling Motors in ... ... ... ... ... 116,117
Dynamo 59,121
Dynamo and Motor in 62,116,120
Motor 59,121
Power Transmission ... ... ... ... .. ... 116
Winding, Advantages of ... .. ... ... ... ... 62
Working 116,213
Shafts, Proportions of, for Motors 45
Shunt Dynamo ... ... ... ... ... ... ... ... 61
Shunt Motor ... ... ... ... ... ... ... ... 63
Silicium Bronze ... ... ... ... ... ... ... ... 83
Sine Curve 164
- Function 154
Law of Alternate Currents ... 154,163,176
Single-Phase Alternator (see also Alternators) 149
Alternate-Current Motor 149
Alternate Currents, Transmission of Power by ... ... 211
Size, Relation of, to Output of Dynamo ... ... ... ...28, 30
Slow-Speed Machine ... ... ... ... ... ... ... 10
Snell-Waterhouse Electric Coal-Cutter 367
Spacing Armature Winding ... ... ... ... ... ... 20
Spark Gap 107
Sparking, Cause of ... ... ... ... ... ... ... 21
- Load Limited by 21,39
Prevention of 21,39
Specific Resistance of Conductors ... ... ... ... ... 80
Speed, Dependence of Volts on 18,65
Effect of Low, in Alternators 174
in Relation to Cooling ... ... ... ... ... ... 20
in Relation to Power ... ... ... ... ... ... 18
Peripheral 20,176
Square-Section Wire for Armature ... ... ... ... ... 20
Stamp Batteries, Driving... ... ... ... ... ... ... 336
Standford's Water-Tight Joint in Piping 101
Starting Mining Motors 327,337
Station, Central Power, for Mining ... ... .,. ^
OF THX
0IU7IRSITY
396 INDEX.
PAGE
Steam Dynamos 10,304
Engines 6,303
Steel, Cast 29
Induction Curves of ... ... ... ... ... ... 35
Mild, Use of, in Dynamo Design ... ... ... ... 31
Steinmetz's Law 173
Step-up Transformers 208
Stokers, Mechanical 304
Stoneware Conduits ... ... ... ... ... ... ... 100
Sub-stations for Power Distribution ... ... ... ... 139,217
Sumpner, Dr. W. E 179.259
Symbols, List of 15,197
Synchroniser ... ... ... ... ... ... .. ... 239
Synchronism ... .. ... ... ... ... ... ... 213
Synchronous Motors 149,213,282
- Polyphase Motors .. 282
Systems of Transmitting Power, Weight of Copper required, etc. 267, 381
Tabulated Form for Designing Dynamos and Motors ... ... ... 56
Temperature, Rise of, in Armature .. .. ... ... ... 20
in Field Coils 31,32
Tests of American Electric Coal-Cutters 362
American Polyphase Motors ... ... ... ... ... 289
Oerlikon Polyphase Motors 286,289
Oerlikon Single -Phase Asynchronous Motors... ... ... 183
Thompson, Prof. S. P., on Alternate-Current Electro-Magnets ... 376
Alternate-Current Motors ... ... ... ... ... 178
- Phase Conversion 278
Thomson-Houston Air-Blast Lightning Discharger ... ... ... 108
: Alternator 240
Arc Dynamo ... ... ... ... ... ... ... 232
Coal-Cutter 372
Compensator ... ... ... ... ... ... ... 236
Transformers 195,196,200
Winding Engine, Electric ... ... ... ... ... 331
Three-Phase Circuits, Power in 261
Connections of ... ... ... ... ... ... ... 276
- Transmission of Power by ... ... ... ... .. 276
Three-Phase Alternators 256,273
Three-Wire Systems of Distribution ... 123, 132, 228, 237, 254, 272, 276
Size of Middle Wire 133
Toothed Armatures 42,292
Torque 43, 54, 118, 175, 263, 293, 337
Total E.M.F. of Armature 18
Traction, Motor 28,41
Series 120
Tr ansf ormer with Sub-divided Secondary Coil ... ... ... 237
Transformers, Brown, C. E. L 194
Brush 192, 196
Change Ratio of 229,246
Constant Current ... ... ... ... ... ... 199
Continuous Current (see Dynamotor)
Copper Loss in ... 201,205
Curves of ... 198,202,204
Design of Alternate Current 190, 197, 200, 205
Dobrowolski Three-Phase 274
Drop of Pressure ... ... ... ... ... ... 197
INDEX. 397
PAGE
Transformers, Efficiency of 188,196,205
- Ferrariti 191,201
Giilcher (W. B. Esson) 193
Heatingof 201,205
Hedgehog 190,199
Hysteretic Loss in ...201,205,207
- Iron in 207
Kapp ... ... ... ... ... ... ... ... 192
Kapp and Snell 193
- Kennedy, Rankin 194
Oerlikou Three-Phase, Tests of 286
Parallel Type 197
-Polyphase 273,281,286
- Power Factor of ... ... ... ... ... ... 188
Series Type 199
- Step-up 208
Thomson -Houston 195,196,200
- Three-Phase 274
Two-Phase 273
-Types of 187,190,199,237
- Use of, in Distribution of Power ... ... ... 187,209
Westinghouse . ...191,196,198
Transmission of Power 5, 76, 132, 210, 218, 236, 263, 272, 283, 301, 381
in Mines ...301,313,318
Systems of 115,211,267,276,381
Turbines 8
Two- and Three-Phase Circuits, Combination of ... ... ... 278
Relative Merits of 267
Two-Phase Currents (see also Polyphase Currents) ... ... 251,267
- Dynamo ... ... ... ... ... ... 253
- Motor 252
Two- Wire System of Distribution 124,128,381
Uninsulated Returns 70,318
Units and Symbols ... ... ... ... ... ... ... 15
Van Depoele Electric Percussive Rock Drill ... ... ... ... 379
Ventilation of Armature ... ... ... ... ... ... ... 21
- of Transformers 194
Wattless Currents 168
Wattmeter 179,188,243
Weight of Copper in Line 125,268
W'estinghouse Alternator... ... ... ... ... ... ... 172
Transformer 191,196
Willans and Robinson High-Speed Engine ... ... ... ... 305
Winding Engines, Electric, in Mines .. ... ... ... ... 331
Wood Casing in Mines 311,314
Work Diagram 169
Work per Revolution of Armature ... ... ... ... ... 44
Wurts Lightning Dischargers ... ... .. ... ,. 111,112
Yoke, Magnet ... ... ... ... ... ... ... ... 33
Proportions of ... ... ... ... ... ... ... 34
Yorkshire Engine Company Coal-Cutter ... ... .. ... 364
I EDISON & SWAN UNITED
ELECTRIC LIGHT COMPANY, LIMITED.
Head Offices, Warehouses, and Showrooms :
EDISWAN BUILDINGS, 36 and 37, QUEEN ST., CHEAPSIPE, B.C.
Telephone No. 1805.
The Largest Manufacturers in the World of Incandescence Electric
Lamps and Electric Light Fittings and Instruments.
Fitted with any Desired Tei
Contractors to the War Office, all Government Departments, many
Colonial Governments, Largest Steamship Companies,
Mining Companies, &c., &c.
SOLE MANUFACTURERS of the SUNLIGHT LAMP,
Single or Multiple Filament, from 100 to 2,000 candle-power.
MANUFACTUREBS of the WATERHOUSE ARC LAMP,
From 1,000 to 10.000 candle-power.
West End Depot, Warehouses, and Showrooms : 50, PARLIAMENT STREET, S.W.
Fully Illustrated Catalogue Free to any part of the World.
INDEX TO ILLUSTRATIONS.
I'IG. PAGE
1 Field-Magnets, Wrought Cores, Cast Yoke, Upright Type ... 23
2 Field-Magnets, Cast Iron Cores and Yoke, Upright Type 23
3 Field-Magnets, Wrought Iron, Inverted Upright Type 23
3A Field -Magnets, VN rought Iron, with Cast Iron Pole Pieces ... 23
4 \ Field-Magnets, Double Magnetic Circuit, Wrought Iron Cores, \ 24
5/ Cast Iron Pole Pieces ... J 25
6 Field- Magnets, Double Magnetic Circuit, Wrought Iron 25
7 Field-Magnets, Four Poles, Wrought Iron 26
8 Field-Magnets, Multipolar, Cast Iron 26
9 Field-Magnets, Armour-Clad 27
10 Thomson-Houston Tramcar Motor 28
11 Curves connecting Weight and Output of Dynamos and Motors 30
HA Curves connecting Cost and Output of Dynamos and Motors.. 30
12 Curves of Magnetic Induction in Iron and Air 35
12A Diagram of W. B. Savers' Commutator Coils 40
12s Sayers' Winding for Drum Armature 42
13 Curves of Drop of Pressure and Power Wasted per Mile of
Conductor 47
14 Diagram showing Method of Designing Dynamo or Motor ... 49
14A Diagram of Path of Lines of Force in Armature 51
15A Diagram of Series Winding 60
IBB External Characteristic Curve of Series Dynamo 60
15c Mechanical Characteristic Curve of Series Motor 60
16A Diagram of Shunt Winding 61
I6u External Characteristic Curve of Shunt Dynamo 61
]6c Mechanical Characteristic Curve of Shunt Motor 61
I?A Diagram of Compound Winding 64
17fi External Characteristic Curve of Over-Compounded Dynamo. 64
17c Mechanical Characteristic Curve of Compound Motor 64
18A Diagram of Separate-Excitation W hiding 67
18s External Characteristic Curve of Separately -Excited Dynamo. 67
18c Mechanical Characteristic Curve of Separately-Excited Motor. 67
19 Cable Hanger 82
20 Section of Armoured Cable 87
'21 Section of Concentric Armoured Cable 87
22 Junction Box for Single Cable 88
23 Junction Box for Concentric Cable, Plan 89
24 Junction Box for Concentric Cable, Elevation 89
25
Iron Stalks, Shackles, and Solid Insulators used for Low-
Pressure Aerial Lines 90
31 1
to[
.34 J
Oil Insulators used for High-Pressure Aerial Lines 92
.34
35 Leather Line-Suspender 93
36 Metal Line-Suspender 93
31 Callender Solid Bitu men System , Cross Section 96
400 ELECTEIG MOTIVE POWER.
FIG. PAGE,
38 Callender Solid Bitumen System, Longitudinal Section 96
39 Callender Solid Bitumen System, Cross Section of Service Box 97
40 Callender Solid Bitumen System, Plan of Service Box 97
41 Callender- Webber Dra wing-in System, Manhole 98
42 Callender- Webber Dra wing-in System, Casing 98
43 Callender-Raworth Dra wing-in System, Cross Section of Casing 99
44 Doul ton's Stoneware Casing, Cross Section 100
44A Doulton's Stoneware Casing, showing Joint 100
45 \ Doulton's Stoneware Casing, showing Expanding Mandril for
45A/ Jointing 100
46 Standf orth's Watertight Joint for Stoneware Pipes 101
47 Grounded Wire on Aerial Circuit 105
48 Lightning Arrester with Plain Gap 106
49 Lightning Arrester with Toothed Gap 106
50 Keystone Pattern Air-Blast Arc Breaker 108
51 The Power Circuit Lightning Arrester ~ 109
5lA Thomson-Houston Arc Line Protector 110
52 The Wurts Lightning Arrester Ill
53 The Wurts Alternate- Current Lightning Arrester 112
54 Double-Pole Lightning Arrester for Continuous-Current Circuit 114
55 Diagram of Motors in Series 116
56 Curves of Series- W ound Dynamo and Motor in Series 121
57 Diagram of Lamps in Series of Five on 500-volt Circuit 124
58 Diagram of Motors in Parallel 129'
59 Diagram of Reverse Parallel Circuit 130
60 Diagram of Feeder System 131
61 Diagram of Motors on Three-Wire System 132
62 Diagram of Three-Wire Feeder System with Three-Wire
Distributors 134
63 Diagram of High-Pressure Two-Wire Feeder System with
Regulator 135
64 Diagram of High-Pressure Two-Wire Feeder System with
Secondary Battery Regulator 136
65 Electric Construction Company's Dynamotor 138
66 Diagram of Feeder System with Dynamotors at Sub-Stations. 139
67 Diagram of Dynamotors in Series 141
68 Diagram of Rising Characteristic Curve of Compound Dynamo 142
69 Diagram of Connections of Two Compound- Wound Dynamos
in Parallel 143
70 Diagram of Separately-Excited Dynamos in Parallel 144
71 Curve showing Relation between Volts and Amperes with
Sayers' Regulator 146
72 Field-Magnet of Mordey Alternator . 151
73 Armature of Mordey Alternator 152
74 Sine Curve of Pressure or Current ... 154
75 Diagram of Typical Alternator Triangular Pressure Curve... 157
76 Diagram of Typical Alternator Flat-Top Triangular Pressure
Curve 157
77 Diagram of Typical Alternator nearly Rectangular Pressure
Curve 158
78 Diagram of Typical Alternator Triangular Pressure Curve... 158
79 Diagram of Typical Alternator Stepped Pressure Curve 160
80 Diagram showing Relation between Effective and Average
Pressure Sine Curve 160-
81 Diagram showing Relation between Effective and Average
Pressure Triangular Curve 161
82 Diagram showing Relation between Effective and Average
Pressure Semi-Circular Curve 162.
INDEX TO ILLUSTRATIONS. 401
FIG. PAGE
83 Diagram of Phases of Pressure 165
84 Diagram of Phases of Current 167
85 Clock Diagram 168
86 Work Diagram Current and Pressure in Phase 169
87 Work Diagram Current Lagging in Phase behind Pressure... 170
88 Volt-Ampere Curves of Alternator 177
88A Curves connecting Exciting and Armature Currents of
Alternator 178
89 Diagram of Connections of Brown Single-Phase Asynchronous
Motors 181
90 Hedgehog Transformer.. 190
91 W T estinghouse Transformer 191
92 Ferranti Transformer 191
93 Mordey Transformer 192
94 Kapp Transformer 192
95 Giilcher Transformer 193
96 Snell and Kapp Transformer 193
97 Eankin Kennedy Transformer 194
98 C. E. L. Brown Transformer 194
99 Thomson-Houston Transformer 195
100 Latest Form of Thomson-Houston Transformer 195
101 Efficiency Curves of Transformers 196
102 Pressure Curves of Westinghouse Transformer 198
102A Thomson-Houston Constant-Current Transformer 200
103 Curves of Ferranti Transformer 202
104 Typical Curves of Transformer 204
105 Curves of Pressure and Current in Alternator and Motor 214
106 Capacity Diagram 222
107 Self-induction Diagram 223
108 Capacity and Self-induction Diagram 224
109 Curves of Inductive E.M.F. in Line 226
110 Curves of Inductive Drop in Line 226
110A Curves of Inductive Drop in Line (part of Fig. 110 enlarged). 227
111 Mutual-induction E.M.F. in Line 229
112 Curve showing Change of Secondary Pressure in Transformer
due to Capacity 230
113 Curve showing Change of Primary Pressure in Transformer
due to Capacity 230
114 Curve showing Change of Transformation Ratio in Trans-
former due to Capacity 231
115 Thomson-Houston Method of Compounding Alternator 232
116 Kapp' s Method of Regulating Drop of Pressure in Feeder ... 233
117 Diagram of Connections of Station Voltmeter for Reading
Pressure at Far End of Feeder 234
118 Ganz's Method of Compensating for Drop of Pressure in
Feeder 235
119 Prof. Elihu Thomson's Compensator System as applied to
Power Circuit 236
120 Diagram of Transformer with Secondary Coils divided into
Separate Circuits 237
121 Diagram of Synchroniser Connections 239
122 Impedance Coil as arranged for putting Alternators in Parallel 240
123 Impedance Coil 241
124 Lord Kelvin's Engine Room Wattmeter, General View 244
125 Lord Kelvin's Wattmeter Shunt Coils and Suspension Details 245
126 Major Cardew's Earthing Device for Transformers 248
127 Ferranti's Earthing Device 249
402 ELECTRIC MOTIVE POWER.
FIG. PAGE.
128 Diagram of Four-Pole Two-Phase Motor ........................... 252.
129 Diagram of Two Periodic Currents with Common Ke turn ...... 254
130 Diagram of Excitation Variation with Two Currents in Quad-
rature .................................................................. 255
131 Diagram of Three Periodic Currents with Phase Intervals
of 120deg ................................................................ 256
132 Diagram of Three-Phase Parallel Coupling ........................ 257
133 Diagram of Three-Phase Dynamo Coupled to Motor .. 257
-
Diagrams of Three-Phase Circuits ....................... ........ 258
136 Diagram of Phases of Current in Closed Three-Phase Circuit 259
137 Diagram of Three- Phase Series Coupling ....................... 260
138 Diagram of Phases of Current in Open-Type Three-Phase
Circuit ................................................................. 261
139 Method of Measuring Power in Three-Phase Circuit with
Mains Equally Loaded ............................................... 262
140 Method of Measuring Power in Three-Phase Circuit with
Mains Unequally Loaded ............................. .............. 262
141 Diagram of Excitation Variation with Three-Phase Currents.. 264
145 Dobrowolski's Combined Series and Parallel Three-Phase
Coupling ................................................................. 265
143 Diagram showing Ampere-Turns with Parallel Three-Phase
Coupling ............................ ........... .. ........................ 266
144 Diagram showing Ampere-Turns with Series Three-Phase
Coupling ................................................................ 266
145 Diagram of Effective and Maximum Pressures in Single-Phase
Circuit .............................................. .................. 267
146 } Diagrams of Effective and Maximum Pressures in Two-Phase / 269
147 / Circuit with Three Wires ......................................... \270
148 Diagram of Effective and Maximum Pressures with Three-
Phase Circuit ........................................................... 271
149 Diagram of Four-Wire Two-Phase Circuit with Two Single-
Phase Transf ormers .......... ...................................... 273
150 Dobrowolski Three-Phase Transformer .............. ............. 274
151 General Diagram of Polyphase Transformer Connections ...... 275
1 ^9 1
1531 Dia S rams of Three-Phase Power Plants ......... .................... 276
Diagrams of Three-Phase Circuit Connections .................... 277
.jrr-. j- Diagrams showing Conversion of Two- to Three-Phase ........ 1 97Q
158 Diagram of Two- to Three-Phase Transformer ..................... 280
159 Diagram of Pressure Distribution with Phase Conversion ...... 280
160 Diagram of Combined Two- and Three-Phase Circuit ......... 281
161 Diagram of Synchronous Polyphase Alternator ................. 283
162 Oerlikon Low-Pressure Polyphase Alternator ..................... 284
163 Oerlikon High-Pressure Polyphase Alternator ..................... 285
164 Characteristic Curve of Three-Phase Oerlikon Alternator ...... 287
166 I ^ er likon Asynchronous Polyphase Motor ................... ..... j noo
167 Allgemeine Electricitats-Gesellschaft Asynchronous Polyphase
Motor ..................................................................... 290
168 Johnson and Phillips Two-Phase Alternator ........................ 291
170 I Grooves for Windings of Polyphase Machine ............ ....... 292
171 Diagram showing Construction of Polyphase Motor ............ 292
17/M fSQ
173 > Curves of Torque of Polyphase Motors .............................. \2Q5
j
INDEX TO ILLUSTRATIONS. 403
FIG. PAGE
174 Curves connecting Power Factor and Output of Polyphase
Motors 296-
175 Diagram of Polyphase Continuous-Current Converter 297
176 Diagram of Rectified Alternate Current 298
177 Ferranti Rectifier 298
178 Steam Dynamo, Open Type Engine 305
179 Steam Dynamo, Closed Type Engine 306'
180 Armoured Concentric Cable 308
182J Wood Casings for Pit Work 311
183 Junction Box for Mines . 312
184 )
184A \ Gas-Tight Starting Switch and Resistance for Mines
184s I
316
317
318
1 ft^l ^
186 f Concentric Cables with Uninsulated Return . ... 320
187 Atkinson Safety Cable 321
188) (323
189 \ Nolet Safety Cable \ 323
190 J 1 324
191 Three-Throw Electric Main Pump 326-
192 Endless Rope Electric Hauling Engine 328
193 Main and Tail Rope Electric Hauling Engine 330
194 Electric Winding Engine 331
195 Electric Three-Throw Dip Pump 333
195A Electric Three-Throw Dip Pump on Trolley 334
196 Electric Centrifugal Dip Pump 335
196A Jeffrey Double Rotary Dip Pump 336
197 Mavor and Coulson Steel-clad Mining Motor 339
198 Goolden-Atkinson Safety Mining Motor 340
199 Davis and Stokes Safety Mining Motor 342
200 Goolden-Atkinson Electric Coal-Cutter, Elevation 349
200A Goolden-Atkinson Electric Coal-Cutter, Cross Section 349
201 Goolden-Atkinson Electric Cutter-Bar 350
20lA Goolden-Atkinson Electric Coal-Cutter, Method of Working... 350
202 Kurd's Electric Coal-Cutter 352
gQ^j Birtley Rotary Bar Electric Coal-Cutter 353
205 Section of Birtley Cutter-Bar 355
206 Jeffrey Electric Coal-Cutter, Method of Working 356
207 Jeffrey Electric Coal-Cut' er, Perspective View 357
208 Jeffrey Electric Coal-Cutter on Trolley 359
208A Rotary Bar Coal-Cutter of General Electric Co 384
209 Yorkshire Engine Company's Side-Wheel Compressed Air
Coal-Cutter 365
210 Cutter-Wheel, Yorkshire Engine Company 366
211 Snell-Waterhouse Electric Coal-Cutter, Plan 368
212 Snell-Waterhouse Coal-Cutter, Longitudinal View 369
213 Snell-Waterhouse Coal-Cutter, End View 370
214 Wantling-Johnson Electric Coal-Cutter and Heading Machine 371
215 Plan of Cutter Wheels of Wantling-Johnson Coal-Cutter 371
216 Thomson-Houston Electric Coal-Cutter 372
217 Jeffrey Rotary Electric Rock and Coal Drill 375
218 Diagram of Electric Percussive Drill, with Two-Way Switch.. 377
219 Diagram of Electric Percussive Drill for Use on Two-Phase Circuit 378
220 Diagram of Marvin Electric Percussive Drill 378
221 Diagram of Van Depoele Electric Percussive Drill 379
CABLESi^WIRES
FOE
IptNC, WORKSHOP, TRAMWAY,
AXD OTHER
ELECTRIC LIGHT AND POWER
CIRCUITS, &c.
CONCENTRBG CABLES.
SIGNAL CIRCUIT CABLES AND WIRES.
BOTH
LOW AND HIGH
TENSION,
To fire 15, 8, & 2
Shots.
EXPLODER
TWIN CABLES.
Fuses, and
all Accessories for
Export.
INSULATORS,
IRONWORK,
LINE STORES &TOOLS,
FOB
Aerial and Mining, Telephone, Telegraph,
Electric Light and Power Circuits.
ALSO
TELEPHONES AND BATTERIES.
THE TELEGRAPH MFG. COMPANY, LTD.,
HELSBY (near Warrington), and
11, QUEEN VICTORIA STREET, LONDON, E.G.
LIST OF TABLES OF DATA AND TESTS.
PAGE
A Permissible Fall of Pressure in Armature Expressed as a Per-
centage of the Total E.M.F 18
B Radial Depth of Core of Gramme Armature 19
C Comparative Magnetic Inductions in Wrought Iron, Cast Iron,
and Air 29
D Magnetic Leakage Coefficients for various types of Field-Magnets 33
E Tabulated Form for Use in Designing Dynamos and Motors ... 56
F Specific Resistance, Specific Gravity, and Tensile Strength of
various Conductors 80
G Specific Resistance of Dielectrics compared with that of Mica ... 85
H Usual Spans with Hard -drawn Copper Conductors 94
I Percentage Drop of Pressure in Two- Wire Mains for various
Current Densities and Distances 128
J Ratio between Effective and Average Pressures in Alternators
having Pressure Curves of various orders 163
K Proportions of Alternator Field-Poles and Armature Coils in
terms of the Pitch, and Consequent Values of Tc 164
L Power Wasted by Hysteresis in Watts per cubic inch 173
M Speed of Alternators with various Numbers of Field-Poles for
the usual Frequencies 174
N Permissible Induction in Alternators for the usual Frequencies... 175
P
Q ]- Tests of Oerlikon Single-phase Asynchronous Motors 182
It
S
T Data of Oerlikon Asynchronous Single-phase Motors 184
U Efficiencies of various Transformers 189
V Increase of Resistance of Conductors in Alternate-Current
Working 219
W Examples of Practical Measuring Instruments suitable for Power
Stations 242
X Weights of Line Copper required with different Systems of
Transmitting Power 268
Y Data of Oerlikon Three-phase Transformers 286
Z Data of Oerlikon Low-pressure Three-phase Alternators 286
A A Data of Oerlikon High-pressure Three-phase Alternators 286
B B Tests of Oerlikon Small Three-phase Motors 289
CO Data of American Three-phase Motors 289
D D Tests of American Electric Coal-Cutters {^2
t 363
E E Cost of Continuous- Current Power Plants in terms of per H.P.
delivered by Motor ... 382
F F Cost of Line and of H.P. delivered, with Three-phase Circuits, for
various Distances and Pressures 383
EE
SIEMENS BROS. & CO.,
LIDMIITIEID.,
(Ekctncal & telegraph (Enptters.
MANUFACTURERS OF
DYNAMOS AND . . .
. . . ALTERNATORS,
MOTORS FOR ALL PURPOSES.
CABLES and WIRES,
ELECTRICAL and TELEGRAPH INSTRUMENTS.
CONTRACTORS FOR
TRANSMISSION* POWER PLANT.
ELECTRIC TRAMWAYS and RAILWAYS,
ELECTRIC LIGHTING.
Head Office :
12, QUEEN ANNE'S GATE, LONDON, S.W.
Branch Offices :
21, GRAINGER ST. WEST, NEWCASTLE ON-TYNE ;
261, WEST GEORGE STREET, GLASGOW;
5$, MARKET STREET, MELBOURNE.
Works: WOOLWICH, KE1VT.
LIST OF FORMULA
NO. PACK
(1) Approximate Output of Gramme-type Dynamo 16
(2) Approximate Output of Drum-type Dynamo 16
(3) Approximate Output of Gramme-type Motor 17
(4) Approximate Output of Drum-type Motor 17
(5) (6) Total E.M.F. of Armature 18
(7) Magnetic Flux in Armature 18
(8) Number of Turns of Wire on Armature 19
(8A) Eise of Temperature of Armature 20
(9) Permissible Circumflux of Gramme Armature 22
^10) Permissible Circumflux of Drum Armature 22
(10A) Rise of Temperature of Field-Magnets 32
(11) Excitation for Air Gap 36
(12) Total Excitation for Dynamo or Motor 37
(13) Compensating Turns for Gramme Armature 38
(14) Compensating Turns for Drum Armature 38
(15) Torque in terms of Armature Constants in C.G.S. Units 43
(16) Torque in terms of Armature Constants in Pound-Feet Units 43
(17) Work per Revolution of Armature 44
(18) Torque in Pound-Feet 44
(19) Peripheral Pull exerted by Armature 44
(20) Equivalent or Average Current 73
(21) Lord Kelvin's Law of Economy 73
(2lA) Mr. E. Tremlett Carter's Modification of Law of Economy ... 73
(22) Figure of Merit of a Conducting Metal 81
<23) (24) (25) Fall of Pressure in Conductor 127
(26) (27) Effective value of total E.M.F. in Alternator 155
(28) Average total E.M.F. of Alternator : parallel connection 156
(29) Average total E.M.F. of Alternator : series connection 156
(30) Maximum total E.M.F. of Alternator : parallel connection ... 156
(31) Maximum total E.M.F. of Alternator : series connection 156
(32) Effective total E.M.F. of Alternator : parallel connection ... 156
(33) Effective total E.M.F. of Alternator : series connection 156
(34) Maximum E.M.F. of Alternator with Triangular Curve of
Pressure 159
(35) Effective E.M.F. of Alternator with Triangular Curve of
Pressure 163
(36) Relation between E.M.F.'s in Alternate-Current Circuit 165
<37) \Maximum E.M.F. of Self-induction in Alternate- Current
(38) / Circuit 166
<39) Effective E.M.F. of Self-induction in Alternate- Current
Circuit 166
(40) Relation between Currents in Alternate- Current Circuit 168
(41) Mean Power in Alternate- Current Circuit 171
(42) Drop of Pressure in Transformer 197
(43) Drop of Pressure in Transformer due to Magnetic Leakage... 198
(44) Number of Watts lost in Iron Cores 201
(45) Effective Primary Pressure in Transformer 206
(46) Number of Secondary Turns in Transformer 207
<48) Capacity of Conductor in Microfarads 222
(49) Condenser Current in Amperes 222
EE2
JOHN DAVIS & SON,
All Saints Works, Derby, and 118, Newgate St., London.
Electric Xigbt anfc power Engineers.
ELECTRIC LIGHTING PLANTS FOR COLLIERIES, MILLS,
WORKS, RESIDENCES, &c.
Electric Haulage Plants. Electric Pumping Plants.
JEFFREY COAL-CUTTING & DRILLING MACHINES.
The Jeffrey Coal-Cutting Machines are constructed for Long- Wall or Pillar and
Stall Work, and are operated by electricity or compressed-air power. Over 600
Jeffrey machines are in daily use, and the number is rapidly increasing.
Estimates furnished and Mines examined to ascertain the suitability
of Jeffrey machines.
THE
MOTOR
Is employed in gassy mines for dip pumps, &c. Has withstood the test of time
and all attempts to explode.
FOWLER-WARING GABLES GO. (L-),
32, Victoria Street,
Westminster, S.W.
Works:
North Woolwich, B.
MANUFACTURED OF
ELECTRIC CABLES FOR ALL PURPOSES.
ARMOURED CABLES, specially adapted for MINING IN-
STALLATIONS and damp situations.
High Insulation, Durability & Mechanical Strength.
WORKING IN ALL PARTS OF THE WORLD.
For Transmission of Power, Lighting, Signalling, &c., &c.
Estimates and further particulars on application.
MANUFACTURERS OF
LIGHTING STATIONS
AND
Transmission of
Power.
DYNAMOS
AND MOTORS,
CABLES
author ventures to think that, in this case, the absence of mathematics is far from unjustifiable.
1, 2, and 3, Salisbury Court, Fleet Street, London, E.G.
"The Electrician" Printing and Publishing Co., Ltd., 11
" THE ELECTRICIAN " SERIES continued.
Over 300 pages, 106 illustrations. Price 10s. 6d., post free.
The ART of ELECTROLYTIC SEPARATION of METALS.
(THEOKETICAL AND PEACTICAL.)
By GEORGE GORE, LLJX, F.R.S.
THE ONLY BOOK ON THIS IMPORTANT SUBJECT IN ANY LANGUAGE.
SYNOPSIS OF CONTENTS.
HISTORICAL SKETCH.
Discovery of Voltaic and Magneto-Electricity First Application of Electrolysis to the
Refining of Copper List of Electrolytic Refineries.
THEORETICAL DIVISION.
Section A. : Chief Electrical Facts and Principles of the Subject. Electric Polarity and
Induction, Quantity, Capacity, Potential Electromotive Force Electric Current Conduction
and Insulation Electric Conduction Resistance.
Section B. : Cliief Thermal Phenomena. Heat of Conduction Resistance Thermal Units,
Symbols, and Formulae.
Section C. : Chief Chemical Facts and Principles of the Subject. Explanation of Chemical
Terms Symbols and Atomic Weights Chemical Formulae and Molecular Weights Relation of
Heat to Chemical Action.
Section D.: Chief Facts of Chemico- Electric or Voltaic Action. Electrical Theory of
Chemistry Relation of Chemical Heat to Volta Motive Force Volta-Electric Relations of
Metals in Electrolytes Voltaic Batteries Relative Amounts of Voltaic Current produced by
Different Metals.
Section 2. : Chief Facts of Electro-Chemical Action. Definition of Electrolysis Arrange-
ments for Producing Electrolysis Modes of Preparing Solutions Nomenclature Physical
Structure of Electro-Deposited Metals Incidental Phenomena attending Electrolysis Decom-
posability of Electrolytes Electro- Chemical Equivalents of Substances Consumption of Electric
Energy in Electrolysis.
Section F. : The Generation of Electric Currents by Dynamo Machines. Definition of a
Dynamo and of a Magnetic Field Electro-Magnetic Induction Lines of Magnetic Force.
PRACTICAL DIVISION.
Section G. : Establishing and Working an Electrolytic Copper Refinery. Planning a Refinery
Kinds of Dynamos Employed Choice and Care of Dynamo The Depositing Room The Vats
The Electrodes The Main Conductors Expenditure of Mechanical Power and Electric
Energy Cost of Electrolytic Refining.
Section H. : Other Applications of Electrolysis in Separating and Refining Metals. Elec-
trolytic Refining of Copper by other Methods Extraction of Copper from Minerals and Mineral
Waters Electrolytic Refining of Silver Bullion and of Lead Separation of Antimony, of Tin, of
Aluminium, of Zinc, of Magnesium, of Sodium and Potassium, of Gold Electrolytic Refining of
Nickel Electric Smelting.
Appendix. Useful Tables and Data.
Second Edition, price 2s., post free.
ELECTRO-CHEMISTRY.
By GEORGE GOEE, LL.D., F.E.S.
This book contains, in systematic order, the chief principles and facts of electro-chemistry,
and is intended to supply to the student of electro-plating and electro-metallurgy a scientific basis
npon which to build the additional practical knowledge and experience of his trade. A scientific
foundation, such as is here given, of the art of electro -metallurgy is indispensable to the electro-
depositor who wishes to excel in his calling, and should be studied previously to and simul-
taneously with practical working. As the study of electro-chemistry includes a knowledge not
only of the conditions under which a given substance is electrolytically separated, but also of the
electrolytic effect of a current on individual compounds, both are described, and the series' of
substances are treated in systematic order. An indispensable book to Electro-Metallurgists.
1, 2, and 3, Salisbury Court, Fleet Street, London, E.G.
12 "The Electrician" Printing and Publishing Co., Ltd.
"THE ELECTRICIAN" SERIES continued.
Electrical Laboratory Notes & Forms.
ARRANGED AND PREPARED BY
I>r. J. A.. FJLESIMIIVO, M.A., FJR.S.
Professor of Electrical Engineering in University College, London.
These " Laboratory Notes and Forms " have been prepared to assist Teachers, Demonstrators
and Students in Electrical Laboratories, and to enable the Teacher to economise time. They
consist of a series of (about) Twenty Elementary and (about) Twenty Advanced Exercises
in Practical Electrical Measurements and Testing. For each of these Exercises a four-page Report
Sheet has been prepared, two pages of which are occupied with a condensed account of the theory
and practical instructions for performing the particular Experiment, the other two pages being
ruled up in lettered columns, to be filled in by the Student with the observed and calculated
quantities. Where simple diagrams will assist the Student, these have been supplied. These
Exercises are for the most part based on the methods in use in the Electrical Engineering
Laboratories of University College, London ; but they are perfectly general, and can be put into
practice in any Electrical Laboratory.
Each Form is supplied either singly at 4d. nett, or at 3s. 6d. per dozen nett (assorted or
otherwise as required) ; in sets of any three at Is. nett ; or the set of (about) Twenty Elementary
(or Advanced) Exercises can be obtained, price 5s. 6d. nett. The complete set of Elementary
and Advanced Exercises are price 10s. 6d. nett, or in a handy Portfolio, 12s. nett, or bound in
strong cloth case, price 12s. 6d. nett.
Spare Tabulated Sheets for Observations, price Id. each nett.
Strong Portfolios, price Is. each.
The very best quality foolscap sectional paper (16in. by 13in.) can be supplied, price Is.
per dozen sheets nett.
^Yoit' ready.)
1. The Exploration of Magnetic Fields.
2. The Magnetic Field of a Circular Current.
3. The Standardization of a Tangent Galvanometer by the Water Voltameter.
4. The Measurement of Electrical Resistance by the Divided Wire Bridge.
5. The Calibration of the Ballistic Galvanometer.
6. The Determination of Magnetic Field Strength.
7. Experiments with Standard Magnetic Fields.
. The Determination of the Interpolar Field of an Electromagnet with Varying Lengths of Air Gap.
9. The Determination of Resistance and Temperature Coefficients with the Post Office Pattern of Wheatstpne's
10. The Determiuation of Electromotive Force by the Potentiometer. [Bridge.
11. The Determination of Current Strength by the Potentiometer.
12. A Complete Test of a Primary Battery.
13. The Calibration of a Voltmeter by the Potentiometer.
14. A Photometric Examination of an Incandescent Lamp.
15. The Determination of the Absorptive Powers of Semi-Transparent Screens.
18. The Determination of the Reflective Powers of Various Surfaces.
17. The Determination of the Electrical Efficiency of an Electromotor by the Cradle Method.
18. The Determination of the Efficiency of an Electromotor by the Brake Method.
19. The Efficiency Test of a Combined Motor Generator Plant.
20. Test of a Gas Engine and Dynamo Plant.
ADYACTGIED SERIES.- (Ready shortly.)
21. The Determination of the Specific Electrical Resistance of a Sample of Wire.
22. The Measurement of Low Resistances by the Potentiometer.
23. The Measurement of Armature Resistances.
24. The Standardization of an Ampere-meter by Copper Deposit.
25. The Standardization of a Voltmeter by the Potentiometer.
26. The Standardization of an Ammeter by the Potentiometer.
27. The Determination of the Magnetic Permeability of a Sample of Iron.
28. The Standardization of a High Tension Voltmeter.
29. The Efficiency Test of a Transformer.
30. The Delineation of the Curves of Current and Electromotive Force of a Transformer
SI. The Photometric Examination of an Arc Lamp.
32. The Measurement of Insulation and High Resistance.
33. The Examination of a Secondary Cell by the Potentiometer.
34. The Efficiency Test of an Alternator.
35. The Complete Efficiency Test of a Secondary Battery.
36. The Calibration of Electric Meters.
57. The Determination of the Hysteresis Curve of Iron by the Magnetometer.
38. The Determination of Hysteresis Loss by the Wattmeter.
39. The Determination of the Capacity of a Concentric Cable.
40. The Complete Hopkinson Test of a Pair of Dynamos.
1, 2, and 3, Salisbury Court, Fleet Street, London, E.G.
"The Electrician" Printing and Publishing Co., Ltd., IB
"THE ELECTRICIAN" SERIES continued.
320 pages, 155 illustrations. Price 6s. 6d., post free.
PRACTICAL NOTES FOR ELECTRICAL STUDENTS.
LAWS, UNITS, AND SIMPLE MEASURING INSTRUMENTS.
By A. E. KENNELLY and H. D. WILKINSON, M.I.E.E.
SYNOPSIS OF CONTENTS.
CHAPTER I. Introductory.
Early Ideas Electricity produced by Chemical Energy Kequirements in a good Cell
Chemical Action.
CHAPTER H. Batteries.
Daniell, Minotto, Thompson Tray, Leclanche, Fuller, De la Kue and Standard Cells.
CHAPTER III. Electromotive Force and Potential
Connecting Cells in Series Distribution of Potential in a Battery.
CHAPTER IV. Resistance.
Eelative Kesistance of Metals Relation between Length, Diameter, and Weight of Telegraph
Conductors Eesistances in Series and in Multiple Arc.
CHAPTER V. Current.
Effect of "Opening " or " Closing" a Circuit Velocity of Current Retardation Period of
Constant Flow The Ampere The Coulomb The Milliampere Ohm's Law.
CHAPTER VI. Current Indicators.
Detectors or Indicators Directions for Making Detectors for Telegraph and for Telephone
Work Indicators for Large Current.
CHAPTER VII. Simple Tests with Indicators.
Tests for " Continuity," for Fault in Telegraph Apparatus, for Identity of Wires, for Insu-
lationOverhead Line Insulators G.P.O. Standard Indicator.
CHAPTER VIII. Calibration of Current Indicators.
Calibration by Low-Resistance Cells Calibration Curves Simultaneous Calibration of
Instruments of Similar Sensitiveness and of Differing Sensitiveness Use of the "Shunt"
Comparison by Tangent Galvanometer.
CHAPTER IX. Magnetic Fields and their Measurements.
Permanent Magnetic Fields Electro-Magnetic Fields Magnetic Fields of Coils and Solenoids.
TABLE OF NATURAL TANGENTS.
190 pages, 116 illustrations. Price 3s. 6d., post free.
THE STEAM-ENGINE INDICATOR & INDICATOR DIAGRAMS.
A PRACTICAL TREATISE ON.
Edited by W. W. BEAUMONT, M.I.C.E., M.I.M.E., &c.
This useful book considers the object of an Indicator Diagram, or what it is desired that the
Diagram shall show ; describes the construction for the Indicator in its various forms ; describes
the apparatus necessary for the attachment of the Indicator to the engine, and how to use the
instrument ; gives examples of diagrams from all kinds of engines most in use, comparing these
diagrams and showing how far they agree with theoretical diagrams ; and shows the most simple
methods of calculating and constructing theoretical curves of expansion, and of comparing the
actual with the theoretical performance of steam in the steam engine cylinder.
Fully illustrated. Price Is. 6d., post free Is. 9d.
THE MANUFACTURE OF ELECTRIC LIGHT CARBONS.
A Practical Guide to the Establishment of a Carbon Manufactory.
Contains the results of several years' experiments and experience in carbon candle-making, and
gives full particulars, with many illustrations, of the whole process.
1, 2, and 3, Salisbury Court, Fleet Street, London, E.C.
14 "The Electrician" Printing and Publishing Co., Ltd.,
"THE ELECTRICIAN" SERIES continued.
Over 400 pages, nearly 250 illustrations. Price 10s. 6d.
ELECTRIC MOTIVE POWER.
By ALBION T. SNELL, Assoc.M.lNST.C.E., M.I.E.E.
The rapid spread of electrical work in collieries, mines, and elsewhere has created a demand for a practical
fcook on the subject of transmission of power. Though much had been written, there was no single work dealing
with the question in a sufficiently comprehensive and yet practical manner to be of real use to the mechanical
or mining engineer ; either the treatment was adapted for specialists, or it was fragmentary, and power work
was regarded as subservient to the question of lighting. The Author has felt the want of such a book in dealing
with his clients and others, and in "ELECTRIC MOTIVE POWER " has endeavoured to supply it.
In the introduction the limiting conditions and essentials of a power plant are analysed, and in the
subsequent chapters the power plant is treated* synthetically. The dynamo, motor, line, and details are
discussed both as to function and design. The various systems of transmitting and distributing power by con-
tinuous and alternate currents are fully enlarged upon, and much practical information, gathered from actual
experience is distributed under the various divisions. The last two chapters deal exhaustively with the
applications of electricity to mining work in Great Britain, the Continent, and America, particularly with
reference to collieries and coal-getting, and the results of the extensive experience gained in this field are
-embodied.
In general, the Author's aim has been to give a sound digest of the theory and practice of the electrical
transmission of power, which will be of real use to the practical engineer, and to avoid controversial points
which lie in the province of the specialist, and elementary proofs which properly belong to text-books on
electricity and magnetism.
A LARGE=SHEET TABLE, 1
-Giving full particulars of the Electricity Supply Stations throughout Great Britain up to January, 1895, can be
obtained mounted on stout board, with cord for hanging. Price : Varnished, 3s. 6d. ; Unvarnished, 3s.
each post free. A Map, showing positions of Supply Stations, is mounted on the back of the Table. A
Coloured Map, showing the Streets of London in which Mains for Private Lighting are laid up to January, 1895,
together with the areas allotted to the different Supply Companies, is also mounted on some copies of the
above Table ; and the price of these, complete, post free, is 5s.
NEW VOLUMES IN PREPARATION.
SUBMARINE CABLE-LAYING AND REPAIRING.
By H. D. WILKINSON, M.I.E.E., &c., &c.
This work will describe the procedure on board ship when removing a fault or break in a submerged cable
and the mechanical gear used in different vessels for this purpose ; and considers the best and most recent
practice as regards the electrical tests in use for the detection and localisation of faults, and the various
difficulties that occur to the beginner.
MOTIVE POWER AND GEARING
FOR EJL.ECTRICAT, IVI ACMHSTER Y.
BY E. TEEMLETT CARTER, C.K
{COPIOUSLY ILLUSTRATED WITH SCALE DRAWINGS & NUMEROUS PLATES.)
The purpose of this work is the explanation of the principles and practice of modern mechanical motive
power and gearing, especially in their application to electrical machinery. Electrical engineering is as much a
matter of engines and gearing as of dynamos and cables ; but the conditions of electric light and power distribu-
tion are such that a special study of the mechanical plant is necessary. Just as marine or locomotive steam
practice is treated in a special manner in works on the subject ; so the Author has endeavoured to hold in
view the special requirements of electrical practice, and to produce a work on steam and other motive power
which shall be solely devoted to these requirements.
"MOTIVE POWER AND GEARING" is adapted equally to the needs of the practical engineer and of the
student, and the treatment is such as may be easily understood without special mathematical training.
Besides steam plant, as used in electric power stations, the work treats of gas, oil, and water-power engines, and
the chapters on these, as well as the section on Gearing, are written on the lines of the latest practice in electric
power stations. The best points in the development of motive power for electrical engineering on the Continent
and in the United States have also been considered, and are fully treated, and compared with English practice.
This work constitutes the only existing treatise on the Economics of Motive Power and Gearing for Electrical
Jtachinery.
1, 2, and 3, Salisbury Court, Fleet Street, London, E.G.
"The Electrician" Printing and Publishing Co., Ltd., 15
"THE ELECTRICIAN" SERIES continued.
* *
NOW READY. Price 1. 5s., in Sepia or Black; in very Massive Frame, 2. 2s.
A Handsome Plate Reproduction of ROBERT DUDLEY'S famous Painting of
THE "GREAT EASTERN,"
(By permission of the Executors of the late Sir JAMES ANDERSON.)
The first of a series of Fine Art Plates which it is proposed to issue from time to time, and executed in the
lest style, and by the.latest and best process of faithful reproduction. The Plate has a high historic value ; it
ortrays the great ship at the critical moment when, in endeavouring to pick up the 1865 Atlantic Cable, " the
icking-up tackle having given out," her Captain gives orders for her return to England.
At the foot of the picture is a lithographed extract from the letter of Captain (afterwards Sir James)
inderson to the owners of the ship, and &fac simile signature.
The subject measures 24in. by!7in., and is India mounted on fine etching boards, the mount measuring
rin. by 21in. The entire plate measures 36in. by 27in.
Price 10s. 6d., in very Massive Frame, 1. Is.
A Handsome Reproduction of HERKOMER'S famous Painting of
SIR JOHN PENDER, G.C.M.G.,M.P.
Mounted India on fine etching boards. The subject measures 15in. by llin., the mount ISAin. by
nd the whole plate 28iin.
Price 10s. 6d., in very Massive Frame, 1. Is.
A Handsome Plate Reproduction of WILLIAM SYMONDS' fine Painting of
SIR JAMES ANDERSON, J.P.
Mounted India on fine etching boards. The subject measures 15in. by llin., the mount ISJin. by 14Jin
nd the whole plate 28in by 2lin.
OTHER REPRODUCTIONS WILL FOLLOW SHORTLY.
STEEL-PLiTE PORTRAITS
OP
7ILLOUGHBY SMITH (out of print),
OCHAEL FARADAY (Is. extra),
IR JOHN PENDER, G.C.M.G., M.P.,
1IR WILLIAM THOMSON, F.R.S.
(LORD KELVIN),
(Past-President of the Institution of Electrical
Engineers),
J. H. B. PATEY, C.B.
(Late Secretary of Telegraphs, G.P.O.),
)R. JOHN HOPKINSON, F.R.S.
(Past-President of the Institution of Electrical
Engineers),
)R. OLIVER J. LODGE, F.R.S.,
ROF. WILLIAM CROOKES, F.R.S.
(Past-President of the Institution of Electrical
Engineers)
HERMANN VON HELMHOLTZ,
PROF. W. E. AYRTON
(Past-President of the Institution of Electrical
Engineers),
LORD RAYLEIGH, F.R.S.,
CYRUS W. FIELD,
W. H. PREECE, C.B., F.R.S.
(Past-President of the Institution of Electrical
Engineers).
WERNER VON SIEMENS,
SIR JAMES ANDERSON, J.P.,
JOSEPH WILSON SWAN,
ALEXANDER SIEMENS
(President (1894) of the Institution of Electrica
Engineers),
HEINRICH HERTZ,
AND R. E. B. CROMPTON (President for 1895 of the Institution of Electrical Engineers),
HAVE BEEN ISSUED AS SUPPLEMENTS TO
Jjje
PEACTICAL TREATISE ON THE STEAM-ENGINE. By Arthur Rigg. 1. 5s,
THERMODYNAMICS OF THE STEAM ENGINE AND OTHER HEAT
ENGINES. By Prof. C. H. Peabody. 21s.
AN ELEMENTARY TREATISE ON STEAM. By Prof. John Perry. 4s. 6igh,
Prof. Rowland,
Prof. Hueker,
Air. Wairen de la Rue,
Sir J)avid Salomons
Dr. Paul Schoop, '
Mr. Louis Schwendler,
Mr. G. F. C. Searle,
Mr. J. . Sellon,
Mr. Alex. Siemens,
Dr. Werner Siemens,
Mr. M. Holroyd Smith.
Mr. Willoughby Smith,
Mr. Albion T. Snel?,
Mr. W. H. Snell,
Dr. W. Spottiswoode,
Mr. J. T. Sprague,
Prof. Balfour Stewart,
Dr. W. E. Sumpner,
Mr. James Swinburne,
Mr. Nikola Tesla,
Prof. Silvanus Thompson,
Mr. Elihu Thomson,
Prof. J. J. Thomson,
Sir Wm. Thomson (Lord
Kelvin),
Mr. H. Tomlinson,
Mr. A. P. Trotter,
Mr. G.W. de Tunzelmann,
Prof. John Tyndall,
Mr. F. C. Webb,
Mr. F. M. Weymouth,
Mr. H. D. Wilkinson,
Dr. Zetzsche,
&c., &c., &c.
TERMS OF SUBSCRIPTION:
YEAR. HALF-YEAR.
Great Britain 19 6 to IO O
Countries in the Postal Union .. 1 4 O O 12 6
Outside the Postal Union . ISO. O 14 6
QUARTER.
050
066
076
The large and influential circulation of " THE ELECTRICIAN," which far exceeds that of any
of its British contemporaries, together with its moderate tariff rates, combine to make the journal
THE YERY BEST MEDIUM FOR ADVERTISING.
"THE ELECTRICIAN" PRINTING A PUBLISHING COMPANY,! Ltd;,
SALISBURY COURT, FLEET STREET, LONDON, ENGLAND.
T "
YC
UNIVERSITY OF CALIFORNIA LIBRARY