key: cord-1055061-ljxmhd74 authors: Lee, Joon Kee; Jeong, Hye Won title: Rapid expansion of temporary, reliable airborne-infection isolation rooms with negative air machines for critical COVID-19 patients date: 2020-05-01 journal: Am J Infect Control DOI: 10.1016/j.ajic.2020.04.022 sha: 8bac4d00a658f0cac3bc4bfd9875b9deb311b4a4 doc_id: 1055061 cord_uid: ljxmhd74 Abstract More airborne-infection isolation rooms (AIIRs) are needed in centers that treat severely affected COVID-19 patients. Wards and rooms must be carefully checked to ensure an ample supply of medical air and oxygen. Anterooms adjacent to AIIRS are required to maintain pressure differentials and provide an area for donning/doffing or disinfecting medical equipment. More airborne-infection isolation rooms (AIIRs) are needed in centers that treat severely affected COVID-19 patients. Wards and rooms must be carefully checked to ensure an ample supply of medical air and oxygen. Anterooms adjacent to AIIRS are required to maintain pressure differentials and provide an area for donning/doffing or disinfecting medical equipment. A novel human coronavirus, severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2), which emerged in Wuhan, China, in late 2019 is causing a pandemic. As of March 27 th 2020, over 500,000 cases have been diagnosed and there have been 23,335 deaths (1) . The numbers of infected patients and related deaths are markedly increasing worldwide. Resources, including medical personnel, medicine and medical equipment, are in great shortage, as are airborne infection isolation rooms (AIIRs). Patients with severe coronavirus 2019 (COVID-19) disease need aerosol-generating procedures such as intubation with mechanical ventilation or tracheal suction. To prevent the spread of infection to medical personnel or other hospital patients, rapid expansion of AIIR capacity is critical in centers to which severely affected patients are referred (2, 3). We would like to share our experience and emphasize some essential points in building temporary AIIRs for COVID-19 patients with severe signs and symptoms. Chungbuk National University Hospital (CBNUH) is an 810-bed (including 47 beds for intensive care) referral hospital in Cheongju, South Korea with approximately 2,300 employees and 4,000 outpatient visits per day. CBNUH had an airborne infection unit 4 composed of five AIIRs, which were opened in 2015. It is one of the government-designated referral centers for severely affected COVID-19 patients and it needed to increase the number of AIIRs urgently. To achieve this, the first step was to select adequate ward and patient rooms in respect to the flow of medical personnel and equipment. For most critical patients who need extracorporeal membrane oxygenation (ECMO), mechanical ventilation, or continuous renal replacement therapy (CRRT), the room needs to be large enough to allow such procedures, equipped with a suctioning device, medical air, and oxygen. For rooms with ventilators, a medical air supply needs to be present. In rooms equipped with an oxygen supply, but not equipped with medical air, oxygen therapy is achieved with portable ventilators or high-flow oxygen therapy devices. Considering the size, function, and distribution of patient rooms in the hospital, we selected two wards in the same building as the pre-existing airborne-infection unit. Anterooms are necessary to maintain the pressure gradient of AIIRs and reduce the migration of infectious particles from the isolation room into the corridor. In addition, an anteroom provides space for healthcare workers to put on or take off personal protective equipment (PPE), and to disinfect medical devices, sample bottles, and specimen cups leaving the patient's room. Thus, the anteroom is considered to be a buffer zone between the patient's room and corridor, and has a crucial role for infection control in AIIRs. Expanding AIIRs with negative air machines needs the partitioning of rooms or corridors to be used to make anterooms. Staff preparing temporary AIIRs need to be extremely flexible when designing and building an anteroom. The location of the restroom and sink, the alignment of patient beds, and the location of windows where the flexible duct from the negative air machine is connected should be reviewed thoroughly when designing the partition. The partition should 5 include a transparent panel through which medical personnel can communicate with one another (Figure 1 ). Different types of anterooms have been applied in our newly expanded AIIRs (Figure 2 ). For rooms located at the end of the corridor (635, 636), a shared anteroom was made by partitioning the end of the hallway, since these rooms were for patients infected with the same pathogen. For rooms adjacent to the middle part of the corridor (632, 633, 634) , anterooms were prepared within each room after removing superfluous patient beds. We decided to make an oblique partition to avoid locating the restroom inside the anteroom (room 634, blue line) after some trial and error. With the oblique partition ( Figure 3A ), we could make anterooms large enough (compared with the green line partition, Figure 2 ) to maintain door interlock when moving the portable X-ray machine or isolation carts. Mirrors were placed in each anteroom to help medical personnel check their PPE status both before entering patient rooms and when removing PPE to avoid contamination. Negative air machines are shown in blue and red boxes according to type. Partitions for anterooms are colored in red. In room 634, partitions that were tested but found to be inadequate are shown by blue and green lines. Reliable and stable negative pressure is one of the basic elements of an AIIR (4). Negative air machines are capable of generating high air flow and have been traditionally used to facilitate air changes in industrial facilities. The machines we used had embedded High Efficiency Particulate Air (HEPA) filters to prevent spreading of pathogens or dust through the exhaust ducts ( Figure 3 ). Patient rooms and negative air machines differed with respect to size and efficiency, respectively. Therefore, 'trial and error' is inevitable to some extent. In order to generate maximum pressure differentials, the walls and ceilings of the rooms were sealed with vinyl and tape and the gaps between the window and the window frames were sealed with tape and silicone gel. We tried to ensure a constant high pressure differential by 7 placing dual portable devices in each room and maintain adequate negative pressure in case one of them broke down or was switched off inadvertently. Practices Advisory Committee recommend pressure differentials > -2.5 Pa between the AIIR 8 and the corridor, and ≥ 12 air changes per hour (5) . Korea Centers for Disease Control and Prevention (KCDC) recommends > -2.5 Pa pressure differentials for between both the patient room and anteroom, and the anteroom and corridor (6) . All our expanded AIIRs achieved a pressure differential of at least -8 Pa (up to -15 Pa in certain combinations when both pressure gradients were combined. The pressure differentials were continuously monitored by using differential pressure transmitters applied on the walls between the patient's room and anteroom, as well as between the anteroom and corridor (Figure 3 ) to allow for easy verification of the pressure differential. Once a negative air machine became available, it was possible to install it and complete partitioning, sealing, fixing of the pressure transmitter with a display to the walls, and equip the room with CCTV in one day. In general, access for medical personnel to patients in AIIRs is more difficult than for ordinary patient rooms. To negate this problem, KCDC suggested a patient monitoring system that included video surveillance, usually by closed-circuit television, as a requirement for nationally designated AIIRs in South Korea (6) . In addition, to provide critical care to severely affected COVID-19 patients, patient rooms that could contain equipment to monitor all the general vital signs, including an electrocardiograph, were selected for conversion to temporary AIIRs. For some patients referred from a psychiatric hospital that had a large nosocomial outbreak of COVID-19, we made a device that could be turned on and off to control the sliding doors between the patient's room and the anteroom to prevent the patient's egress. For the temporary AIIRs, we applied a similar manual system to the doors between anterooms and patient rooms to prevent unintended door opening, especially by patients with mental illness or delirium. Healthcare Personnel (HCP) are one of the most important parts of our facility. World Health Organization Implementing a negative-pressure isolation ward for a surge in airborne infectious patients Airborne Infection Isolation Rooms -A Review of Experimental Studies. Indoor and Built Environment Designing a biocontainment unit to care for patients with serious communicable diseases: a consensus statement Guideline for Isolation Precautions: Preventing Transmission of Infectious Agents in Health Care Settings Guideline for Managing and Operating National Airborne Infection Isolation Units Infection control for emerging infectious diseases in developing countries and resource-limited settings