key: cord-1030918-9qjz6u1x authors: Pekdogan, Tugce; Tokuç, Ayça; Ezan, Mehmet Akif; Başaran, Tahsin title: Experimental Investigation of a decentralized heat recovery ventilation system date: 2020-11-18 journal: nan DOI: 10.1016/j.jobe.2020.102009 sha: ba83f8927e1fa5eedd1ce8c79cc94167df8d10ef doc_id: 1030918 cord_uid: 9qjz6u1x Indoor air quality is an important issue for improving and maintaining the indoor environment because it is directly related to people's health and work performance. These days, in many settlements, the applicability of natural ventilation is limited in the face of the decreasing infiltration loads, increased atmospheric pollution, and the climatic conditions. Therefore, the use of mechanical systems that are designed to ensure proper ventilation is becoming widespread. This paper presents full-scale experimental research of a wall-integrated decentralized ventilation system with heat recovery in the laboratory conditions. The heat recovery unit includes a ceramic block for sensible thermal energy storage. Parametric experimental studies were carried out to obtain the temperature distributions and the thermal capacity of the ceramic block during the supply and exhaust modes of working. In order to simulate the winter and summer conditions, two large scale temperature-controlled rooms are built up. The duration of the ventilation period is varied to be 1, 2, 5, 7.5 and 10-minutes. Experimental measurements indicate that 2 minutes of operation time shows the best thermal performance in terms of maintaining a comfortable indoor temperature with the least energy consumption. And some shortcomings were observed about the fan and thermal storage limitations. The social and economic transformation of society brought a change in living spaces. Places of living affected the spread of the COVID-19 virus [1] despite the fact that many measures are described by scientists and paramedics for preventing the spread of the virus. Thus, it was seen that humanity is not technologically, economically, or scientifically ready for that kind of crisis [2] . The importance of indoor air quality was once again remembered during the 2020 crisis. Therefore, it is essential to carry out scientific and technological studies for the revision and development of both existing and new ventilation systems. During the COVID-19 pandemic period, the importance of choosing correct filters and HVAC systems operating with 100% fresh air became significantly evident [3] . The supply of fresh air is very important for human comfort to lead healthy and productive lives. The air leakages from building elements caused by pressure differences between inside and outside occur to some degree. But these leakages are mostly uncontrolled; therefore, they induce significant energy losses. Besides, they are a probable cause for polluted air to come indoors since they are unfiltered. As a commonly accepted principle, the infiltration loads are kept as low as possible in building codes to reduce energy consumption. All-air systems are used to supply the required fresh air to the indoors; however, they are not usually considered as a proper solution in all kinds of ventilation practices due to their high investment costs and large volume requirements. The utilization of heat recovery ventilation systems with installed all-water systems and/or direct expansion systems are becoming more widespread applications. These types of systems are either placed within the ventilated space or mounted on a suitable place outside the volume to meet the indoor fresh air requirements. Another mechanical ventilation system as a decentralized heat recovery unit integrated within room walls has the potential to become a notable alternative and is the topic of this study. It is necessary to provide sufficient air from outside to ensure indoor air quality. Supplying fresh air helps to (i) limit the concentration of pollutants such as CO 2 [4] . However, the relationship between the spread of serious acute respiratory diseases such as COVID-19 and the rate of transmission is shown [5] . Indoor air quality does not only depend on indoor sources, but it also depends on the air quality provided from the external environment through doors, windows, and building structural cracks [6] . Therefore, proper ventilation is necessary, and it is possible to improve indoor air quality with a decentralized ventilation system using an appropriate filter. Today, it is imperative to install mechanical ventilation systems in new buildings, especially in cold climates. According to Buildings Performance Institute Europe [7, 8] , mechanical ventilation is mandatory for high-rise residences and buildings in some cold climatic countries such as Denmark and Poland. Additionally, in some mild climate European countries, mechanical ventilation systems are increasingly used in parallel with the reduction of infiltration loads [8] . As a result of the necessity and requirement of mechanical ventilation, many studies were performed to assess the current and potential technologies according to ventilation system classifications [9, 10] . There are several studies in the literature on centralized and decentralized ventilation systems based on computational fluid dynamics (CFD) simulation, basic theoretical analysis (TA), or experimental measurements (EM) ( Table 1) . The recent review studies on centralized (CVS) or decentralized ventilation methods (DVS) are summarized, and an overview of their general inferences is also presented in Table 1 . J o u r n a l P r e -p r o o f 5 Table 1 . Overview of the past reviews. ---- [11] is a review of the recent development of air-to-air heat and mass recovery technologies. -Extensive research was conducted on passive systems, mechanical ventilation systems, defrosting methods, dehumidification systems, and heat and mass exchangers integrated into the energy-efficient systems of buildings. -The applications, advantages, disadvantages, and basic performance criteria of each system are detailed. -Radiant panel with a decentralized ventilation system was found to have the lowest energy consumption for heating, ventilation, and air conditioning. -- [13] details the description of heat recovery systems, their working principles, and system components as well as the typical heat recovery technologies, including building applications with theoretical, experimental, and simulation studies. -The environmental impacts of heat recovery systems are also evaluated. -- [14] examines heat exchangers in wastewater source heat pump applications, classifies wastewater heat exchangers in detail based on many features, including their utilization and construction methodology. -North America -- [15] explores existing and potential ventilation technologies following the ASHRAE 62.2 Standard for residential buildings in the North American climate. Various mechanical systems, natural ventilation, and passive ventilation systems are among the studied technologies. -The main parameters related to each system include operating costs, installation costs, ventilation rates, and heat recovery potential. : Information is available in the paper. -: Information is not available in the paper. J o u r n a l P r e -p r o o f 6 Table 1 depicts that a wide range of energy-efficient systems have been developed for the buildings, and studies on recovery of waste energy from buildings are evaluated within this scope [12, 16, 17] . Another important drawback in buildings is that in most of the ventilation solutions in the literature, the systems occupy a significant amount of place in the conditioned environment [10] . In many studies, decentralized ventilation systems have been compared with centralized systems under various climatic conditions. Their results show that decentralized ventilation systems cause lower pressure losses, and these systems save much more energy as they reduce energy losses due to heating and ventilation. Moreover, heat recovery units make it possible to regulate the thermal balance in rooms and provide thermal comfort enhancement [18] . Heat recovery ventilation systems ensure the efficient use of energy due to their working principle of transferring the heat from exhaust air to the fresh air supplied to indoors [13] . These systems typically recover approximately 60% to 95% of the energy in the exhaust air and significantly improve the energy performance of buildings [19] . There are various concepts for heat recovery from exhaust air for ventilation applications. Besides, there are many studies according to building typologies, and studies that examine the performance and potential of reducing the energy consumption of decentralized ventilation units integrated into the facade of offices [20, 21] . In some studies, wall-integrated heat recovery ventilation systems or single-room ventilation systems, especially for decentralized ventilation, were mentioned, and their potential applications for residential ventilation were evaluated [16, 22, 23] . Although there are several studies on the heat recovery systems, there are still shortcomings in the research and development of the use of decentralized ventilation systems in building applications [22, 24] . Storing thermal energy in the sensible form is one of the most widely used techniques that is preferred in the wall-integrated decentralized heat recovery ventilation systems [25] . These systems usually involve electronically driven two-way fans. The working principle of the ventilation unit with heat recovery is simple. The indoor air that is discharged to the outdoor flows through a ceramic material and transfers the useful energy to the ceramic block. The temperature variations within the ceramic block correspond to the sensible heat storage. After completing the discharging process, the fan works in the opposite direction, and it transfers the fresh outdoor air to the indoor. Energy stored inside the ceramic material is transferred to the air coming from the outside, thus delivering fresh pre-heated/cooled air into the indoor environment. Removable filters in the system prevent the entrance of outdoor contaminants. The number of units applied to a build environment is typically depending on J o u r n a l P r e -p r o o f 7 the volume to be ventilated since two units should also run asynchronously with each other to prevent pressure imbalance. The aforementioned decentralized heat recovery ventilation systems can be applied by using one of the many different wall-integrated products from the market. The structure of these products generally consists of an air supply grill, an air filter, an axial fan, and a ceramic heat exchanger. Depending on the size of the space to be ventilated and the desired air change rate, the number of systems is determined, and the homogeneous fresh air distribution in the space is taken into consideration for the placement of the systems. In small spaces, a single system divided into two can be also used with double axial fans. These decentralized systems offer advantages of integration with architectural design and adding aesthetic value, being less noisy and easier to control than centralized systems. However, the proper design, selection, and implementation of energy-efficient ventilation systems require a holistic approach to the buildings and the users in the applications. The performance of the wall-mounted single-room ventilation unit with ceramic heat exchanger was studied. Firstly, on-site measurements were performed in laboratory conditions. The next step was to calibrate the laboratory measurements according to measured indoor and outdoor temperature, air velocity data. In experimental studies, uncertainties affect the accuracy of the data. So, the uncertainties were calculated. Then the fan performance and the performance of the heat recovery unit are calculated according to calibrated and measured data. Lastly, the results of the single-room ventilation unit with ceramic heat exchanger were analyzed and the conclusions on the performance of this unit were given. Also, the heat exchanger efficiency was calculated. In Appendix, Figure A shows the flow chart of the main steps of the study. The experimental study was carried out in the Building Physics Laboratory of Izmir Institute of Technology, Faculty of Architecture. The setup previously used for the thermal performance of the double-skin facade [26, 27, 28] and was redesigned and prepared for this study. The experimental setup includes two temperature-controlled volumes, which correspond to indoor and outdoor environments, and an aerated concrete wall separates these two environments. Parametric experimental studies were carried out to determine the performance of two wall integrated heat recovery ventilation systems. The experimental setup shown in Figure 1 consists One of the key parameters to evaluate the functional capacity of an HVAC system is the volumetric flow rate of air. A parabolic velocity profile occurs inside the duct section due to the viscous fluid flow within the channels; therefore, measurement of air velocity at a single point is not sufficient to determine the mean velocity. Different standards can be used to accurately measure the airflow rate. EN 12599 [29] is used in Germany and most of Europe; in addition, EN 16211 [30] and ASHRAE 111 [31] can be used. The common point of all these standards is that measurement points must be distributed inside the cross-section of the duct. EN 12599 [29] recommends using the Trivial linear equation solution method while measuring the air velocity in these air ducts. According to this method, the first step is to divide the velocity field in the channel section into equal-sized measurement areas. Then, measurements are taken from the midpoint of each section, and finally, the resultant arithmetic mean value represents the result. Blitz Sens VS-C2-1-A air velocity transmitter is used to measure the air velocity inside the ducts at specified positions. The measurement range of this device is 0-1m/s. This thermal anemometer, also called velocity meter works on the principle of measuring the airspeed and volumetric flow via heating and cooling of the sensor by electricity [32] . Its highly precise thin-film sensor is 180mm long and is produced for use in narrow spaces. Table 2 represents the characterization test results for supply (out to in) and exhaust (in to out) values of Channel 1 by the Trivial method [29] . According to the measurement results, the points that gave the closest values to the average were determined, and the measurements were taken from those points at the cross-section of the duct (shown in Table 2 The positions of thermocouples inside the test rooms are shown in Figure 1 . The air velocity measurement probe was calibrated in a wind tunnel by comparison method in which the reference sensor and the test instrument were placed in the test section of the tunnel. The uncertainty of the measurement value of the test instrument was calculated by using 5 data in a series measured in 30 seconds. In experimental studies, some uncertainties affect the accuracy of the data. Uncertainty calculations were made within the scope of the method followed by Holman [33] and Tokuc et al. [34] , which is also provided in ISO "Guide to the Expression of Uncertainty in Measurement" as the uncertainty analysis method for errors caused by an experimental set and measurement tools [35] . For a measurement with n variables, the result R is a function of the independent variables x 1 , x 2 , x 3 …x n, whereas w 1 , w 2 , w 3 If W R is defined as the uncertainty value in the result, the uncertainty of all independent variables are given with the same odds, then Eq. (2) is used; For the experimental studies, the uncertainty analysis of the mass flow rate (Eq. (3)), and heat transfer rate (Eq. (4)) in the channel were calculated. Accordingly; The uncertainty in Eq. The uncertainty values of each independent variable are given in Table 3 . The uncertainty of the mass flow rate is calculated according to the parameters defined in Eq. (3). For the measured air velocity values obtained in the experiments, the uncertainty value was taken from the catalog value of the manufacturer. And later, it was determined to be approximately 5.94% by interpolation. The uncertainty of the mass flow rate of air calculated for each independent variable given in Table 3 The uncertainty of heat transfer rate during the experiments is calculated based on the parameters defined in Eq. (6). The total uncertainty value of thermocouples with data logger was evaluated in accordance with the uncertainty of the devices used during the calibration. And the uncertainty of heat transfer rate is calculated as 6.35% based on the mass flow rate, specific heat, and temperature uncertainty values. J o u r n a l P r e -p r o o f 16 The decentralized heat recovery ventilation systems, which store sensible energy into the ceramic material, exhaust air from the inside and supply fresh air from the outside during the working cycles in this experimental study. During the experiments, the fan performance of the exhaust and supply is observed to be different in the measurements. This is due to the design of the fan blades in the experimental system, therefore the suction fan worked with a lower flow rate than discharge. For this reason, in this study, a new fan characteristic was obtained by making measurements at manufacturing speed settings. The axial fan, which is installed inside the ventilation unit, can work in two flow directions. The fans of commercial products have limited speed, and their exhaust-supply times are also limited ( Figure 5 ). Therefore, a fan control system was developed in the current study. This interface was used to control the desired speed and working period of the fans on the heat recovery system. Before running the experiments, fan characteristic of the system was obtained, and the common points in the direction of supply and exhaust were determined according to the normalized air velocity and the pulse width modulation (PWM). Also, it is seen that from Figure 5 , the fan operates with 47% efficiency. J o u r n a l P r e -p r o o f In this study, seven experiments are detailed for two decentralized heat recovery units operating simultaneously, the channel and the simulation rooms were monitored until steadystate conditions were attained before recording measurements for each experiment. respectively. The average of the three thermocouples placed before the filter in the unit and the average of the three thermocouples placed after the ceramic heat exchanger are coded as C 1Tin and C 2Tin , C 1Tout, and C 2Tout , in C1 and C2, respectively. In Figures 11 and 12 , the units were operated for 10 minutes, in simulated winter and summer conditions, respectively. The indoor environment is generally stable at 20°C and the outdoor environment varies between 3°C to 5°C in Figure 11 . Considering temperature distribution inside the ceramic at the end of the cycle process, almost all the temperature values are equal to the outdoor temperature or the indoor temperature depending on the airflow direction. Figure 12 shows that the outdoor temperature fluctuates up to 2°C and the indoor temperature is generally stable at 21°C. There is a decrease or increase of The amount of heat stored in/released from the ceramics is calculated by using Eq. (7), where Q is the thermal energy (J), m is the mass of the ceramic (kg), c p is the specific heat capacity of the ceramic (J/kg℃) and ΔT is the change in temperature (℃) of the ceramic material. Specific heat is the amount of heat required to change the temperature of the unit mass of a substance and the differential scanning calorimeter method is used to measure specific heat. This method measures the amount of energy absorbed or released while the sample taken from the ceramic material is heated and cooled for a few cycles [36] between 5℃ and 35℃. The specific heat value of the ceramic material was measured to have an average value of 0.725kJ/kg℃. The results of the heat recovery ventilation system with a ceramic heat exchanger for C2 are tabulated in Table 4 . These results are for a working cycle when the system operated from the indoor to the outdoor environment and from the outdoor to the indoor environment. Table 4 indicates that the result of the air energy change obtained to the weighted averages of C2-T in and C2-T out data and air velocity data measure during different time steps. The maximum possible heat transfer capacity, Q max is defined in Table 5 for the given set of operating conditions and it is calculated by using Eq. (8) as; 24 where is the mass flow rate of air (kg/s), c p is the air specific heat capacity (J/kg℃), ΔT is the temperature change of air (℃) and the Δt is the cycle period in second. Table 5 gives the results for the thermal energy storage in the ceramic, as well as the energy from the fan and the maximum energy values that can be stored. According to the fan manufacturer's catalog data [37] , power consumption is 3.4Watt when the nominal voltage is 12.0Volts. Therefore, there is an energy gain/loss of approximately 0.2-2kJ from the fan during a cycle period. When the data from Channel 2 are calculated; while the system is operated in winter conditions for 1 minute from outdoor environment to indoor environment, 4.478kJ heat release occurs, when it is operated for 2 minutes, 10.762kJ energy is released. As seen in Table 5 , as the system's operating time increases, heat transfer also increases. However, when looking at the storage per unit time, the best performance can be seen by operating the system for 2 minutes. When the fan runs for a long time period, the cost of electrical energy increases. The fan is more advantageous when the system operates in a short period. The efficiency of the sensible heat recovery ventilation system with a ceramic heat exchanger is obtained by using the data in Tables 4 and 5 . The efficiency is calculated [25] as the ratio of stored/released energy from the ceramic unit (∑ 31) to the maximum amount of energy considering outdoor and indoor temperature (∑ 32): Ƞ = ∑ 31 ∑ 31 + ∑ 32 (9) According to calculations via Equation 9, the supply efficiency for 2 minutes operation time is 82%, the result for 5 minutes is 76%, for 7.5 minutes the result is 73% and the winter condition average result is 77% and the exhaust efficiency is 65%. For summer conditions, when the unit is operated for 7.5 minutes, the supply efficiency is 89% and for 10 minutes, the J o u r n a l P r e -p r o o f 25 exhaust efficiency is 45%. Table 6 shows the energy efficiency results according to different working times. Fan energy consumption is not considered for the efficiency calculations. According to the average heat transfer rates in Figure 13 , the best result was observed This study critically reviewed the current work in the public domain and carried out laboratory measurements with changing indoor-outdoor temperatures and operation times during winter and summer conditions. The performance of the ceramic heat recovery ventilation unit with sensible energy storage and its axial fan were experimentally investigated under different working conditions. Ventilation performances for supply and exhaust were also analyzed to provide new experimental data under controlled environment conditions. For this case of the studied heat recovery ventilation unit, the airflow caused large differences in the supply and exhaust efficiencies. Also, the pressure differences were affected by the airflow rates in this ventilation system. And, the pressure was affected by the airflow balance of the unit. Thus, the stack effect pressure this resulted in a change in heat recovery system efficiency. The simulation results showed that the best heat transfer result was observed when the system operated for the 2-minute cycle in winter conditions. In addition, the best performance according to efficiency results was also the 2 minutes of operation time. This experiment allowed for the calculation of the actual efficiency of the ceramic unit and -The fan operates in the supply direction with a lower flow rate than the exhaust direction. Due to the relatively higher flow rate, during the fresh air flow from the outdoor to the indoor environment, a more homogeneous distribution occurs in the heat exchanger, rather than during the air transfer from the indoor to the outdoor environment. Thus, the supply efficiency for 2 minutes operation time is 82%, while the efficiency of this unit for exhaust efficiency is 67% for the simulated winter condition. For this reason, the axial fan direction of airflow, and the direction of airflow should be controllable. A pitch control fan or two separate fans can generate better ventilation performance by ensuring these two operations. An Invited Commentary on "World Health Organization declares global emergency: A review of the 2019 novel Coronavirus (COVID-19)": Emergency or new reality? Hygiene and future in air conditioning systems in COVID-19 perspective Indoor Air Quality and Severity of COVID-19: Where Communicable and Noncommunicable Preventive Measures Meet Indoor air quality and its effects on humans-A review of challenges and developments in the last 30 years Epidemiology and transmission of COVID-19 in 391 cases and 1286 of their close contacts in Shenzhen, China: a retrospective cohort study Indoor Air Quality and Coronavirus Disease (COVID-19), Public Health Analysis of residential building regulations Indoor air quality: a guide for facility managers Annual Total Heating and Cooling Gains of Heat Recovery Devices in Some Cities Ventilation Rate Measurements A review on the air-to-air heat and mass exchanger technologies for building applications Energy analysis of a decentralized ventilation system compared with centralized ventilation systems in European climates: Based on a review of analyses A comprehensive review of heat recovery systems for building applications Heat exchanger applications in wastewater source heat pumps for buildings: A key review Review of residential ventilation technologies Field tests of centralized and decentralized ventilation units in residential buildings -Specific fan power, heat recovery efficiency, shortcuts, and volume flow unbalances Energy and exergy analyses of advanced decentralized ventilation system compared with centralized cooling and air ventilation systems in the hot and humid climate Decentralized ventilation systems with exhaust air heat recovery in the case of residential buildings An experimental study on the performance of the enthalpy recovery system for building applications Residential ventilation: a review of established systems and a preliminary laboratory investigation of an innovative fine wire heat recovery ventilator, in 14th Can Modelling and simulation-based analysis of a façadeintegrated decentralized ventilation unit A review on the air-to-air heat and mass exchanger technologies for building applications Results of the evaluation study DeAL decentralized facade integrated ventilation systems The impact of air pressure conditions on the performance of single-room ventilation units in multi-story buildings Research of single room decentralized heat recovery unit Experimental and numerical investigation of natural convection in a double-skin facade Experimental investigation of the pressure loss through a double skin facade by using perforated plates Experimental and numerical investigation of forced convection in a double skin façade, Energies DIN EN 12599-Ventilation for buildings-Test procedures and measurement methods to hand over air conditioning and ventilation systems DIN EN 16211-Ventilation for buildings. Measurement of air flows on site ASHRAE 111-1988, Practices for Measurement, Testing, Adjusting and Balancing of Building Heating, Ventilation, Air-Conditioning, and Refrigeration System Industrial ventilation design guidebook Experimental methods for engineers An experimental and numerical investigation on the use of phase change materials in building elements: The case of a flat roof in Istanbul The Guide to the Expression of Uncertainty in Measurement (GUM) Analytical Chemistry Product Data Sheet 4412 FGMPR