key: cord-1028373-gxuvswnd authors: Gormley, M.; Aspray, T. J.; Kelly, D. A. title: Aerosol and bioaerosol particle size and dynamics from defective sanitary plumbing systems date: 2020-11-04 journal: nan DOI: 10.1101/2020.11.01.20223974 sha: 14bfbbc39c407c7752c2bd9a7d39be877bf6b71f doc_id: 1028373 cord_uid: gxuvswnd Aerosols are readily transported on airstreams through building sanitary plumbing and sewer systems and those containing microbial pathogens (known as bioaerosols) are recognised as contributors to infection spread within buildings. When a defect occurs in the sanitary plumbing system that affects the system integrity, a cross transmission route is created that can enable the emission of bioaerosols from the system into the building. These emission occurrences are characterised as short burst events (typically < 1 minute in duration) which makes them difficult to detect and predict. The characterisation of these emission events is the focus of this research. Two methods were used to characterise bioaerosol emission events in a full scale test rig : (i) an Aerodynamic Particle Sizer (APS) for particle size distribution and concentrations; and (ii) a slit to agar sampler to enumerate the ingress of a viable tracer microorganism (Pseudomonas putida). The APS data confirmed that most particles (> 99.5%) were <5 m and were therefore considered aerosols. Particles generated within the sanitary plumbing system as a result of a toilet flush leads to emissions into the building during system defect conditions with an equivalence of someone talking loudly for over 6 and a half minutes. There were no particles detected of a size > 11 m anywhere in the system. Particle count was influenced by flush volume, but it was not possible to determine if there was any direct influence from airflow rate. Typical emissions resulting from a 6 litre flush were in the range of 200 to 400 particles per second at a concentration of typically 9 to 12 number per cm 3 and a total particle count in the region of 3,000 to 4,000 particles, whereas the peak emissions from a 1.2 litre flush was 60 to 80 particles per second at a concentration of 2.4 to 3 number per cm3 and a total particle count in the region of 886 to 1045 particles. The reduction in particles is in direct proportion to the reduction in flush volume. The slit to agar sampler was able to provide viable time course CFU data and confirmed the origin of the particles to be the tracer microorganism flushed into the system. The time course data also has characteristics consistent with the unsteady nature of a toilet flush. The mechanism of airborne transmission of the SARS-CoV-2 virus, specifically the transport 47 in the air for significant periods of time, allowing them to be transmitted over longer distances 66 >1 m 5-7 Bioaerosols is the term used to define aerosols that contain viruses, bacteria , fungi, 67 or bacteria and fungi cell components 8 . They can also contain pollen grains or other biological 68 material. 69 70 perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint and wastewater is needed, the evidence is building and some studies have suggested that faeces 103 can contain viable virions 18, 19 . 104 shown to be both a reservoir for pathogens 21 perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint aimed to quantify and characterise the aerosol particle release from people when breathing, 127 talking, singing, coughing, etc., this research aims to quantify and characterise the aerosol 128 particle emissions from within a sanitary plumbing system following a toilet flush event. 129 130 131 The test rig shown in Figure 3 was constructed in the Water Laboratory at Heriot-Watt 149 University. The test rig is designed to European standards using EN12056:2000-2 27 and 150 represents a two storey building sanitary plumbing system. The system simulates a toilet flush 151 on Floor 1 and has a sealed test chamber on Floor 2 (to represent a bathroom). The test chamber 152 has an extract fan with a length of flexible ducting attached. Instruments for analysis of aerosols 153 and bioaerosols (see below) through the system were positioned at the end of the ducting. 154 The induced airflow in the system was set by a variable fan speed controller and the air velocity 156 was measured by the anemometer in the pipework. To simulate a toilet flush, a pipe with a 157 capacity to hold 6 litres of water (the maximum flush volume of a new toilet) was connected 158 above a manual discharge valve. A 6 litre culture of P. putida, was inoculated into the drainage 159 system via toilet flush and tracked at the outlet duct using the slit-to-agar sampler. The simulated 160 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint can be seen to last no more than 10 seconds. The fluid from the flush enters the vertical stack 168 of the sanitary plumbing system and falls creating an annular flow. The shear between the water 169 and the air causes an airflow to be entrained, thus causing air pressure fluctuations as the system 170 preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint attempts to balance airflow and pressure. The dynamics of this air intake follow the same pattern 171 as the toilet discharge flow profile. The turbulence caused by the air/water mixture as they 172 interact is sufficient to produce aerosols within the sanitary plumbing system. If the discharging 173 wastewater contains pathogenic micro-organisms, then bioaerosols can be generated that can 174 be transported on internal airflows. Since the test rig was in a laboratory (and not connected to a complete sanitary plumbing system 181 or main sewer network) it was necessary to induce an updraught airflow using an extractor fan 182 in the test chamber. The airflow rates used were defined previously 22 and were set to three 183 broad ranges: 184 • Low flow rate (~3 l/s ) 185 • Medium flow rate (~5 l/s ) 186 • High flow rate (>6 l/s ) 187 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. This ensured that results could be compared if they fell within the same range and ensured that 189 flow rates were representative of those found in real systems. An APS device (model 3321, TSI Inc., Shoreview, MN) was used to enumerate the particle 206 sizes of the air emitted from the test rig. The APS device was set to sample for 60 seconds 207 before the airflow was initiated and the toilet flush was discharged. Samples were taken from 208 the main vertical stack (APS sampler locations 1, 2, and 3 in Figure 3 ) and at the ductwork exit 209 (APS sampler location 4 in Figure 3 ). Each test was set to record data for approximated 500 210 seconds. The data was recorded and processed to give time stamped recordings of specific 211 particle sizes and the results graphed for inspection and analysis. 212 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint Slit-to-agar sampler 214 Before each experiment, the sampler plate housing and slit inlet were sterilised with 95% 219 ethanol. A single 150 mm diameter Pseudomonas Isolation Agar (PIA) plate was placed on the 220 rotor platform and secured with adhesive tape to prevent slippage. The height from plate to the 221 slit was adjusted as required to allow for differences in agar thickness. 222 The sampler was set to run for 60 seconds before the toilet flush was discharged. The sampler 224 was then allowed to run for a total of 300 secs per experiment. After the experiments, the PIA 225 plates were incubated for 24 h at 30 °C before imaging and image analysis. The experimental procedure for both of these methods can be summarised as follows: 234 1. The system was washed down with biochlor ® solution and rinsed with tap water 235 2. The 'inoculum' was loaded into the valve controlled discharge pipe 236 3. The induced airflow was initiated and allowed to stabilise 237 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint up and taken for incubation 241 A range of 'inocula' were used to establish the importance of different factors. Table 2 shows 242 the range of tests carried out. 243 244 preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint flush liquid used was de-ionised water, NaCl, and P. putida bacterium (as detailed on Table 2 259 above), measured at APS sampler location 4 (see Figure 3 ). The background level is stable at 260 just under 4 particles per cm 3 , which is expected in this type of test environmenta large water 261 engineering laboratory. The peak particle counts resulting from the aerosolization from the flush 262 can clearly be seen. The peak of the induced spike was 245 particles/second at a concentration of 9 particles/cm 3 277 (normalised without background). An average background particle level of 87 particles/second 278 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint was also observed. Analysis of particle sizes show that 99.5% of all particles have an 279 aerodynamic diameter ≤5 μm. with an aerodynamic diameter greater than 9 μm detected in the system following the toilet 336 flush and none greater than 11 μm in the background data. (the particle size limit of the system 337 being 20 μm) 338 339 Most of the tests were carried out using a simulated toilet flush volume of 6 litres. An additional 341 set of experiments were carried out using a reduced volume to see the impact on aerosol 342 generation, Figure 8 below shows the results. 343 344 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint (A) (B) 346 An example slit-to-agar PIA plate after incubation is shown in Figure 9 . The colonies start 353 appearing a short time after the flush is initiated. This time is determined by the delay between 354 turning on the slit-to-agar sampler and the initiation of the toilet flush and the time taken for the 355 tracer organism to travel from the discharge point to the slit-to-agar sampler, approximately 10 356 metres. The pattern of colonies shows clustering at the beginning, shortly after the flush is 357 initiated with a tailing off until the event ceases to contribute further tracer organism. An 358 analysis of the kinetics of viable quantities of the tracer organism is given below. 359 360 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint Table 3 . In addition to the CFU 369 data, an estimate of the velocity of the tracer organism in the system is given. This is based on 370 the time from the flush peak to the time the peak CFUs occurred. It can be seen that the tracer 371 organism velocity is much lower than the air velocity. 372 373 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint the sanitary plumbing system can be detected in the extract duct of a room on the level above 383 that of the contaminant input level within a building. The APS data shows a profile consistent second toilet flush event was found to result in aerosols being emitted into the building over 60 386 seconds, however, this was found to range from 30-110 seconds in duration. This profile is 387 repeated in the slit-to-agar results for the tracer organism, with a characteristic sharp rise in 388 numbers followed by a longer tail off. 389 Although slit-to-agar samplers are typically used to quantify viable microorganisms within a 391 given volume of air and are generally used for clean room and production area contamination 392 monitoring 29,30 , more recently they have found application for more general indoor air and 393 environmental monitoring 31,32 . Here, we show the novel application of a slit-to-agar sampler to 394 determine the kinetics of viable cells transported in the airstream through a building's sanitary 395 plumbing system. The sampler effectively determined a ~15 second time window when the 396 highest number of cells went through the system, followed by a tail of decreasing cell numbers 397 with time. This pattern in terms of peak and tails time was consistent across replicate 398 experiments and with different air flow rates. The CFUs measured at the system exit ranged in 399 duration between 48 seconds and 155 seconds. 400 401 When higher flow rates were used we found the same peak and tail patterns, however, isolated 402 colonies also appeared 140 seconds after the toilet flush on more than one occasion. We believe 403 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint this was the result of cells detaching from within the sanitary plumbing system due to shear 404 stress under this higher air flow rate. 405 In our experiments, the slit-to-agar sampler was used as a semi-quantitative manner. The reason 407 for this was that the air flow rates within the sanitary plumbing system were in excess of the 408 sampling rate of the sampler. In addition, the duct outlet was larger than the inlet of the sampler 409 and designed as such so as not to restrict airflow within the sanitary plumbing system. The 410 results obtained from the slit-to-agar sampling are indicative of the spatial and temporal 411 distribution of viable bacteria into the building from the sanitary plumbing system. While this 412 serves as semi-quantitative data, there is evidence that slit-to-agar sampling underestimates the 413 number of bacteria against other methods 33 414 415 In order to establish an equivalence with a known source of bioaerosol infection emission, we 417 adapted data from Asadi et al., 34 who investigated particle emissions from people talking 418 loudly. Asadi's team asked subjects to talk loudly into a particle sampler to capture the 419 magnitude, concentration and particle size distribution from a test speech involving talking 420 loudly followed by periods of breathing only. We adapted this data to show the cumulative 421 emissions from talking loudly for 120 seconds. This is shown in Figure 10 . We also plotted the 422 cumulative emissions from our Experiment D which used 6 litres as the toilet flush volume, and 423 measured at APS sampler location 4. By extending the trendline on the Asadi data we can see 424 that the number of particles emitted from the sanitary plumbing system as a result of a toilet 425 flush is equivalent to a person talking loudly for 404 seconds (or just over 6 and a half minutes). 426 427 428 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. were only a small number of particles between 10 and 11 μm when measured nearer the source. 452 Over 99.5% of all particles were <5 μm in diameter. These characteristics mean that aerosols 453 and bioaerosols from a sanitary plumbing system are amenable to be carried long distances on 454 airflows inside buildings. We assume that larger droplets were generated but were not carried 455 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint on the airflow and were deposited on pipe walls and in the chamber. The total number of 456 particles emitted by the system into the room has been shown to be the equivalent of a person 457 taking loudly for approximately 6 and a half minutes. 458 459 Particle count was influenced by flush volume, but it was not possible to determine if there was 460 any direct influence from airflow rate, although it may have had some effect on the duration of 461 the emission. A wider range of airflow rate would be required to verify this. Typical emissions 462 resulting from a 6 litre flush was in the range 280 -400 particles per second at a concentration 463 of typically 9 to 12 number per cm 3 and a total particle count in the region of 3,000 to 4,000 464 particles, whereas the peak emissions from a 1.2 litre flush was 60 -80 particles per second at 465 a concentration of 2.4 to 3 number per cm 3 and a total particle count in the region of 886 to 466 1045 particles. The reduction in particles is in direct proportion to the reduction in flush volume. 467 The event-causing bioaerosols in these experiments was a simulated toilet flush containing the 469 P. putida KT2440 tracer organism at a dose rate of ~10 6 cfu ml -1 . This event lasted no more 470 than 10 seconds. The discharge of the toilet flush into the sanitary plumbing system instigated 471 an aerosolisation process due to the turbulent flow conditions. The resulting CFUs measured at 472 the system exit ranged in duration between 48 seconds and 155 seconds. The pattern of CFU 473 on the slit-to-agar sampler PIA plates confirms that the tracer organism concentration followed 474 the flush characteristic (in litres/sec), the elongation of the surge wave being attributable to the 475 difference in velocity between the bioaerosols and the air. 476 477 This work highlights the complexity of tracking and quantifying aerosols and bioaerosol 478 transmission due to short-burst events such as those found in sanitary plumbing systems. The 479 current COVID-19 pandemic has emphasised the challenges for all building systems in 480 All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint potential cross-contamination routes due to defective appliance water trap seals in 566 perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted November 4, 2020. ; https://doi.org/10.1101/2020.11.01.20223974 doi: medRxiv preprint A novel coronavirus from patients with pneumonia in 498 It is Time to Address Airborne Transmission of COVID-19 Droplet fate in indoor environments, or can we prevent the spread of 502 infection? Indoor Air Detection and enumeration of airborne 507 biocontaminants Can numerical computer modelling aid innovation, efficiency and cost 539 reduction in sanitation provision? Desalination Transient Airflow in Building Drainage Systems. London: Spon Persistence and clearance of viral RNA in 2019 novel 543 coronavirus disease rehabilitation patients Enteric Involvement of Severe Acute Respiratory Syndrome 547 Probable Evidence of Fecal-Respitory Transmission of SARS-CoV-2 549 in a high-rise building Environmental conditions and the 551 prevalence of norovirus in hospital building drainage system wastewater and airflows Pathogen cross-transmission via 554 building sanitary plumbing systems in a full scale pilot test-rig Consensus document on the epidemiology of severe acute respiratory syndrome 557 (SARS) Fungal biodiversity in indoor environments in Aerosol 591 emission and superemission during human speech increase with voice loudness