key: cord-1003856-ach2lhhe authors: Mousavi, Ehsan S.; Kananizadeh, Negin; Martinello, Richard A.; Sherman, Jodi D. title: COVID-19 Outbreak and Hospital Air Quality: A Systematic Review of Evidence on Air Filtration and Recirculation date: 2020-08-26 journal: Environ Sci Technol DOI: 10.1021/acs.est.0c03247 sha: cd2b9a77cf7e4eaea7816e859459f11d33291056 doc_id: 1003856 cord_uid: ach2lhhe [Image: see text] The outbreak of SARS-CoV-2 has made us all think critically about hospital indoor air quality and the approaches to remove, dilute, and disinfect pathogenic organisms from the hospital environment. While specific aspects of the coronavirus infectivity, spread, and routes of transmission are still under rigorous investigation, it seems that a recollection of knowledge from the literature can provide useful lessons to cope with this new situation. As a result, a systematic literature review was conducted on the safety of air filtration and air recirculation in healthcare premises. This review targeted a wide range of evidence from codes and regulations, to peer-reviewed publications, and best practice standards. The literature search resulted in 394 publications, of which 109 documents were included in the final review. Overall, even though solid evidence to support current practice is very scarce, proper filtration remains one important approach to maintain the cleanliness of indoor air in hospitals. Given the rather large physical footprint of the filtration system, a range of short-term and long-term solutions from the literature are collected. Nonetheless, there is a need for a rigorous and feasible line of research in the area of air filtration and recirculation in healthcare facilities. Such efforts can enhance the performance of healthcare facilities under normal conditions or during a pandemic. Past innovations can be adopted for the new outbreak at low-to-minimal cost. The prevention of healthcare associated infections (HAIs) has long been a top strategic priority for the Center for Disease Control and Prevention (CDC). 1 Still, an estimated 90,000 deaths occur per year in the United States. 2 The recent pandemic manifested an urgent need to better understand and implement design, maintenance, and operations that ensure indoor air quality in healthcare facilities. Specifically for the SARS-CoV-2 virus, the CDC recognizes three main routes of transmission: (1) direct large droplet transmission between people within close proximity; (2) indirect respiratory droplet deposition on surfaces and objects and subsequent transmission via the contaminated fomite; and (3) the airborne transmission via small particle aerosols containing viable virus. Although the portion each route contributes to disease transmission is under close investigation, one can reasonably assume that lowering the number of virus particles in the indoor space would result in lower rates of transmission. Engineering tools can be instrumental to remove, contain, and dilute virus concentrations in the spaces where the COVID-19 patients are evaluated and treated, and air filtration− recirculation is a long-lasting method used to remove and dilute contaminants. 3−5 1.1. What Do Past Outbreaks Reveal? Infection may transfer via air from one person to another and become epidemic. 6 Although it is accepted that the airborne route exists, its attributed contribution to the spread of infectious diseases is less certain. 7 For example, tuberculosis (TB) is transmitted person-to-person by the airborne route via small particle aerosols measuring 1 to 5 μm, sufficiently small that they remain aloft in the air. 8 In 1966, aboard the Navy ship U.S.S. Richard E. Byrd, 45.5% of the at-risk crew members (140 out of 308) unfortunately became infected with TB. In this episode, air recirculation on the ship was implicated as the primary amplification pathway of infection. 9 In 1972, Ehrenkranz reported 21 healthcare staff who developed latent TB infections out of 60 formerly tuberculin-negative personnel. Ten of these 21 staff had little or no direct contact with the patient with TB, and the authors concluded that they likely had been infected by the spread of Mycobacterium tuberculosis through an unbalanced air conditioning system which was found by smoke stick to allow air from patients' room to enter the hallway, and this system lacked a "high-efficiency filter" (80% or greater). 7, 10 During 1983−1984, 6 employees of the emergency department of Parkland Memorial Hospital (Dallas, TX) developed active TB. One of the reasons that led to the outbreak of TB was the lack of adequate f iltration of the 60% recirculated air which could not remove tubercle bacilli in the emergency department. 11 Prior to 1994, it was recommended that isolation rooms for patients known or suspected of active TB disease should have had a minimum total of 6 air changes per hour (ACH), at least 2 of which with outdoor air. 12−14 In the updated 1994 guidelines, the CDC recommended that, wherever feasible, air flow rates be increased to 12 air changes per hour with recirculating air in the room through fixed, monitored high efficiency particulate air (HEPA) filtration or portable air cleaners. 15 Reviews of other environmental parameters in healthcare facilities exist, such as Memarzadeh (2012) on the effect of temperature and relative humidity on pathogen viability. 16 Another review specifically targeted thermal comfort in hospitals, concluding that while it is almost impossible to satisfy every occupant, there are certain engineering tools and numerical techniques that can be utilized to improve the design and operation of the hospital. 17 Most recently, a review of scientific evidence on hospital buildings studied the temperature, relative humidity, and ventilation system. It briefly mentioned the filtration systems; however, recirculation was not considered. 18 1.2. Focus of the Current Paper. The current state of healthcare ventilation management stems from two complementary schools of thought around minimizing both recirculation of indoor air and energy demands. Various studies demonstrate the importance of the airborne route of infection transmission in the hospital setting. 19 On one hand, it seems unreasonable to allow recirculation of return air into patient care environments. On the other hand, it seems reasonable to take advantage of the energy in the return air to dilute contamination through air recirculation, while ensuring that the return air is clean and comfortable. With recent advancements in technology, the latter can also be achieved via energy recovery techniques, and recirculation is no longer the sole option. However, these techniques are not always a feasible and affordable retrofit response to the emergence of COVID-19, especially in existing facilities while replacing the filtration system, and altering the air distribution system could be more convenient. Perhaps, a natural question is, to what extent can new approaches in air filtration/recirculation improve the health and safety of patients and the front-line medical personnel? These approaches bring about this literature review on the issue of air filtration and recirculation in healthcare facilities. In the present work, we will first briefly discuss the theoretical background of interconnections between air filtration and recirculation. Next, the process of identifying relevant publications, followed by assessing their methodology, will be explained, and evidence for air filtration and air recirculation and potential interconnections will be reviewed. The true effect of air filtration and air recirculation on the temporal and spatial distributions of contaminants indoors is a very difficult problemone that does not have an analytical solution and is computationally very expensive. However, one could set aside the spatial term by assuming that contam-ination is uniformly distributed throughout the space. This socalled well-mixed assumption is a useful simplification that is often used in the field. 20, 21 Taking the room as a large control volume, one could derive the differential equation where V is the volume of the room, C is contaminant concentration as a function of time, C s is contaminant concentration at the supply air inlet, Q s and Q r are supply and return flow rates, and S is a source of contamination in the room (Figure 1 ). Without a loss of generality, let us assume that the supply and return flow rates are identical, Q s = Q r = Q. It is noteworthy that for pressurized spaces (i.e., operating rooms (OR), AIIRs) this assumption is not valid. In general, eq 1 is a linear differential equation with an exponential solution. For example, eq 1 shows an exponential decay for a single release of contaminant. One can argue that the efficiency of the filter changes with time, which will turn eq 1 into a nonlinear problem that must be solved numerically. 22 Moreover, the concentration at the supply air inlet can be written as where α is the percentage of outside air mixed with return air, C out is contaminant concentration in the outside environment, and η is filter efficiency. For the scope of this work, C out can be assumed as zero, as one does not expect to have COVID concentrations at the outside air intake location. In essence, α represents the recirculation in the system where α = 100% shows a full recirculation system and α = 0% shows a one-pass (i.e., no recirculation) system. Combining eq 1 and eq 2, and moving V to the right-hand side of the equation, we will have where the Q V term is the space ventilation rate that is often referred to as air changes per hour (ACH). To show the effect of filtration against increasing the ratio of outside air, eq 3 was solved for different values of α (10% to 100%) and η ranging from MERV 12 (70% efficiency for 0.3 μm) to HEPA (99.97% efficiency for 0.3 μm). To compare different cases, a time index (T) was defined as the amount of time it takes for the concentration of the contaminant to decay to 0.001 initial release value. The shorter the time index, the more efficient the ventilation system is in removing contamination from the space. Results showed that for low filter efficiencies T reduced significantly by introducing more outside air (α on the x-axis), but HEPA filters can clean the space such that T became insensitive to the portion of outside air ( Figure 2 ). Another interesting interaction between the filtration and recirculation systems is that filters with higher efficiencies create a pressure drop across the filter, leading to lower supply airflow rates. 23, 24 This process is more profound for fibrous media that are frequently used for HVAC air filtration. 25, 26 The literature suggests that the pressure drop across the air filter is linearly related to filter efficiency. 27, 28 Further, for a constant fan power, pressure drop is inversely related to flow rate squared. 29 Therefore, for a room with a fixed volume and fan power: The combination of eq 3 and eq 4 was solved to obtain the coupled effect of air filtration and recirculation. As shown in Figure 3 , considering the impact of higher filter efficiency on the recirculation flow rate can result in significant increase in the cleaning time index (T). It must be noted that there are several other filtration mechanisms that produce less significant pressure drops compared to fibrous filter media, 30 yet the coupled effect seems to deserve great consideration when increasing filter efficiency without changing fan power. In Phase I of this systematic literature review, related academic databases, and codes and guidelines by relevant organizations have been identified. The databases include PubMed, Web of Science, Engineering Village, and Compendex. Key terms such as "filtration", "recirculation", "ventilation", "HVAC", "mechanical system" in combination with terms such as "hospital", "healthcare facilities", "outbreak", "epidemic", and "pandemic" were used to identify relevant articles from the above databases. Table 1 shows the results of the initial search of the key terms with a separate focus on air filtration and air recirculation in healthcare facilities. Next, the research team looked for duplicated outcomes from these databases. The reference list of these articles were also searched to include relevant articles that otherwise may not have been included. The first round of source selection resulted in 394 publications. Only peer-reviewed documents, available in English, were selected for further review. Next, these publications were independently reviewed by two experts for relevance to the topic of this literature review, that is, the effect of air filtration and air recirculation on the spread of pathogenic agents in the hospital. The inclusion criteria were as follows: availability in English (390 documents), peer reviewed conference or journal articles (307 documents), a focus on the building mechanical ventilation (178 documents). Finally, only those publications with either original results or rigorous review papers were included for the final review (91 documents). Figure 4 illustrates the systematic review method. In Phase II of document identification, guidelines from relevant organizations such as the Facility Guide Institute (FGI), The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), The American Hospital Association (AHA), the American Society of Healthcare Engineers (ASHE), and the Center for Disease Control (CDC) were included. Guidelines from regulatory bodies from across the globe were also included, contingent upon the availability of the documents in English. This study reviews 20 codes, guideline, standards, and handbooks pertaining to ventilation in healthcare facilities. Further, the level of evidence was evaluated based on the methodology in the articles ( Table 2 ). To that end, the publications were categorized in five levels based on the methodology rigor based on Preferred Reporting Items for Systematic Reviews and Meta-Analyses (PRISMA) recommendations. Of note, none of the studies retrieved were randomized trials with direct evidence. Also, Figure 5 shows the distribution of publications with original data based on the methodology employed. 4.1. Air Filtration. As it relates to air filtration, ASHRAE recognizes five different spaces in a typical in-patient hospital facility: (1) surgery and critical care spaces including operating rooms (ORs), inpatient and ambulatory diagnostic and therapeutic radiology, and inpatient delivery rooms; (2) protective environment rooms, or rooms that are intended to protect a high-risk immunocompromised patient from human and environmental airborne pathogens; (4) laboratories and procedure rooms and associated semirestricted spaces; and (5) all other service, administrative, food preparation, and laundry, and storage spaces. 32 It must be noted that in the most recent version (2017), ASHRAE Standard 170 offers design parameters for in-patient facilities, out-patient facilities, and nursing homes. However, the above categories and the associated requirements are still very similar for these three facility types. Specifically, filtration and air recirculation requirements for inpatient facilities, where a COVID patient is likely hospitalized, have not changed compared to the previous version. Moreover, in the older versions of Standard 170, ORs are classified based on the type of surgery in Group A (minor surgery), Group B (procedures that require intravenous sedation), and Group C (procedures that require general/regional block anesthesia). This classification has been removed from the 2017 revision, and the definition by the Facilities Guideline Institute (FGI) has been adopted. 33 In this paper, however, we still note the old classification just for referencing purposes. Table 3 shows the minimum filtration and air recirculation requirements for these spaces based on the various standards reviewed in this work. The filtration rating is reported in the minimum efficiency reporting value (MERV) rating, that is, the lowest point of filter efficiency in removing three different size ranges of 0. 35 These guidelines required the protective environment rooms (i.e., dedicated to immunocompromised patients) to be equipped with HEPA filters with a 99.97% efficiency for particles larger than 0.3 μm. 35 For product protection in pharmacies, laminar flow with a nonhydroscopic filter at 99.97% removal efficiency should be designed. The committee on operating room environment of the American College of Surgeons advised the use of HEPA filters as standards for all operating rooms, to help prevent surgical site infections. 36 When two banks of filters are necessary as with areas for inpatient care, and protective environment rooms, the first filter should be on the upstream of air conditioning equipment and the second filter should be downstream of fans or blowers. Hoods that are used to process radioactive or infectious materials should be equipped with HEPA filters. When designing a filtration system, it is important to make sure that no stagnation or short-circuiting of air flow happens. 35 Patients on airborne precautions for possible aerosolizing infections shall be placed in hospital rooms with HEPA filters to reduce their risk of cross-contamination. 37, 38 The American Institute of Architects (AIA) and the CDC recommend that for Airborne Infection Isolation Rooms (AIIRs), the exhaust air should be directly discharged to the outside or filtered prior to recirculation using in-duct HEPA filters. 39, 40 The exhaust should be at least 25 feet away from public areas. In case a good location for exhaust cannot be met, HEPA filters can be installed in the discharge duct upstream of the exhaust fan to clean the air. 41 It must be noted that adding a HEPA filter to an existing system is not recommended as it can cause friction in the airstream that leads to delivering less-than-designed amounts of air to the room (i.e., pressure drops). 41 Therefore, if the installation of in-duct HEPA filters is not feasible, a recirculating HEPA filter unit should be added. They are available as wall, floor, and ceiling mounted types. The wall and ceiling units are less obstructive to the airflow, while the floor units are easier to service. 40 The Australian guideline for design of isolation room by the Victorian Advisory Committee on Infection Control requires the supply or exhaust air to be filtered at their maximum pressure drop. 42 For class P or positive pressure room, the air change rate should be kept at 12 ACH with supply air HEPA filtration. 43 The state of California requires that manufacturers specify filter efficiency and that specified rooms have filters with specific filtration efficiency based on ASHRAE Standards. 44 Table 3 shows filtration and air recirculation requirements for several key spaces in the hospital informed by English et al. 45 and Betz et al. 46 Filter efficiencies for other countries are converted into the MERV rating system. 45 35 No recirculation of air is allowed in operating rooms, delivery rooms, recovery rooms, or rooms with odor problems. 48 CDC recommends placing patients who have infections which may be transmitted by small particle aerosols in rooms without air recirculation. 49 The state of Texas recommends not allowing recirculation in operating rooms and delivery rooms. If recirculation is necessary to increase the air changes per hour, filters of MERV 17 or higher (HEPA filters) shall be used. 50 These recommendations result in ethical challenges to performing prospective controlled trials. Hence, there is a dearth of high quality studies that prospectively examine the effect of recirculation on disease spread in the hospital setting. 37, 51 Before recent pharmacological advancements, anesthetic gases were at risk of combustion, and recirculation of air was prohibited by both federal and state regulations. 45 A very important note pertaining to the COVID-19 outbreak is that many healthcare facilities, especially those in more populated states (e.g., New York, California), have rapidly surpassed their capacity for isolation rooms. This means that new admissions must be placed in intensive care units (ICUs) or general patient rooms where far less stringent air filtration schemes are required by codes. Awareness must be raised that such practices may exacerbate the spread of virus in the room and other adjoining spaces (i.e., hallways), and the potential to reconfigure air and pressure flows to increase safety capacity should be evaluated. 52 4.3. Epidemic Task Force Guidance. Since the beginning of the COVID-19 pandemic, several organizations such as the World Health Organization, U.S. Federal Government, and State Jurisdictions have established taskforces to assess various aspect of the pandemic such as emergency medical services, health inequalities, and healthcare preparedness. The one taskforce related to hospital ventilation design has been established by ASHRAE. Among other considerations, ASHRAE recommends increasing filtration level (if possible), minimizing air recirculation, maintaining 40−60% relative humidity, and utilizing portable HEPA filtration and anteroom units. Further, ASHRAE proposes five options of airflow alteration to the patient room before hosting a COVID case ( Figure 6 ). It must be noted that filtration and recirculation are central to these air distribution schemes. In the case of no filtration (i.e., option 2), air must be discharged at least 25 feet away from any building opening and entrance. Several research groups examining vulnerable patient populations showed that private rooms with air filtration significantly reduced the risk of infection and mortality. 53−55 For instance, Oren and colleagues (2001) reported that leukemia patients had an infection rate of 50% to invasive pulmonary Aspergillosis in rooms with natural ventilation during hospital renovation. Some patients were then moved to rooms with HEPA filtration and showed no sign of infection even after 3 years. 56 Annual tests performed on all the HEPA filters in a biological laboratory for 13 years showed that they were very reliable. Little failure (∼10%) was observed through the filter medium, provided filter clogging did not occur. Clogging was associated with 75% of failure cases. 57 HEPA filters have a 99.97% or larger removing efficiency of particulate matters of 0.3 μm or larger and are typically protected with less expensive filters on the outside air intake and air return. 58 They were first developed for war time, for their capability to reduce air contamination, along with recirculation of air and laminar flow. 59 It is worth mentioning that not every study supports the use of HEPA filters. Kowalski et al. (1998) suggested that in some cases HEPA filters are unnecessary and it was better to have a high-efficiency filter with outside air to lower the pressure drop and increase system efficiency. 60 Another study by the same research group indicated that for removing 1 μm and larger common spores, 90% efficient filters were as effective as HEPA filters. 61 Miller-Leiden et al. (1996) showed that for removing aerosol with 0.7 and 1.3 μm non-HEPA units was as effective as HEPA units. 62 Stephens and colleagues (2013) offered a method by modifying the Wells−Riley approach to calculate the risk related to airborne infectious diseases in a hypothetical hospital waiting room. The analysis showed that having HVAC filtration greatly reduced the risk of HAIs, with the lowest cost of operation depending on climate and building. MERV13−16 were more effective in reducing HAIs compared to MERV 11. 63 Another simulation of airflow and contaminant transport was used to analyze the decay of TB concentration over time. Between various filtration setups, no significant difference was found between removal rates of MERV 15 and HEPA filters. 20 The main disadvantages of HEPA filters are that they are costly in terms of maintenance, and also in terms of electricity requirements, as they have high pressure drop which increases the fan energy consumption. 60 5.1. Filtration in Operating Room (OR). High efficiency filters have been widely used in operating rooms to reduce the risk of surgical site infection. 64, 65 The SARS-CoV-2 pandemic has brought to light an abundance of relevant publications pertaining to filtration in the OR. For example, during an 53 2 Burn units Observational study of 2519 patients over ten years Isolation of burn patients in separate rooms equipped with new filters reduced mortality ratio to one-third of predicted ratio. Authors attributed the improvements to the use of single-bed rooms, rather than the filtration system. However, these two effects were not decoupled. HVAC system operations audit of 20 operating rooms in 10 different hospitals in the Hellenic Republic, the most common problems were poor maintenance of filters and nonexistent of air exhaust filters. 66 Another study compared freestanding HEPA filter units placed inside the OR to a novel portable anteroom system with HEPA unit (PAS-HEPA) that is placed outside the OR, near the main entrance. 67 It was found that with the PAS-HEPA system, experimental smoke plumes were observed moving downward and toward the main entry door. However, when freestanding HEPA units were placed on the patient bed inside the OR, smoke plumes were moving vertically upward toward the breathing zone of the OR personnel. These findings suggest that PAS-HEPA systems can be adopted when coping with surgical patients during an airborne pandemic. Al-waked (2010) investigated the steady state operation of a laminar flow system (LAF) using HEPA filters that was centrally located in the OR ceiling, using computational fluid dynamics (CFD), and results indicated their effectiveness in minimizing the spread of contaminants and providing thermal comfort. 68 One major difference between the OR design and that for the AIIR is the use of laminar airflow systems. The laminar flow system provides a unidirectional flow, 36 and it must not be confused with cleaned air. 69 The HEPA filtration plays an outstanding role in the efficiency of laminar flow systems, as it assures the cleanliness of the supply air prior to pouring it on the OR bed. 70−72 The laminar air flow combined with HEPA filters can bring the contamination level down and is recommended for ORs and immunocompromised patient rooms. 37,73−78 It must be noted that a true laminar flow system is not achievable, as hospital personnel and equipment movements often disturb airflow patterns. 7 In a study by Sheretz et al. (1987) , the use of whole-wall HEPA filtration units with horizontal laminar flow (LAF) in patient rooms reduced the number of Aspergillus organisms in the air to 0.009 colony-forming units/m 3 , which was significantly lower than in all other areas of the hospital. 78 However, Sadrizadeh et al. (2016) showed that horizontal laminar flow systems, even when equipped with HEPA filters, lose efficiency due to the movement of medical staff and equipment. 79 The Surgical Infection Society recently published guidance on delivering surgical care to SARS-CoV-2 patients. They recommended the use of a negatively pressurized OR, should one be available. Facilities that lack negative pressure ORs shall equip a room with a HEPA filter for surgical purposes. Also, the guidance requires a geographical separation (including the supply room) between the OR dedicated to COVID-19 patients and the rest of the surgical suite. No particular mention of air recirculation was found in the guidance. 80 5.2. Filtration in AIIRs. Research on 2519 burn patients provided strong evidence that single-bed isolation rooms in combination with air filtration substantially reduced the incidence of infection with Gram-negative bacteria. 53 Another study measured the efficiency of isolation rooms with and without anteroom and with and without care provider traffic. Two micrometer aerosol particles that were dyed with fluorescent dye were released inside three isolation rooms that were equipped with HEPA filters. The negative pressure and HEPA filtration was effective in containing more than 99% of the aerosols. 81 The experiments were repeated for different provider traffic levels (i.e., no pass, one pass, and three pass) and results revealed over 99.7% containment of aerosols under all three conditions, providing a 5 min stay inside the AII unit. This is particularly important as it relates to providing care to the COVID-19 patients in AIIRs. Marier and colleagues (1993) investigated a novel filtration−ventilation system to recirculate AIIR air through an Ultra-Low Penetration Air (99.9995% efficiency for 0.12 μm particles) filter and return the clean air into the adjacent anteroom. This system partially contributed to establishing the negative pressurization in the AIIR. The concentration of particles reduced to 30% of the baseline (fan off) when the system worked on the low mode, and up to 2% of the baseline for the high mode. 82 5.3. Filtration in Protective Environment (PE). Bone marrow transplant (BMT) units in the University of Minnesota hospital, built in 1986, had three different filters: 1, rough filter 40% (ASHRAE 52−76); 2, 95% bag filter (ASHRAE 52−76); and 3, HEPA final filters. 83 Other rooms in the hospital had the same filters, with the exception of HEPA filtration. By mapping particle concentrations to the level of filtration and occupancy level in the room, it was found that the number of small particles (0.3−0.5 μm) was a function of the filtration, and that the number of large particles (>5 μm) was a function of the occupancy level. Compared to the rooms without HEPA filters, the count of small particles (0.3−0.5 μm) was substantially lower for BMT units equipped with HEPA filter. Hahn et al. (2002) also showed that HEPA filters made a significant reduction in the number of HAIs in highly immunocompromised patients. 77 The incident of nosocomial Aspergillus infection was 10 times lower when the BMT patient was placed in a room with HEPA filtration and laminar airflow. 78 Passweg et al. (1998) also found that HEPA filters reduced contamination and increased the survival of BMT and leukemia patients. 54 During a four-year period, in two hematology wards and a BMT unit, there were 64 cases of invasive nosocomial Aspergillus. The rooms were equipped with HEPA filters and/or laminar air flow (LAF) systems. Air and surface samples were collected to measure the level of fungal contamination bimonthly during this period. Results showed no fungi in air or surface in the rooms equipped with HEPA-LAF, 73 consistent with the findings of other investigators. 78, 84, 85 Table 4 presents a summary of publications on air filtration with a brief discussion of the employed method. 5.4. Portable HEPA Filters. HEPA filters can reduce the fungal spore and pathogen counts. 73, 86, 87 HEPA filters are usually placed in the HVAC system. 88 It is better to locate the HEPA filter at the point of air discharge to the room rather than at the discharge of the fan. 89−91 This is because the ductwork system from the fan discharge to the room outlet could be contaminated due to maintenance or construction. 92 Portable HEPA units can be used if this practice is not feasible. Portable HEPA filters are capable of increasing the effective ACH, removing particles, and reducing the risk of transmission in general wards when there are not enough isolation wards as is the case with the COVID-19 pandemic 8,39,89,93−95 (Table 5) . Miller et al. (1996) investigated the effectiveness of portable air filters (PAFs) and ceiling mounted air filters (CMAFs) for controlling TB exposure. CMAFs were shown to be more advantageous over PAFs due to their elevated inlet and the buoyant nature of the droplet nuclei. 62 Qian and colleagues tested the performance of portable HEPA filters, such as their effect on the airflow pattern, using both smoke visualization and computer simulation. They found that having portable HEPA filters with strong air supply could bring a global airflow mixing by interacting with the airflow pattern. 93 One study found, on average, a 75% reduction in MRSA surface contamination when portable HEPA filter was placed inside three different patient rooms. 96 While the portable unit did make a significant change in overall airflow patterns, the final outcome (i.e., surface decontamination) did not change by changing the location of the HEPA unit. Casagrande and Piller (2020) demonstrated that the change in the global patterns of air movement due to a portable HEPA unit can be positively harnessed. By placing the portable HEPA unit next to the instrumentation table in the OR, an invisible air curtain was created around the instrument table that reduced the risk of instrument contamination up to 75%. 97 Another investigation assessed the impact of 48 portable HEPA filter units on the invasive Aspergillosis (IA) incidence. Portable HEPA filters nearly halved the IA incidence ratio. The costs of HEPA filtration were negligible compared to the significant decrease in the rates of IA infection. 88 Nevertheless, portable HEPA filters can be noisy, and bring physical obstruction for airflow in the room. 39 A more recent study assessed the performance of a portable air purifier (filter efficiency not specified) in a pediatric hospital setting. A total of 562 patients diagnosed with infectious or noninfectious respiratory distress were included in this study in pre-and post-cohorts. Results showed that the rate of using invasive patient ventilation (i.e., intubation) was reduced 30%, and the average hospitalization time declined from 0.7 days to 0.4 days upon placing the portable air purifier in the rooms, 98 though these differences did not achieve statistical significance. Further, clinical details were not provided to allow a better understanding of potential differences in specific clinical outcomes such as healthcare associated pneumonias, so it is difficult to understand these changes. 5.5. Other Air Treatment Methods. While filtration is critical in maintaining the quality of hospital air, filters themselves can shelter viable organisms and hence sometimes support their growth. 99−101 Therefore, the device itself can become the source of contamination. 102−107 In an investigation of three sealants with different active antimicrobial compounds, only two of them reduced the fungal regrowth. 108 Some of the air microorganisms are compatible with the antimicrobial agents applied on them. 109 On the other hand, found that filters did not become the source of microbial growth as long as polyacrylate copolymer antimicrobial agents containing zinc oxide and borates were used under normal conditions. 110 It was also reported that antimicrobial agents were not effective in curbing fungal reproduction on dust-loaded filters, while chemically coated filters had slightly higher than 60% efficiency. 111 This area of research has remained fairly controversial where there are not enough studies to support (or impugn) the use of antimicrobial agents on air filters. 20, 112 Specific to the coronavirus outbreak, rigorous research must be conducted to characterize the viability and reproduction of the virus on the filters. These data are particularly critical when deciding on protocols for replacing, storing, and disposing of used filters. Bergeron and colleagues (2007) designed a novel mobile air treatment unit to both remove airborne particles and destruct microorganism by use of electrostatic capture and nonthermal plasma reactors. 107 Nonthermal plasma reactors ensure that no microorganisms were stored in the system and eventually released into the air. Their efficiency for removing biological 113 The combination of filtration and disinfection has been recommended by CDC, NIOSH, and ASHRAE as a complementary air cleaning approach to the room air conditioning system. 12, 15, 114 For example, the combination of ultraviolet germicidal irradiation (UVGI) lamps and filtration was most effective in removing and killing pathogens like Aspergillus spp. and Staphylococci. 91, 115 Ryan et al. found that installation of UVGI in the HVAC systems equipped with 95% filter efficiency helped reduce ventilator-associated pneumonia and tracheal colonization. 116 Another more recent work studied the effectiveness of UVGI when used in ventilation ducts. Results showed the UVGI inactivated nearly all the microorganisms in the ductwork when the air velocity was 3.0 m/s. However, an increase in air velocity (6.0 m/s) led to insufficient exposure of bacteria to irradiation, and thus only 80% inactivation was found for S. enterica and S. epidermidis. 117 Interested readers may find further useful discussions in a review article published by Memarzadeh and colleagues on the application of the UVGI technology in healthcare settings. 118 Waiting for a contaminant to decay naturally in the building is a slow process. Hence, engineering alternatives like mixing indoor air with the outside air and recirculating it back to the room and pressurization control are utilized. There are two types of general air systems: (1) single pass and (2) recirculating. 119 The single pass air system supplies air from the outdoors, and after passing through the room air it is then exhausted 100% back to the outdoor environment. This system does not, however, take advantage of the embodied energy required for heating/cooling of discharged air. In the recirculating system, however, a limited portion of the air is exhausted to the outdoors and replaced by fresh air. 120 Recirculating systems are typically designed for significantly larger flow rates compared to single pass systems as they utilize the power of contaminant dilution. Recirculation could be used as long as air is filtered through high efficiency filters or is cleaned by disinfection techniques. 121 Recirculation of air can be problematic under two conditions: (1) when it leads to the delivery of insufficient fresh air, and consequently excessive CO 2 exposure, or (2) when the return air is not properly filtered. 122 For most patient-care areas, there are two filters in central HVAC systems. The outside air is filtered through the first bank filter to remove larger particles (1−5 μm). The incoming air then mixes with the recirculated air and is reconditioned for temperature and humidity and eventually passes through the second filter in the air handling unit. 35, 123 Ulrich (1974) studied two neurosurgical operating rooms at St. Mary's Hospital in Rochester, Minnesota, during surgical procedures. Air and surface samples were taken to determine bacterial counts. Results for both rooms demonstrated that recirculation of air along with filtration reduced the number of bacteria inside the OR when compared to 100% fresh air. 124 Woods et al. (1986) studied two operating rooms in Mary Medical Center in Ames, Iowa, and data were recorded from two existing HVAC settings. In the first OR, the system performed 12 air changes per hour with 100% outdoor air and only one filter. In the second operating room, the system performed 17 air changes per hour with 20% from the outdoor (i.e., 3.5 ACH) and two filters. Although the percentage of outdoor air in the second operating room was lower than the first room, computer simulations and field measurements showed a reduction in particulate matter concentrations, indicating the usefulness of air recirculation and filtration. 125 Research has shown that air recirculation should only be used in the hospital setting in conjunction with adequate air filtration. The distribution of particles were studied in a patient room of a Brazilian hospital that was ventilated with a split system that recirculated air inside the room with outdoor air, but without filtration. Results showed that small particles followed the path of the air and remained suspended in the room due to air recirculation inside the room. Hence, pure recirculation can increase the risk of contamination due to random particle movements, and it may also result in significant particle deposition onto surfaces. 126 The placement of inlet and outlet filters is also important, as the HVAC system can cause different recirculation patterns in the room. 127, 128 7. PRACTICAL IMPLICATIONS There is substantial evidence (Level 2 publications) that contaminated air can result in disease spread, and that the combination of air filtration and recirculation can reduce this risk. Observational and animal studies suggest that air recirculation alone may result in the airborne transmission of pathogens. 129−131 The experimental setup is mostly designed for extreme cases to prove the airborne route, which is far from realistic in the healthcare setting. There are a few outstanding findings from the literature that can be used to minimize the adverse impact of the SARS-CoV-2 virus on medical personnel who spend many hours of their time inside the hospital as well as reduce risk of nosocomial infections. 1. The combination of HEPA filtration and air recirculation has been shown to be extremely effective in many space functions such as ORs, AIIRs, and PEs. These systems clean air by simultaneously removing (i.e., filtering) and diluting (through recirculation) contaminants from the space. They have shown significant reduction in the number of bacterial colonies, and surrogate particulate matters previous studies, and they are expected to show a similar efficiency for the COVID-19 pandemic. The role of air distribution systems in buildings during an outbreak has been the subject of previous research. 132, 133 A finding that is worthy of reiteration is from Streifel and colleagues (1995) that showed HEPA filters are remarkably efficient in capturing submicron particles. 83 The SARS-CoV-2 virus is shown to have a diameter less than 1 μm. This further suggests that HEPA filters will be effective tools to mitigate hospital spread, as noted in a recent review on the potential airborne route of the SARS-CoV-2 transmission in hospitals. 134 2. The coronavirus outbreak has severely hit the healthcare settings. Notably, in hospitals in the epicenter of the pandemic during the spring of 2020 (New York, Connecticut, and Boston), the surge capacity exceeded standard room configurations and SARS-CoV-2 positive patients were placed in general patient wards and converted ICUs without negative pressure capacity. These spaces likely frequently lack sufficient filtration requirements, ventilation rates, and negative pressurization capacity. Therefore, one short-term solution seems to be substituting the existing filter in those rooms with higher efficiency filters (i.e., HEPA filters). Though this seems like a logical decision at the first glance, it may result in unfavorable outcomes such as increasing the pressure drop when replacing a lower rate filter with HEPA filters. 29, 135 When the pressure drop increases and the fan speed remains constant, the amount of air supplied to the space will decrease. This can result in an imbalanced system that can increase the distribution to spread disease. 3. Portable HEPA filter systems have been shown to be another effective tool in reducing viral load. Another innovative design is to place a portable HEPA filter that discharges air into a portable plastic anteroom right at the entrance. 82 Such a system, also recommended by the ASHRAE epidemic task force, can clean the air inside the patient room, while creating negative pressure with respect to the plastic anteroom. Therefore, both virus removal and containment may be achieved. The Centers for Disease Control and Prevention Strive Initiative: Construction of a National Program to Reduce Health Care-Associated Infections at the Local Level The Direct Medical Costs of Healthcare-Associated Infections in U.S. Hospitals and the Benefits of Prevention On Airborne Infection. Study III. Viability of Droplet Nuclei Infection Airborne Infection: Transmission and Control Aerosol Technology: Properties, Behavior and Measurement of Airborne Particles Some Aspects of the Airborne Transmission of Infection Hospital Ventilation Standards and Energy Conservation APIC and CDC Survey of Mycobacterium Tuberculosis Isolation and Control Practices in Hospitals Caring for Children. Part II: Patient and Family Isolation Policies and Procedures Spread of Tuberculosis Via Recirculated Air in a Naval Vessel: The Byrd Study Tuberculosis Outbreak in a General Hospital: Evidence for Airborne Spread of Infection 204−210. (12) ASHRAE. ASHRAE Handbook of Fundamentals (14) US Department of Health and Human Services. Minimum Requirements of Construction & Equipment for Hospital and Medical Facilities; He Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care Settings. Centers Dis Literature Review of the Effect of Temperature and Humidity on Viruses Effects of Indoor Environmental Parameters Related to Building Heating, Ventilation, and Air Conditioning Systems on Patients Molecular Epidemiology of Microbial Contamination in the Operating Room Environment: Is There a Risk for Infection? Surgery Multizone Modeling of Strategies to Reduce the Spread of Airborne Infectious Agents in Healthcare Facilities Preventing Airborne Disease Transmission: Review of Methods for Ventilation Design in Health Care Facilities An Air Filter Pressure Loss Model for Fan Energy Calculation in Air Handling Units Studies in Filtration: III. Derivation of General Filtration Equations Evaluation of a High Efficiency Cabin Air (HECA) Filtration System for Reducing Particulate Pollutants inside School Buses Influence of Different Mesh Filter Module Configurations on Effluent Quality and Long-Term Filtration Performance Fibrous Filter Efficiency and Pressure Drop in the Viscous-Inertial Transition Flow Regime Evolution of the Efficiency and Pressure Drop of a Filter Media with Loading Modeling Indoor Air Concentrations Near Emission Sources in Imperfectly Mixed Rooms The Effects of Filtration on Pressure Drop and Energy Consumption in Residential HVAC Systems (RP-1299) Electrospun Polyacrylonitrile/β-Cyclodextrin Composite Membranes for Simultaneous Air Filtration and Adsorption of Volatile Organic Compounds The PRISMA Statement ASHRAE Standard 170. Ventilation of Health Care Facilities 34) ASHRAE Standard 52.2−2017-Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size Guidelines for Design and Construction of Hospital and Health Care Facilities Current Status of Special Air-Handling Systems in Operating Rooms A Review of the Research Literature on Evidence-Based Healthcare Design (Part I). HERD Heal The Ventilation of Multiple-Bed Hospital Wards in the Management of Patients Infected with Airborne-Spread Diseases: An Algorithm for Infection Control Professionals Tuberculosis Infection Control A Practical Manual for Preventing TB Isolation Rooms: Design, Assessment and Upgrade Victorian Advisory Committee on Infection Control. Guidelines for the Classification and Design of Isolation Rooms in Health Care Facilities Health Care Ventilation Standard: Air Changes per Hour or CFM/ Patient Minimum Ventilation Requirements in Operating and Procedure Rooms: A Comparison of International Standards Benchmarking the US Healthcare Ventilation Standard with the German Healthcare Ventilation Standard A History of the Changing Concepts on Health-Care Ventilation ACIP: Use of BCG Vaccines in the Control of Tuberculosis: A Joint Statement Byt He ACIP and the Advisory Committee for the Elimination of Tuberculosis APIC State-of-the-Art Report: The Role of Infection Control during Construction in Health Care Facilities Association for Professionals in Infection Control and Epidemiology Novel Coronavirus (COVID-19) Pandemic: Built Environment Considerations To Reduce Transmission A Decade of Reduced Gram-Negative Infections and Mortality Associated with Improved Isolation of Burned Patients Influence of Protective Isolation on Outcome of Allogeneic Bone Marrow Transplantation for Leukemia Effects of Environment on Infection in Burn Patients Invasive Pulmonary Aspergillosis in Neutropenic Patients during Hospital Construction: Before and after Chemoprophylaxis and Institution of HEPA Filters Hepa Filter Replacement Experience in a Biological Laboratory Clean Room and Work Station Requirements, Controlled Environment Providing the Best Environment For the Hospital Surgical Suite. HPAC Eng Airborne Respiratory Diseases and Mechanical Systems for Control of Microbes. HPAC Eng Filtration of Airborne Microorganisms: Modeling and Prediction. ASHRAE Trans Effectiveness of In-Room Air Filtration and Dilution Ventilation for Tuberculosis Infection Control HVAC Filtration and the Wells-Riley Approach to Assessing Risks of Infectious Airborne Diseases Operating Theatre Quality and Prevention of Surgical Site Infections Statement of the Committee on Operating Room Environement of the American College of Surgeons on Special Air Systems for Operating Rooms HVAC and Indoor Thermal Conditions in Hospital Operating Rooms. Energy Build Pilot Study of Directional Airflow and Containment of Airborne Particles in the Size of Mycobacterium Tuberculosis in an Operating Room Effect of Ventilation Strategies on An Observational Study of Door Motion in Operating Rooms The Relationship of Genitourinary Tract Procedures to Deep Sepsis in Total Hip Replacements. Surgery, Gynecology Obstet Laminar Airflow and the Prevention of Surgical Site Infection. More Harm than Good? Surg Maintenance of Aseptic Barriers in the Conventional Operating Room: General Principles Relationship between Environmental Fungal Contamination and the Incidence of Invasive Aspergillosis in Hematology Patients Measurement of Bacterial and Fungal Air Counts in Two Bone-Marrow Transplant Units Environmental Controls in Operating Theatres The Addition of a Mobile Ultra-Clean Exponential Laminar Airflow Screen to Conventional Operating Room Ventilation Reduces Bacterial Contamination to Operating Box Levels Efficacy of High-Efficiency Particulate Air Filtration in Preventing Aspergillosis in Immunocompromised Patients With Hematologic Malignancies • Impact of Air Filtration on Nosocomial Aspergillus Infections A Numerical Investigation of Vertical and Horizontal Laminar Air Flow Ventilation in an Operating Room Surgical Infection Society Guidance for Operative and Peri-Operative Care of Adult Patients Infected by the Severe Acute Respiratory Syndrome Coronavirus-2 (SARS-CoV-2) Containment Effectiveness of Expedient Patient Isolation Units A Ventilation-Filtration Unit for Respiratory Isolation Hospital Building Design for Particle Management Control of an Outbreak of Nosocomial Aspergillosis by Laminar Air-Flow Isolation Efficacy of Prevention by High Efficiency Particulate Air Filtration of Laminar Airflow against Aspergillus Airborne Contamination during Hospital Renovation Fungal Survelliance of an Open Haematology Ward Fungal Infections after Haematology Unit Renovation: Evidence of Clinical, Environmental and Economical Impact The Impact of Portable High-Efficiency Particulate Air Filters on the Incidence of Invasive Aspergillosis in a Large Acute Tertiary-Care Hospital Efficacy of Portable Filtration Units in Reducing Aerosolized Particles in the Size Range of Mycobacterium Tuberculosis Further Evaluation of Alternative Air-Filtration Systems for Reducing the Transmission of Porcine Reproductive and Respiratory Syndrome Virus by Aerosol Guidelines for Environmental Infection Control in Health-Care Facilities Use of HEPA Filters to Reduce Airborne Concentrations of Pseudomonas Aeruginosa Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-Care Facilities Reduction in MRSA Environmental Contamination with a Portable HEPA-Filtration Unit Conflicting Effects of a Portable Ultra-Clean Airflow Unit on the Sterility of Operating Rooms: A Numerical Investigation Impact of a New Portable Air Purification Technology Device in the Pediatric Hospital Setting -A Pre-Post Assessment Study Survival of Bacterial and Mold Spores in Air Filter Media Mold Colonization during Use of Preservative-Treated and Untreated Air Filters, Including HEPA Filters from Hospitals and Commercial Locations over an 8-Year Period Nosocomial Invasive Aspergillosis in a Heart Transplant Patient Acquired during a Break in the HEPA Air Filtration System Outbreak of Invasive Aspergillus Infection in Surgical Patients, Associated with a Contaminated Air-Handling System Ventilation Grilles as a Potential Source of Methicillin-Resistant Staphylococcus Aureus Causing an Outbreak in an Orthopaedic Ward at a District General Hospital Outbreak of Bloodstream Infections in a Nursery Associated with Contaminated Aerosols and Air Conditioners An Outbreak of Serratia Marcescens Infection in a Special-Care Baby Unit of a Community Hospital in United Arab Emirates: The Importance of the Air Conditioner Duct as a Nosocomial Reservoir Decreasing Airborne Contamination Levels in High-Risk Hospital Areas Using a Novel Mobile Air-Treatment Unit Investigation of the Potential Antimicrobial Efficacy of Sealants Used in HVAC Systems Effects of Antimicrobial Treatment on Fiberglass-acrylic Filters Determine the Efficacy of Antimicrobial Treatments of Fibrous Air Filters Determining the Performance of a Commercial Air Purification System for Reducing Airborne Contamination Using Model Micro-Organisms: A New Test Methodology Efficacy of Antimicrobial Filter Treatments on Microbial Colonization of Air Panel Filters Inactivation of Airborne Viruses Using a Packed Bed Non-Thermal Plasma Reactor Environmental Control for Tuberculosis: Basic Upper-Room Ultraviolet Germicidal Irradiation Guidelines for Healthcare Settings The Role of the Hospital Environment in Preventing Healthcare-Associated Infections Caused by Pathogens Transmitted through the Air Effect of Enhanced Ultraviolet Germicidal Irradiation in the Heating Ventilation and Air Conditioning System on Ventilator-Associated Pneumonia in a Neonatal Intensive Care Unit Disinfection Efficacy of Ultraviolet Germicidal Irradiation on Airborne Bacteria in Ventilation Ducts Applications of Ultraviolet Germicidal Irradiation Disinfection in Health Care Facilities: Effective Adjunct, but Not Stand-Alone Technology Studies of Ventilation Efficiency in a Protective Isolation Room by the Use of a Scale Model Internal Contaminant Source Dilution and Filtration in Dedicated Outdoor Air Systems Energy Efficient and Hygienic Operating Theatres' HVAC Airside Design Architectural and Engineering Consideration Design and Ventilation of Operating Room Suites for Control of Infection and for Comfort Design and Maintenance of Hospital Ventilation Systems and Prevention of Airborne Nosocomial Infections Recirculation of Air in Operating Rooms Ventilation Requirements in Hospital Operating Rooms -Part I: Control of Airborne Particles Modeling and Measurement of Air Contaminant Distribution in an Operating Room Ventilated with Split System, Part II: The Impact on Airborne Particles Ventilation Rates and Airflow Pathways in Patient Rooms: A Case Study of Bioaerosol Containment and Removal Effects of Supply Air Temperature and Inlet Location on Particle Dispersion in Displacement Ventilation Rooms Identification of Mycobacteria in Peat Moss Processing Plants: Application of Molecular Biology Approaches Culture-independent Approach of the Bacterial Bioaerosol Diversity in the Standard Swine Confinement Buildings, and Assessment of the Seasonal Effect The Guinea Pig as a Transmission Model for Human Influenza Viruses Hospital Preparedness in Community Measles Outbreaks-Challenges and Recommendations for Low-Resource Settings Role of Air Distribution in SARS Transmission during the Largest Nosocomial Outbreak in Hong Kong Airborne Route and Bad Use of Ventilation Systems as Non-Negligible Factors in SARS-CoV-2 Transmission Modelling the Pressure Drop across HEPA Filters during Cake Filtration in the Presence of Humidity