key: cord-0995613-ifupuouq authors: Faulkner, Cary A.; Castellini, John E.; Zuo, Wangda; Lorenzetti, David M.; Sohn, Michael D. title: Investigation of HVAC operation strategies for office buildings during COVID-19 pandemic date: 2021-11-12 journal: Build Environ DOI: 10.1016/j.buildenv.2021.108519 sha: 7059e04b0087ec825c278d3d18a032444679cc1c doc_id: 995613 cord_uid: ifupuouq To minimize the indoor transmission of contaminants, such as the virus that can lead to COVID-19, buildings must provide the best indoor air quality possible. Improving indoor air quality can be achieved through the building’s HVAC system to decrease any concentration of indoor contaminants by dilution and/or by source removal. However, doing so has practical downsides on the HVAC operation that are not always quantified in the literature. This paper develops a temporal simulation capability that is used to investigate the indoor virus concentration and operational cost of an HVAC system for two mitigation strategies: (1) supplying 100% outdoor air into the building and (2) using different HVAC filters, including MERV 10, MERV 13, and HEPA filters. These strategies are applied to a hypothetical medium office building consisting of five occupied zones and located in a cold and dry climate. We modeled the building using the Modelica Buildings library and developed new models for HVAC filtration and virus transmission to evaluate COVID-19 scenarios. We show that the ASHRAE-recommended MERV 13 filtration reduces the average virus concentration by about 10% when compared to MERV 10 filtration, with an increase in site energy consumption of about 3%. In contrast, the use of 100% outdoor air reduces the average indoor concentration by about an additional 1% compared to MERV 13 filtration, but significantly increases heating energy consumption. Use of HEPA filtration increases the average indoor concentration and energy consumption compared to MERV 13 filtration due to the high resistance of the HEPA filter. The COVID-19 pandemic has increased the need for buildings to improve 1 their indoor air quality to help reduce the risk of infection from airborne 2 transmission. A recent study [1] found that all 318 identified outbreaks of 3 three or more COVID-19 cases in China occurred in indoor environments. J o u r n a l P r e -p r o o f Journal Pre-proof the effect of filter pressure drop on energy consumption and clean-air-delivery-rate. 25 They found replacing a MERV 8 filter with MERV 13/14 filter for a system 26 in fan-only mode with fan speed control increased energy consumption by 27 11-18% but improved clean-air-delivery-rate by a factor of 2.9-3.8. Santos The removal of virus can be described as: where c out is the virus concentration exiting the filter, η f ilter is the filter Next, the static pressure drop caused by the resistance of the filter is: J o u r n a l P r e -p r o o f where ∆p f ilter is the static pressure drop caused by the filter,ṁ f ilter is the 188 mass flow rate of air though the filter, and k f ilter is: where ∆p nom is the nominal pressure drop at the nominal mass flow rate, The settings used for the filters used in this study are shown in Table 1 . Table 1 The viral decay in the room due to gravitational settling and the death 233 of airborne viruses is modeled based on Equation 4, which has been used in 234 literature to model viral decay in well-mixed zones [12] . This is described as: whereċ decay,zone is the rate of viral decay in the zone, k decay is a defined 236 constant rate of viral decay, and c zone is the virus concentration in the zone. where R(t) is risk of infection in terms of percentage, IR is the volumetric time interval. This can be described as: where R 0,T (t) is the predicted number of infections in the zone for time The monthly results for building-average virus concentration for the four 336 strategies are shown in Figure 9 . This further reveals the implications of is calculated and summed for each hour to account for these dynamic effects. For example, R 0 (t) begins to increase at 9:00 AM as the concentration 381 increases and susceptible occupants are exposed to the virus. The slope that there is a 75% chance that one person in the zone that day is exposed to The predicted number of infections for this day are shown next in Figure 417 13. Since the concentrations overlap for the cases (excluding HEPA filter) 418 in Figure 12 , it is expected the predicted number of infections also overlap 419 for these cases. Once again, even though these cases supply 100% clean air The total annual energy consumption for the four different strategies are 431 shown in The monthly breakdown of energy consumption is shown next in Figure 464 14 to compare the operational strategies throughout the year. Both monthly achieve a good balance between the indoor air quality and operational cost. In this paper, we develop computational modules and allow for temporal Indoor 537 Transmission of SARS-CoV-2 COVID-19 Outbreak Among Attendees of an Exercise Facility 540 COVID-19 Outbreak Associated with Air Conditioning 544 in Restaurant HVAC filtration for controlling infectious 565 airborne disease transmission in indoor environments: Predicting 566 risk reductions and operational costs Effect of Ventilation And Filtration on 569 Investigation of potential 572 aerosol transmission and infectivity of SARS-CoV-2 through central 573 ventilation systems Equation-based object-oriented modeling and simulation of data center 576 cooling systems Modelica-based system 578 modeling for studying control-related faults in chiller plants and boiler 579 plants serving large office buildings An optimization 582 [21] Buildings.Examples modelica/releases/v5.0.0/help/Buildings Examples VAVReheat.html# 602 Buildings.Examples.VAVReheat Standard 62.1 Ventilation for Acceptable Indoor Air Quality OpenBuildingControl: Modeling Feedback Control as a Step Towards Formal Design, Specification, Deployment and Verification of Building 611 Control Sequences Evolution of pressure drop across electrospun 614 nanofiber filters clogged by solid particles and its influence on indoor 615 particulate air pollution control MERV 10 Pleated Filters MERV 13 Pleated Filters Estimation of airborne 622 viral emission: Quanta emission rate of SARS-CoV-2 for infection risk 623 assessment Quantitative assessment of 625 the risk of airborne transmission of SARS-CoV-2 infection: prospective 626 and retrospective applications Energy Information Administration. Colorado Net Electricity 631 Generation by Source Spatio-temporal changes 634