key: cord-0983243-rm0v5xog authors: Gaspar, K.; Gangolells, M.; Casals, M.; Pujadas, P.; Forcada, N.; Macarulla, M.; Tejedor, B. title: Assessing the impact of the COVID-19 lockdown on the energy consumption of university buildings date: 2021-12-16 journal: Energy Build DOI: 10.1016/j.enbuild.2021.111783 sha: b4814ccda8aa40826332ec8d549425ce8d9c14a3 doc_id: 983243 cord_uid: rm0v5xog Exceptional pandemic lockdown measures enabled singular experiments such as analysing the energy consumption of vacant buildings. This paper assesses the impact of the COVID-19 lockdown on the energy use of academic buildings. For this purpose, weather-adjusted energy use was compared before and during the lockdown, including different levels of lockdown restrictions. Results obtained for the 83 academic buildings of Universitat Politècnica de Catalunya - Barcelona Tech (UPC) reveal that the avoided energy consumption amounted to over 4.3 GWh during the post-pandemic year. However, the results indicate that academic buildings were still using approximately 46.9% of their typical energy consumption during strict lockdown. This revelation emphasizes the high environmental burden of buildings, regardless of whether they are occupied. In March 2020, the World Health Organization declared COVID-19 to be a global pandemic (Kanda and Kivimaa, 2020) . Urgent measures were adopted to contain the spread of the SARS-CoV-2 virus, including stay at home orders, mandatory quarantines and restricted movements, among others. One year after the COVID-19 outbreak, restrictions still continue and might be prolonged with different intensities, depending on national or localised outbreaks. Along with the staggering loss of life, the pandemic has undoubtedly disrupted lives, businesses and economies (Sovacool et al., 2020) . The pandemic is also having an unprecedented impact on education worldwide. Over 190 countries have implemented closures of educational institutions, affecting over 94% of the world's student population (United Nations, 2020). Although the impacts of COVID-19 on health systems and national economies have been covered extensively in the media, the implications of the disease for energy and climate policy are more prosaic (Sovacool et al., 2020) . Even in the research field, the impact of COVID-19 on energy consumption has not been extensively studied until now although Zhang Following the coronavirus outbreak, universities closed their doors and immediately transitioned to distance learning. Academics quickly adopted digital tools for lectures, conferences and meetings during the lockdown. Many universities held lectures online during the last part of 2019-2020 and the entire 2020-2021 academic year. In other cases, a hybrid model has been adopted, combining mainly theoretical online lessons with in-person lab sessions. In addition, universities around the world are still uncertain about when measures such as physical distancing might end completely. Theoretically, the energy consumption of academic buildings should drop when they are empty. However, minimum operating levels are required to ensure that core activities can be performed remotely (i.e. servers and data centres ensuring access to email, databases or software tools). In addition, essential building services must remain on, such as emergency lights and elevators. Sometimes, shutting down HVAC systems can compromise indoor conditions or cause technical problems that would complicate fast building reopening. Plug loads such as computers, monitors, printers or audio-video equipment might not have been disconnected when the building was closed and could therefore have been consuming energy throughout the period. Although the individual energy consumption of miscellaneous loads is relatively small, they can end up using a significant portion of buildings' energy because of a large, steadily increasing number of devices, their wide distribution around buildings and their invisibility. The COVID-19 crisis provided a unique opportunity to measure on-site the energy consumption of vacant buildings and to devise energy saving options. This is even more relevant as people are expected to study and work from home more often in the future. To the authors' The main objective of this paper was to analyse the impact of the COVID-19 lockdown on the energy consumption of university buildings taking into account climate adjustments to baseline period conditions. The methodology was applied to 83 academic buildings of Universitat Politècnica de Catalunya -Barcelona Tech (Spain) . Following this introduction, Section 2 describes the methodology, Section 3 presents the case study and Section 4 presents and discusses the results obtained for the case study. Finally, conclusions are detailed in Section 5. The methodology used to estimate the impact of the coronavirus lockdown on the energy consumption of university buildings consists of three steps, as shown in Figure 1 :  First, spatial and temporary study boundaries are defined by selecting buildings to be analysed and establishing study periods and their estimated occupancy.  Second, data acquisition process is described. This step encompass data collection process and subsequent data filtering process as raw data usually requires correction and cannot be used directly.  Third, the impact of the COVID-19 lockdown on the energy consumption is evaluated by determining the avoided energy consumption during the post-COVID period compared to the analogous period before the pandemic (covering a full year), considering routine adjustments such as climate conditions and building activity levels. Afterwards, the impact on the overall energy consumption through energy performance indicators is explored and the economic impact of the avoided energy consumption is evaluated. This step involves determining which buildings are going to be analysed. To make an adequate comparison, the selected buildings must be characterised in terms of year of construction, floor area and type of building depending on use. Most academic buildings are intended for more than one use (i.e. teaching rooms, research laboratories, libraries, sports centres, academic and administrative offices, etc.). When the energy consumed by buildings is not sub-metered for individual functional areas, the main use of a building determines the type of building. In this study, the main use of a building is defined as that for which over 50% of its built area is destined. In the event that the area devoted to different uses in a building is similar, without exceeding 50%, the building is classified as mixed use. For each type of building, the operating period and the occupancy levels are identified. Restrictions and their temporally evolution depend on the decisions made by state and local governments. Study periods must be defined according to the restriction levels or the building activity levels, which is the same thing. must be kept within the period. Ideally, the control period should cover at least one year. Other control periods can be used (i.e. the average of the two years immediately preceding the lockdown) but the results might be similar to those obtained from a one-year control period (Rouleau and Gosselin, 2021). whereas non-routine events are characteristics that are not expected to routinely change (i.e. changes in the amount of space being heated or cooled, changes in the buildings' envelope characteristics, changes in the buildings' equipment, changes in indoor air conditions, etc.). Therefore, in this step of the methodology, data related to routine and non-routine adjustments must be collected (i.e. daily outdoor temperature records and total enrolment). Energy performance certificates are a valuable source of information for buildings' main characteristics (i.e. construction year, floor area). Regarding the type of building, the information on the use of spaces can be acquired from the graphic documentation of the building. Building typologies might differ significantly in occupancy patterns, in terms of operating periods (both yearly and daily) and occupation density. Preferably, energy-related data should be retrieved from smart meter data platforms. Alternatively, meter readings or issued bill readings, which are usually provided by building managers, can be used. It might be better to exclude buildings with missing or inaccurate data from the analysis. Daily outdoor temperature records can be obtained from the closest meteorological stations. Typically, the number of enrolled students can be found in university annual reports. However, this analysis can only be performed at school level and each school may be based in more than one building. The impact of the COVID-19 lockdown on the buildings' energy consumption was evaluated by determining the avoided energy consumption during the post-COVID period compared to the control period (Section 2.3.1), by exploring the impact on the overall energy consumption through energy performance indicators (Section 2.3.2), and by estimating the economic impact of the avoided energy consumption (Section 2.3.3). Along the lines of the Efficiency Valuation Organization (2016), the comparison of energy consumption before (pre-COVID periods) and after (post-COVID periods) the lockdown ( Figure 2) should be made using the following equation: where E avoided represents the avoided energy consumption, E adjusted baseline is the adjusted baseline energy consumption or the baseline energy consumption adjusted to routine adjustments, E actual denotes the actual energy consumption and NRA represents non-routine adjustments to reporting period conditions. outdoor dry-bulb temperature and later transformed into heating and/or cooling degree days). Heating degree days (Eq. 2) and cooling degree days (Eq. 3) measure how cold or warm a specific location has been during a certain amount of time, respectively. where Theating base is the outdoor temperature below which the building needs heating, Tcooling base is the outdoor temperature above which the building needs cooling, Toutdoor is the outdoor temperature and N is the number of days of the period to be studied. In any case, base temperatures (also known as balancing points) need to be properly defined according to each case. Data granularity always depends on their availability. If smart meter data is available for all the energy supplies, daily analysis is preferred. If available data is on a monthly basis for any reason, the analysis should be weekly at most, so as not to misunderstand weekday and weekend energy consumption profiles. Energy performance indicators are identified by answering two key performance questions: where Ii j is the average daily energy consumption as a function of the adjustment factors calculated for the j period and Et represents energy consumption during the entire j period, expressed in kWh. Average daily energy consumption data, including energy for heating and cooling, is used. To obtain more accurate results, the average daily energy consumption for heating (Eh) expressed in kWh, and the average daily energy consumption for cooling (Ec) expressed in kWh can be used for the entire period, if possible. N denotes the number of days of the j period. AFi represents the adjustments factors that have an impact on the energy consumption of a building or facility. In this case, differences in consumption observed during the lockdown period might be influenced by routine adjustment factors such as the outdoor temperature and/or the building activity levels. To isolate the influence of outdoor temperature, heating degree days (HDD) and cooling degree days (CDD) are calculated following Eq. (2) and Eq. (3). To isolate the influence of levels of activity within the buildings, differences in the number of enrolled students between periods should be checked. Moreover, it should be noted that if a non-routine event occurs between the compared periods, the designed indicators should take this into account (i.e. an increase in a building's floor area). To determine the impact of the periods of the COVID-19 lockdown on energy consumption, each of the identified periods must be compared with the corresponding control periods in past years. The following equation (Eq. 5) allows an estimation of the difference between the energy consumed during an abnormal situation and normal operating conditions: where VR is the variation rate of indicator Ii expressed in %, I j lockdown represents indicator Ii calculated for the j period of the lockdown and I j control denotes indicator Ii calculated for the j period of the control period. A negative variation rate indicates that the energy consumed during the lockdown period was lower than the energy consumed during the analogous period before the pandemic. Avoided energy consumption (Eq. 1) is translated into economic impact according to energy source prices. The overall economic impact provided by the avoided energy consumption is estimated using Equation (6): where ( ) indicates the total economic impact in period j (in €/period), ( ) is the economic impact in period j in electricity (in €/period), and ( ) is the economic impact in period j in gas (in €/period). (Spain, 2006 ). According to the criteria established in the methodology (Section 2), UPC buildings were first classified according to their main use as teaching buildings, research buildings, office buildings, libraries, sports centres and mixed-use buildings. Table 1 summarizes the main characteristics of the sample in terms of number of buildings, floor area and building age. Daily and yearly operating periods and occupancy patterns for each building typology are summarised in Table 2 . The buildings' main characteristics, including construction year and floor area, were compiled from the UPC Planning, Assessment and Quality Bureau reports (UPC, 2021a) and completed with information provided by the UPC Infrastructure Service. Existing drawings were used to determine building functions. When needed, on-site inspections were also conducted. The number of registered students was collected using schools' annual reports for 2018/2019, 2019/2020 and 2020/2021 (publicly available on the schools' webpages) and UPC statistical and management data (UPC, 2021b). Smart meter data were collected through the UPC Sirena platform (UPC, 2021c). The collected dataset included quarterly electricity consumption data for almost all the buildings and almost all the periods in 2018, 2019 and 2020. To address existing gaps in smart metering data, estimates were used when no more than 12 consecutive quarterly electricity readings were missing. Unfortunately, end-use electricity sub-metering is not available for UPC buildings. Although gas consumption is monitored and displayed on the UPC Sirena platform (UPC, 2021c), detected errors prevented its use and bills had to be used instead. Bills were provided by the UPC Infrastructure Service. In this case, meter readings were available on a monthly basis and they were proportionally distributed to fit the identified periods. In some cases, electricity and gas meter readings include more than one building (often a set of buildings comprising a school). Therefore, this determined the granularity of the analysis. The The impact of the COVID-19 lockdown restrictions on UPC buildings' energy consumption was evaluated in 50 buildings. The remaining buildings (Table 4) had to be discarded, as there were considerable gaps in the electricity readings or the monitoring infrastructure did not cover the analysed periods. For example, the B0 building (on the Diagonal Nord UPC Campus) was first monitored in 2020. Therefore, there were no available data for 2018 and 2019. In this case study, a weekly approach was chosen since gas consumption data were only available on a monthly basis. First, along the lines of what is stated in Section 2.3.1, a baseline energy consumption model was developed using actual energy consumption for the pre-COVID period (from 18/03/2019 to 15/03/2020) for each building. The energy consumption was found to be clearly influenced by climatic conditions, particularly in winter. Therefore, heating degree days were used as a routine adjustment in the baseline equations. To calculate heating degree days, the heating base temperature (T heating base) or the outdoor temperature below which the building needs heating, which is the same thing, was set at 20ºC. Cooling degree days were discarded as an explanatory variable since few UPC buildings have cooling systems and in most cases only a few rooms are cooled. In addition, cooling systems typically only work two months a year (June and July). The number of students enrolled in the UPC schools was found to be very similar in the 2018/2019, 2019/2020 and 2020/2021 academic years (variation rate of 0.9% and 1.0%, respectively). Therefore, the number of registered students was not considered an adjustment factor in the assessment of the impact of the pandemic lockdown restrictions on UPC buildings' energy consumption. The baseline energy consumption model was determined by plotting the energy used for heating (or the best approximation to it) versus weekly heating degree days (Figure 4) . In the second step of the methodology, weekly heating degree days were calculated for the lockdown period (from 16/03/2020 to 14/03/2021) and inserted into the baseline mathematical model to obtain the adjusted base energy consumption. Thirdly, differences between the registered energy consumption (electricity and gas) during the post-COVID period and the adjusted baseline energy consumption were calculated on a weekly basis ( Figure 5 ) and the cumulative sum of differences was calculated and plotted ( Figure 6 ) for each building. As shown in Table 5 energy consumption) for each of the identified periods after the COVID-19 outbreak. Initial lockdown periods experienced the largest decrease in energy consumption. Real energy consumption in period 1 (P1) accounted for 47% of the expected energy consumption according to the adjusted baseline, this period had the strictest lockdown measures. In period 2 (P2) and period 3 (P3), with less stringent measures, actual energy consumption increased, as did the occupancy of buildings, (67% and 75%, respectively). Period 4 (P4) and period 8 (P8) were holidays periods. During these periods there was a slight decrease in expected energy consumption. In period 5 (P5) and period 6 (P6), real energy consumption increased to 82% and 77% of the adjusted baseline energy consumption, respectively. In period 7 (P7), although occupancy of buildings decreased due to new restricting measures, actual energy consumption increased compared to previous periods. However, the increase in energy consumption became more evident during period 9 (P9) and period 10 (P10). Source: own elaboration The results were summarised statistically using IBM SPSS Statistics package 21 (IBM, 2021). Figure 9 shows the time evolution of the impact of the lockdown on the energy consumption of UPC buildings. It can be concluded that differences in the energy consumption were strongly correlated to changes in restriction levels. During period number 0 (P0 from 10/02/2020 to 15/03/2020), buildings were operating normally and therefore no significant changes were detected. Major differences (53.1%) were observed during the first period (P1 from 16/03/2020 to 17/05/2020), with the toughest restrictions. However, one could expect a bigger energy reduction. In other words, energy reduction did not to coincide with the buildings' occupancy drop. This lack of correlation between the occupancy rate and energy consumption was also detected by Chihib et al. (2021) . During the days of the strict lockdown, UPC buildings were completely shut down and the activity in them completely ceased. Lecturers, researchers and students stayed at home and attempted to perform their usual routines in their home offices. Computers, laptops and other officerelated appliances were plugged in at home instead of in lecturers' offices, labs and classrooms. Lighting and space conditioning energy was also shifted from academic buildings to households. In spite of all the above, the results demonstrate that empty buildings still consumed a significant amount of energy. This might have a range of explanations including (i) buildings have a low level of centralised controls, (ii) building systems continue to operate automatically without modifications, (iii) buildings host data servers that must run in the same conditions or (iv) work computers remain on because this is thought to be needed for remote desktop connection. At regional level, Kang et al. (2021) observed that in stronger social distancing, educational and research facilities had the highest decline in energy consumption. The economic impact was estimated according to Equation (6) by considering the avoided electricity and gas consumption.  A data-based comparison of energy consumption before and during the strict lockdown (P1) revealed that the variations in energy consumption were higher in libraries (-74.2%), followed by teaching buildings (-68.1%) and mixed-use buildings (-57.15%). In contrast, the comparison for period 9 (P9), when buildings were only used for examinations, and period 10 (P10), when the second semester of the 2020/2021 academic course began, showed that UPC buildings were found to consume more energy during the lockdown than during the control year (3.0% and 1.1%, respectively). One of the strengths of this study is that the analysed period covers a full year, including the four seasons, with different levels of lockdown restrictions. The methodology could be extrapolated to other geographic areas since differences in lockdown restriction levels and climatic conditions are considered. This research was conducted on academic buildings but the methodology could also be extended to other tertiary-sector buildings such as offices and hotels. The results might be useful to minimize energy consumption in vacant tertiary-sector buildings and forecast demand in case of future pandemic situations. However, this retrospective analysis also allows the identification of potential energy saving opportunities when buildings operate normally. Further research is needed to assess the energy consumed as a consequence of increased digitalisation. This acquires even more importance as the transition towards telework and telelearning has been clearly boosted by the COVID-19 pandemic but it is also a trend that many expect to last. More in-depth analysis and understanding is required to estimate the energy consumed to avoid future spread of infectious diseases in operating buildings as a consequence, for example, of stricter ventilation requirements. Increasing ventilation rates might increase heating and cooling loads, especially in extremely hot or cold seasons. If the existing buildings' capacity is limited, temporary solutions might be adopted including space heaters and portable air filtration systems. In some cases, budget restrictions for system upgrades may make temporary solutions permanent. On another level, and although teleworking has been widely perceived as a more sustainable mode of working or studying compared to the status quo of commuting to centralised buildings (O'Brien and Aliabadi, 2020), the situation is far more complex when the scope is expanded to include home office energy use. The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper. The impact of the COVID-19 on households' hourly electricity consumption in Canada Analysis of the electricity demand trends amidst the COVID-19 coronavirus pandemic Modeling electricity consumption patterns during the COVID-19 pandemic across six socioeconomic sectors in the State of Qatar A Best Practice Guide to Measurement and Verification of Energy Savings Impact of the Lockdown during the COVID-19 Pandemic on Electricity Use by Residential Users Impact of the COVID-19 pandemic on the energy use at the university of almeria (Spain) COVID-19: The impact in US high-rise office buildings energy efficiency Impact of people's behavior on the energy sustainability of the residential sector in emergency situations caused by COVID-19 Indoor Environmental Quality and Consumption Patterns before and during the COVID-19 Lockdown in Twelve Social Dwellings in Madrid Analysis of electricity use and economic impacts for buildings with electric heating under lockdown conditions: examples for educational buildings and residential buildings in Norway EVO 10000-1:2016. Core concepts. International Performance Measurement and Verification Protocol Impacts of COVID-19 on Measurement and Verification (M&V) of Energy Savings Investigation of HVAC operation strategies for office buildings during COVID-19 pandemic A retrospective analysis of the impact of the COVID-19 restrictions on energy consumption at a disaggregated level Addressing the impact of COVID-19 lockdown on energy use in municipal buildings: a case study in Florianópolis The impact of COVID-19 on higher education building energy use and implications for future education building energy studies Changes in energy consumption according to building use type under COVID-19 pandemic in South Korea IBM, 2021. IBM SPSS Statistics 21 Impacts of COVID-19 on energy demand and consumption: Challenges, lessons and emerging opportunities What opportunities could the COVID-19 outbreak offer for sustainability transitions research on electricity and mobility? Impacts of COVID-19 on residential building energy use and performance. Building and Environment Review analysis of COVID-19 impact on electricity demand for residential buildings The effect of occupant distribution on energy consumption and COVID-19 infection in buildings: A case study of university building When pandemics impact economies and climate change: exploring the impacts of COVID-19 on oil and electricity demand in China Does telecommuting save energy? A critical review of quantitative studies and their research methods Impacts of the COVID-19 lockdown on energy consumption in a Canadian social housing building Pandemic and bills: The impact of COVID-19 on energy usage of schools in South Africa. Energy for Sustainable Development Electricity demand during pandemic times: The case of the COVID-19 in Spain Dades de l'estació automàtica Barcelona -Zona Universitària Assessing the impact of COVID-19 on global fossil fuel consumption and CO2 emissions Royal Decree 314/2006, 17 March, approving the Technical Building Code Contextualizing the Covid-19 pandemic for a carbon-constrained world: Insights for sustainability transitions, energy justice, and research methodology Policy Brief: Education during COVID-19 and beyond Relació de les superfícies construïdes per la UPC Dades estadístiques i de gestió. Principals indicadors A preliminary simulation study about the impact of COVID-19 crisis on energy demand of a building mix at a district in Sweden COVID-19 and energy: Influence mechanisms and research methodologies. Sustainable Production and Consumption ☒ The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work  Vacant academic buildings still used 46.9% of their typical energy consumption 2%) and teaching buildings (-68.1%) experienced the highest energy reductions during the strict lockdown This research is part of the R&D project IAQ4EDU, reference no. PID2020-117366RB-