key: cord-0924707-tmkthvq7 authors: Huessler, Eva-Maria; Hüsing, Anika; Vancraeyenest, Markus; Jöckel, Karl-Heinz; Schröder, Bernadette title: Air quality in an air ventilated fitness center reopening for pilot study during COVID-19 pandemic lockdown date: 2022-05-13 journal: Build Environ DOI: 10.1016/j.buildenv.2022.109180 sha: 98d91578c164ec6e49c29dded734c4d988a5de1f doc_id: 924707 cord_uid: tmkthvq7 During COVID-19 lockdowns less people were able to fulfill the WHO recommendations on physical activity. Also, fitness centers were associated to SARS-CoV-2 superspreader events. However, the risk of infection can be strongly reduced by outdoor air ventilation. To investigate whether a reopening of fitness centers can be justified, CO 2 concentration was measured during four days in a fitness center. Except for one room, the observed CO 2 concentrations were mainly under 800 ppm, which stands for high air qualityIn none of the fitness center’s areas, a CO 2 concentration of more than 1000 ppm was observed, which stands for a sufficient air change. The strong decrease of CO 2 concentration during the 15 min evacuations following each hour of workout, speaks for the functionality of the ventilation system. In particular, the number of people present in the studio has a strong impactinfluence on the estimated CO 2 value. In a linear mixed model, an additional CO 2 concentration of 2.24 ppm (95 % confidence interval [2.04, 2.43]) was estimated for this setting with a total volume of 4065 m 3 in the fitness center and a possible air change rate per hour up to 10. This means, so that for 45 visitors, 100 ppm can be added to the predicted concentration. To summarize, a combination of ventilation, restriction of the number of visitors and surveying the CO 2 concentration allowing for further restrictions in case of need, seems to be an adequate means to reduce the risk of SARS-CoV-2 infection in fitness centers. Physical activity plays an important role in public health [1] . The World Health Organization (WHO) recommends for adults aged 18 to 84 an aerobic physical activity of moderate-intensity of 150 to 300 minutes per week or a physical activity of vigorous-intensity of 75 to 150 minutes per week [2] . Additionally, major muscle groups should be strengthened at least twice a week. During COVID-19 pandemic lockdowns, physical activity decreased tremendously worldwide [3, 4] . In studies where subjects were interviewed about their physical activity before and during lockdown a decrease in time of vigorous to moderate intensity of 33 % [3] and of 41 % [4] was observed resulting in only 62.5 % compliance to the WHO recommendations compared to 80.9 % of compliance before lockdown [4] . However, when governments reopened facilities, such as shops, restaurants, bars and theaters, sport facilities often did not have priority. Therefore, it is of special interest to study if and under which conditions a responsible operation of sport facilities such as fitness centers is feasibly. Physical activity can induce an increased inhalation of air to larger proportion inhaled through mouth, getting deeper into the respiratory tract [5] . Hence, outbreaks of COVID-19 in fitness centers have been analyzed in several studies [6, 7, 8, 9] . Some studies suggest a higher risk of infection in fitness centers. Chang et al. [10] analyzed movements of 98 million people by analyzing mobile phone data. They conclude that a majority of SARS-CoV-2 infections can be associated to a minority of superspreader points of interest, including fitness centers. Kriegel and Hartmann [11] estimated that the risk of infection, assuming a SARS-CoV-2 infected person in the facility, is 2 to 3.4 times higher in a fitness center (30 % or 50 % occupied) than in a supermarket (80 % occupied). However, in these studies the ventilation was either not taken into account [10, 9] or mentioned as improvable [6, 7, 8] or only considered as minimum standard [11] . The American Society of Heating, Refrigerating and Air-Conditioning (ASHRAE) states that ventilation systems with a large amount of fresh air supply can reduce the risk of aerosol transmission [12] . The risk of direct transmission of larger droplets cannot be reduced by a ventilation system [12] but by a physical distance between people [13] .Contaminated surfaces seem to represent only a very small J o u r n a l P r e -p r o o f Journal Pre-proof risk of SARS-CoV-2 infection [14] . Many studies support the fact that a large amount of fresh air ventilation plays one of the key roles in reducing the risk of SARS-CoV-2 infection [13, 15, 16] . Thus, the risk of infection can be reduced by a higher ventilation rate. To survey that the air is changed sufficiently and air quality is good enough, CO 2 concentration can be measured [17, 18] . CO 2 concentration can hence serve as a proxy variable for aerosol concentration, that is also commonly used in other environments such as schools or restaurants, e.g. by Di Gilio et al. [19] and by Rivas et al. [20] . For this study and during the lockdown in Germany in spring 2021, the German state of North Rhine-Wesphalia allowed reopening one fitness center of the fitness company FitX GmbH in the city of Essen under the conditions of the current infection control regulation before the official reopening of similar facilities. The aim was to analyze the air quality via CO 2 concentration in an air ventilated fitness center to gain insight under which conditions a responsible opening of fitness centers can be allowed. The here presented pilot study is an observational study. During four days in May 2021 (May 25, 8:00 a.m. to May 29, 07:55 a.m.) technical measurements such as CO 2 concentration in parts per million (ppm), room temperature in Celsius and room humidity in percent were collected. Starting at 08:00 a.m., the 24 hours opening time per day was divided into time slots of one hour of workout for a group of athletes followed by an evacuation of 15 minutes, resulting in 19 time slots per day. In order to get access to the fitness center, visitors had to book in advance one of the available timeslots. Furthermore, a negative COVID-19 test, which must not be older than 48 hours, had to be presented by the trainees, if the visitor cannot prove that he/she is fully vaccinated or recovered. Every visitor had to leave the fitness center during the break of 15 minutes. Wearing face masks (surgery or FFP2 mask) was mandatory except when working out. women and limited to a number of four women working out simultaneously. The fitness classroom was separated to the other rooms by closed doors. Every class lasted 30 minutes and was limited to a maximum number of ten visitors, who had to subscribe in advance. For a detailed class schedule, see Table A .1 in the Appendix. Measurements of CO 2 concentration, relative humidity and temperature, were taken every five minutes by two sensors per room at a height of 1.50 meters. The measurements of CO 2 concentration, relative humidity and temperature are taken by sensors, that measure all these variables with an automatic calibration. The measurement precision for the CO 2 concentration is +/-50 ppm plus 2 % of the measurement. A mechanical ventilation system is installed in the fitness center, where outdoor air is introduced in the fitness center. Incoming and outcoming air is filtered. For a detailed volumetric flow see Table 1 . As a default, the ventilation system is set to 50 % of its potential capacity. If in any of the rooms the threshold of 650 ppm is exceeded, the capacity will be gradually increased up to 100 % where 100 % is reached, when the CO 2 concentration is around 800 ppm. This threshold of 650 ppm will be called technical threshold in the following. In the fitness classroom, that is separated by doors to the other rooms, the volumetric flow rate lies between 575 m 3 /h per person (50 % ventilation) and 1150 m 3 /h per person (100 % ventilation) when the maximum number of ten visitors is reached. In the other rooms, the volumetric flow rate for scenario A (max. 111 visitors) lies between 187 m 3 /h per person (50 % ventilation) and 374 m 3 /h per person (100 % ventilation), and in scenario B (max. 83 visitors) between 250 m 3 /h (50 % ventilation) per person and 500 m 3 /h (100 % ventilation) per person. The German national organization for standardization (Deutsches Institut für Normung, DIN) recommends a minimum volumetric flow rate of 60 m 3 /h per person [21] . Thus, in scenario A with only 50 % ventilation, volumetric flow rate is more than three times higher than recommended. Access to the fitness center is recorded with a turnstile. 3,770 entrances were registered of which 551 entrances are counted for two time slots, as some visitors stayed for more than one slot. For the calculation of the number of visitors associated with a time slot, the visitors' entrances were fully counted, independently of the length of stay. In addition to the entrances to the fitness center as such, the entrances to the fitness classroom were registered separately. The exact number of visitors, that were present in the fitness classroom during a specific time slot, is therefore known. For all other areas in the fitness center, it is only known, how many visitors were present overall during a specific time slot, but not for a specific area. Hence, for the analyses regarding the fitness classroom, only the number of visitors registered to the fitness classroom is considered. For the analyses regarding all other areas, the total number of visitors in the fitness center minus the number of visitors in the fitness classroom is calculated. Descriptive analyses will be provided for the number of visitors in the fitness center as well as J o u r n a l P r e -p r o o f Journal Pre-proof for the technical measurements, i.e. CO 2 , temperature and relative humidity. Measurements in the same and different rooms are compared through Pearson's correlation coefficients. Graphical representations will be provided, where appropriate. The primary variable of interest is the concentration of CO 2 (dependent variable). To analyze the influence of potential covariates, e.g., the scenario and the number of visitors per slot on the dependent variable, a regression model will be applied. There are two sensors in each room, that measure the concentration of CO 2 simultaneously. To avoid underestimation of the CO 2 concentration, only the maximum of two simultaneous measurements in a fitness area is considered for analysis. Since the measurements are recorded every five minutes, 13 measurements remain per time slot per room. To account for these repeated measures, a linear mixed effect model for repeated measures will be applied to analyze the influence of the covariates on CO 2 . For every time slot and fitness area, a random effect with an autoregressive correlation of first order will be modeled. As the exact number of visitors in the fitness classroom is known, this area will be analyzed separately. The other rooms will be analyzed jointly. In addition, a subgroup analysis per room will be provided. In There were a total of 4,232 people in the entire fitness center (minus the people in the fitness classroom), and 89 people in the fitness class room (see Table 2 ). Almost two third of the visitors (without fitness classroom) are male and almost three quarter of the visitors are younger than 30 years. Hence, men under 30 represent the largest part of the number of visitors with 46 %. In contrast, the fitness classroom is mainly attended by women (90 %). The maximum number of allowed visitors (111 in scenario A and 83 in scenario B) is not reached in any of the time slots (see Figure 1 ). On average, the number of visitors is higher in scenario A, where more visitors were allowed in the fitness center. Journal Pre-proof In Table 3 , the summary of the air quality measurements by room and scenario is represented. The The room temperature varies from 19.4 • C to 30.5 • C (see Table 3 ). Noticeable is the maximum observed value of 30.5 • C in the ladygym, whereas in all other areas all temperature measurements are below 23 • C. The relative humidity varies from 37.5 % (ladygym) to 62.5 % (free weight). Pearson's correlation coefficient between measurements in the same room was usually high (≥ As the values for the CO 2 concentration between the sensors are highly correlated in the areas Fitness 1, Fitness 2, free weight and fitness classroom, only the maximum of the two sensors is considered in the following. The CO 2 concentration in the ladygym will be represented separately for the two sensors, since they do not correlate very strongly. In the areas Fitness 1, Fitness 2 and free weight, the CO 2 concentration is in general lower during night than during day (see Figure 2 ). This can be explained by a lower number of visitors during nighttime. All graphs show a high variation, probably due to the 15 minutes break that follows of each time slot. The values for the CO 2 concentration seem to be higher in these three areas in scenario A, where more people are allowed in the fitness center. In the areas Fitness 1 and Fitness 2, it is only necessary for a few time slots to increase the power of the ventilation system (due to a CO 2 concentration greater than 650 ppm) regarding scenario B, but almost necessary for all time slots regarding scenario A. In the free weight area the threshold of 650 ppm is exceeded in nearly every time slot regardless of the scenario. In summary, the CO 2 concentration is much higher in the free weight area than in the other ones. The development of the CO 2 concentration in the fitness classroom is represented in Figure 4 . When no class is offered, i.e. no visitors are allowed in the room (black line), the CO 2 concentration varies slightly above 400 ppm, which is comparable to the CO 2 concentraion of outdoor air [23] . During nighttime and just before 8:00 a.m. the CO 2 concentration decreases, which is probably due to the lower number of visitors in the fitness center. At the beginning of each class, the concentration increases, especially when a higher number of visitors attend a class. The technical threshold of 650 ppm was only reached once. In order to predict the CO 2 concentration and to analyze the effects of the covariates, i.e. number of visitors, scenario, time t and t 2 , a linear mixed model was applied, where for 76 time slots (19 per day) a random effect is estimated for each room. The results for the fixed effects are shown in Table 4 . They reveal that the CO 2 concentration is estimated at the lowest in the ladygym. The room with the highest estimate is the free weight area with an estimate of a CO 2 J o u r n a l P r e -p r o o f Journal Pre-proof The linear mixed model was applied to the data set split by room. Of main interest is the comparison of the different estimates for the number of visitors separated by age and sex (see four effects with a significant confidence interval not including zero. The small effects for sensor 2 can be due to the small number of women allowed in the ladygym. Interesting is that the effect for the number of men under 30 years is the largest and the only significant effect. A possible explanation can be, that women tend to prefer the ladygym especially, when the number of young men in the fitness center is large. The fitness classroom is the only room for which the numbers of participants in the room itself are known. The effects for men in the fitness classroom are negative. However, these parameter estimates have a large standard error, so that the 95 % confidence intervals for these effects are According to the German standard DIN EN 19779:2007-09, a CO 2 concentration ≤ 800 ppm stands for high air quality, > 800 ppm but ≤ 1,000 ppm for medium air quality, > 1,000 ppm but ≤ 1,400 ppm for moderate air quality and > 1,400 ppm for low air quality [24] . A CO 2 concentration of approximate 400 ppm can be expected in outdoor air [23] . During the study period of four days outdoor air CO 2 concentrations between 391 ppm and 441 ppm were observed. This is larger than the minimum CO 2 values observed in the fitness center (minimum of 378 ppm in the classroom), which can be due to small measurement errors and different measurement methods. To reduce the risk of a SARS-CoV-2 infection, the German Environment Agency (Umweltbundesamt) recommends a high ventilation rate and states that a CO 2 concentration of less than 1,000 ppm can be applied as an indicator if the air change is sufficient [25] . They argue that a CO 2 concentration of more than 1,000 ppm is potentially linked to an increased SARS-CoV-2 infection risk. The German "expert group for aerosols" recommends during COVID-19 pandemic to start ventilation when CO 2 concentration is larger than 800 ppm. They argue that a CO 2 concentration smaller than 800 ppm, obtained by ventilation, is a useful approach to reduce aerosol concentration and that up to now there is no evidence, that a threshold of 1,000 ppm is not sufficient [18] . In our study of indoor air quality in a fitness center, the CO 2 concentration of 400 ppm for fresh air was exceeded most of the time. However, the threshold of 1,000 ppm was never reached in any of the rooms. Over the four days the CO 2 concentration varied between 378 ppm (fitness classroom) and 983 ppm (free weight area). In all areas, except for the free weight area, the CO 2 concentration was mostly under 800 ppm (maximum value 806 ppm in Fitness 1). Thus, the air change in these areas seems to be sufficient. This is equivalent to a sufficient ventilation rate, as the ventilation rate is proportional to the air change rate for a given room. In the free weight area, the threshold of 800 ppm was exceeded several times. However, because of a technical problem, the J o u r n a l P r e -p r o o f Journal Pre-proof ventilation system was not working as intended at a capacity of 100 %, when the CO 2 concentration was larger than 800 ppm. It is to question, to which extent the CO 2 concentration could have been lower in the free weight area, if the ventilation system had worked without disturbance. Although the ventilation system did not work properly when high values of CO 2 concentration were reached, the air change does not seem to be insufficient, since all observations are smaller than 1,000 ppm. However, even if the threshold of 1,000 ppm is never reached, it can be questioned, if this threshold is large enough for fitness centers. Peng and Jimenez [26] point out that the heavier the exercise, the less excess CO 2 volume mixing ratio an uninfected individual has to inhale for 1 hour for a given probability of infection. concentrations (see, e.g., Batterman [27] of fitness facilities with a reasonable risk of infection seems feasible. As a threshold of 1,000 ppm was never reached, a volumetric flow rate between 250 m 3 /h (50 % ventilation) and 500 m 3 /h per person seems to be sufficient. However, as the infection risk increases with a higher amount of physical activity [26] , it could be advisable for this setting, to implement additional restrictions at least for the free weight area, since the free weight area is the only area with CO 2 concentrations regularly above 800 ppm and an area where high physical activity is expected. Such additional restrictions can be, e.g., a smaller amount of visitors for this area or additional filtration. Because of a strong decrease of CO 2 concentration during every 15 minutes break, one can conclude that the ventilation system serves its purpose. The results of this study are in line with recommendations of limiting the number of visitors and to focus on ventilation to keep air quality high [21] . Here, not the aerosol concentration itself was measured to evaluate the risk of infection, but the CO 2 concentration. As discussed, the CO 2 concentration is a good indicator for the aerosol concentration if air is not cleaned. It would, nevertheless, be of interest to analyze the aerosol emission during physical exercise more in detail, as done by Blocken et al. [28] and few others, e.g., Almstrand et al. [30] and Johnson and Morawska [31] . The conducted study was a pilot study under several restrictions. For instance, the visitors had The analysis of the study was funded by the city of Essen, Germany. Appendix A. Details of fitness center Fitness 1 Combi-Sensor 2 Combi-Sensor 1 Combi-Sensor 1 Combi-Sensor 2 Combi-Sensor 2 Combi-Sensor 2 Combi-Sensor 1 Combi-Sensor 1 Erdgeschoss Figure Physical inactivity: the biggest public health problem of the 21st century Global recommendations on physical activity for health Effects of COVID-19 home confinement on eating behaviour and physical activity: results of the ECLB-COVID19 international online survey A pandemic within the pandemic? Physical activity levels substantially decreased in countries affected by COVID-19 Exercise and outdoor ambient air pollution SARS-CoV-2 superspread in fitness center Community transmission of SARS-CoV-2 at three fitness facilities-Hawaii COVID-19 outbreak among attendees of an exercise facility Cluster of coronavirus disease associated with fitness dance classes, south korea Mobility network models of COVID-19 explain inequities and inform reopening Covid-19 Ansteckungüber Aerosolpartikel -vergleichende Bewertung von Innenräumen hinsichtlich des situationsbedingten R-Wertes ASHRAE position document on infectious aerosols Can indoor sports centers be allowed to re-open during the COVID-19 pandemic based on a certificate of equivalence? COVID-19 rarely spreads through surfaces. So why are we still deep cleaning Experimental investigation of indoor aerosol dispersion and accumulation in the context of COVID-19: Effects of masks and ventilation Human exposure to air contaminants in sports environments Infection risk in gyms during physical exercise Expert Group Aerosols" on the development, infectivity, spread and reduction of airborne, virus-containing particles in the air CO2 concentration monitoring inside educational buildings as a strategic tool to reduce the risk of Sars-CoV-2 airborne transmission Impact of natural ventilation on exposure to SARS-CoV 2 in indoor/semi-indoor terraces using CO2 concentrations as a proxy Sports halls -Halls and rooms for sports and multi-purpose use -Part 1: Planning principles R: A Language and Environment for Statistical Computing, R Foundation for Statistical Computing Gesundheitliche Bewertung von Kohlendioxid in der Innenraumluft Ventilation for non-residential buildings -Performance requirements for ventilation and room-conditioning systems Das Risiko einerÜbertragung von SARS-COV-2 in Innenräumen lässt sich durch geeignete Lüftungsmaßnahmen reduzieren. Stellungnahme der Kommission Innenraumlufthygiene am Umweltbundesamt Exhaled co2 as a covid-19 infection risk proxy for different indoor environments and activities Review and extension of co2-based methods to determine ventilation rates with application to school classrooms Ventilation and air cleaning to limit aerosol particle concentrations in a gym during the COVID-19 pandemic Position paper of the Gesellschaft für Aerosolforschung on understanding the role of aerosol particles in SARS-CoV-2 infection Effect of airway opening on production of exhaled particles The mechanism of breath aerosol formation The authors are indebted to all participants in the pilot study, in particular to the personnel of the City of Essen, who made this study possible. The city of Essen funded the analysis of this study. J o u r n a l P r e -p r o o f Air quality in an air ventilated fitness center reopening for pilot study during COVID-19 pandemic lockdown Karl-Heinz Jöckel Bernadette Schröder  Real world data was observed measuring air quality in a fitness center with restrictions due to the COVID-19 pandemic with a special focus to air ventilation  In none of the fitness center's areas, a CO 2 concentration of more than 1,000 ppm was observed, which stands for a sufficient air change  Except for one room, the CO 2 concentration was mainly under 800 ppm, which stands for high air quality  During predefined breaks, the CO 2 concentration strongly decreased, showing the functionality of the ventilation system  The number of visitors in the fitness center has a strong impact on the estimated CO 2 concentration The authors declare that they have no known competng fnancial interests or personal relatonships ☒ that could have appeared to influence the work reported in this paper.The authors declare the following fnancial interests/personal relatonships which may be considered ☐ as potental competng interests: