key: cord-0921565-l4iby025 authors: Guo, By Mingyue; Xu, Peng; Xiao, Tong; He, Ruikai; Dai, Mingkui; Zhang, Yongming title: Review and comparison of HVAC operation guidelines in different countries during the COVID-19 pandemic date: 2020-10-11 journal: Build Environ DOI: 10.1016/j.buildenv.2020.107368 sha: e7029d8006408a38bcb217b826104d3fe9c6bbfa doc_id: 921565 cord_uid: l4iby025 Various organizations and societies around the globe have issued guidelines in response to the coronavirus disease (COVID-19) and virus (SARS-CoV-2). In this paper, heating, ventilating, and air-conditioning-related guidelines or documents in several major countries and regions have been reviewed and compared, including those issued by the American Society of Heating Refrigerating and Air-Conditioning Engineers, the Federation of European Heating, Ventilation, and Air Conditioning Associations, the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan, Architectural Society of China, and the Chinese Institute of Refrigeration. Most terms and suggestions in these guidelines are consistent with each other, although there are some conflicting details, reflecting the underlying uncertainty surrounding the transmission mechanism and characteristics of COVID-19 in buildings. All guidelines emphasize the importance of ventilation, but the specific ventilation rate that can eliminate the risk of transmission of airborne particulate matter has not been established. The most important countermeasure, commonly agreed countermeasures, the conflicting content from different guidelines, and further work have been summarized in this paper. residential buildings, hotels used for temporary isolation, and public buildings that were 23 transformed into temporary hospitals. of SARS-CoV-2 and the countermeasures that need to be taken with respect to HVAC systems. 3 A respiratory infection can be transmitted through direct contact with surfaces contaminated 5 by respiratory droplets, by inhaling airborne respiratory droplets, or by fecal-oral transmission. 6 According to World Health Organization's (i.e. WHO) latest technical briefing, [5] the two primary 7 transmission routes are inhaling airborne droplets that contain viruses and contact. Up to now, 8 there is no scientific evidence to support fecal-oral route transmission for SARS-CoV-2, but some 9 evidence has shown that the SARS-CoV-2 virus may lead to intestinal infection and could be 10 present in patients' feces. In specific situations, this can trigger airborne transmission, such as with 11 SARS (e.g. Amoy Gardens [21] ). ASHRAE explains the inhalation route of transmission (e.g., see 12 have shown that SARS-CoV-2 is detected in the air. [5] Before a definitive conclusion can be made 19 at as to whether SARS-CoV-2 can be transmitted by air, the HVAC system should be operated 20 with caution. Droplets < 1 micron have a high probability of transmission through ventilation 21 ducts, since these smaller diameter droplets can remain suspended for long periods of time. In the 22 United States, most air-conditioning systems are all-air systems, and an infection in one room is 23 more likely to infect an entire floor, or even an entire building. There have been no reports so far 24 of COVID-19 disease acquired because of spreading through the HVAC system. The main transmission routes of SARS-CoV-2 in a building, as established by REHVA, are 1 shown in Figure 2 . Dark blue arrows represent transmissions recognized by WHO, and REHVA 2 and WHO have increasingly been paying more attention to fecal-oral transmission, because 3 SARS-CoV-2 viruses have been detected in stool samples. [24, 25] A light blue color shows 4 transmission by inhalation of airborne droplets, which is known as a route from SARS-CoV-1 and 5 other flu viruses. Current understanding of inhalation transmission of SARS-CoV-2 is that it is 6 more probable when certain conditions are met (i.e., crowded indoor environments, with longer 7 exposure times and minimal fresh air ventilation to dilute concentrations of airborne droplets). Given that we do not yet fully understand SARS-CoV-2, REHVA proposes to adopt the 12 principle of ALARA (As Low as Reasonably Achievable), especially in "hot spot" areas; this is in 13 addition to the standard hygiene measures recommended by WHO. 14 SHASE's views on the transmission of the virus are similar to those of ASHRAE and 15 REHVA. A study comparing SARS-CoV-2 with SARS-CoV-1, mentioned in the SHASE guide, 16 shows that the survival characteristics of SARS-CoV-2 and SARS-CoV-1 are similar, and there is 17 evidence that SARS-CoV-1 can be transmitted through air. [26] 18 Overall, the views on SARS-CoV-2's transmission routes are consistent. Airborne 19 transmission of SARS-CoV-2 is possible, according to the experience with previous similar 20 viruses (e.g., SARS-CoV-1). Suggestions on the operation and maintenance of HVAC systems are 21 given in the form of guidelines in almost all countries, to help reduce the spread of SARS-CoV-2. 22 HVAC engineers should propose solutions based on available information to ensure safe and 24 healthy buildings. Since national guidelines mainly apply to public buildings (e.g. office buildings 25 and commercial buildings) other than hospitals and health centers, the countermeasures for HVAC 26 systems suggested in this paper primarily focus on public buildings. Ventilation with effective airflow patterns is the most important infectious disease control 2 strategy, [28] by diluting the indoor air around the source and removing the infectious agents. 3 Many buildings are completely or partially naturally ventilated. These strategies are associated 4 with both risks and benefits. On the one hand, the airflow rate and quality of outdoor air in those 5 buildings are variable and unpredictable, resulting in different air distribution patterns, thus greatly 6 reducing the ability to actively manage risk in these buildings. On the other hand, the rational use 7 of natural ventilation can reduce the risk of infectious aerosols. 8 Pressure differentials between zones in the building should be controlled so that air flows 9 from safe areas to unsafe areas, from personal use areas to public areas, such as from anterooms to The research carried out by Derby 2) Operate HVAC related device including exhaust fan and outside air damper to provide 7 flushing 2 hours before and post occupancies. 8 3) Keep the system running on minimum outside air when the building is unoccupied. 9 4) Run garage exhaust two hours before occupancy. recommendation from REHVA can be summarized in the following aspects. 18 The key to mitigate the airborne transmission of SARS-CoV-2 in buildings is secure 20 ventilation of spaces with outdoor air. REHVA recommends supplying as much outside air as 21 reasonably possible. Ensure the amount of fresh air supplied per person by maintaining or 22 increasing social distancing (minimum physical distance 2-3 m between persons). 23 The windows should be opened regularly even in mechanically ventilated buildings. It is 24 recommended to open windows for about 15 minutes before occupation of the room, especially a 25 room that was occupied by others beforehand. 26 During the outbreak, HVAC system shouldn't be operated as usual. It is recommended to run 28 ventilation at the nominal speed for at least 2 hours before the building usage time and at a lower 29 speed 2 hours after the building usage time. In DCV systems, the CO 2 setpoint is suggested to be 30 changed to 400 ppm, ensuring ventilation system operation at the nominal speed. It is not 31 recommended to turn ventilation off at night and during weekends; instead, the system should be 32 kept running at a lower speed. In buildings that have been vacated due to the outbreak, such as 33 office buildings and schools, it is also not recommended to turn the ventilation system off, but to 34 keep the system running continuously at a lower speed, so that the virus in the building can be 35 removed from the building with limited energy penalties. For the toilet ventilation system, it is 36 recommended to keep running for 24 hours a day, 7 days a week to avoid the fecal-oral 37 transmission route. [23] It appears that the viability of SARS-CoV-2 will not be reduced significantly in 12 moderate humidity (40-60%), according to the studies. However, the nasal chambers and mucous 13 membranes of human beings are more sensitive to infections at a very low relative humidity range 14 of 10-20%. [38] However, the indoor relative humidity in the forthcoming climatic conditions in 15 Europe will be higher than 30% without humidification. Most importantly, humidification is not a 16 method for reducing the viability of SARS-CoV-2. 17 REHVA believes that filters in central outdoor air and extract air have low efficiency and can 19 filter only large particulate matter, but the filters should be replaced and maintained as usual 20 according to the maintenance schedule, to prevent filter blocking, which would reduce the supply 21 airflow rate. For air cleaning, REHVA considers cleaning with HEPA filters to be effective, but the 22 airflow through air cleaners is often limited (due to noise and fan size). Hence, it is recommended 23 to locate the air-cleaning device close to the breathing zone. Special UV cleaning equipment 24 installed for the supply air or room air treatment is also effective. 25 For heat recovery equipment, it is recommended to inspect the devices including setting the 27 pressure difference measurement to make sure that leakages are under control. The leakage rate of 28 properly operating rotary heat exchangers is in the range 1-2%. For existing systems, heat 29 exchangers with leakage below 5% are acceptable. This can be compensated for by increasing the 30 amount of outdoor air ventilation. However, if return air fans have been mounted in those systems, 31 the pressure of the exhaust air may be higher than the supply air side. The leakage rate will then 32 increase to 20% or so, which is not acceptable. Because the air leakage rate has nothing to do with 33 the rotation speed of the rotor, there is no need to switch the rotors off. As the leakage rate is 34 higher at a low airflow rate, it is suggested to operate with an increased ventilation rate. 35 To be on the safe side, REHVA recommends to wear masks, gloves‚ and other respiratory 37 protection when regular filter replacement and maintenance work is being performed. Besides, REHVA release two system specific guidance documents on fan coils operation in 3 case recirculation can't be avoided and on measures to minimize air-leakages across rotary heat 4 exchangers. 5 As members of REHVA, CIBSE and RLT have supported the recommendations in the 6 REHVA guidance. CIBSE stressed the importance of ventilation and outdoor air. But in-duct 7 UV-C devices are not recommended by CIBSE unless it is to decontaminate air that is recirculated. 8 Devices that emit ozone or other potentially hazardous by-products are also not recommended in 9 occupied spaces.[16, 18] RLT believes the SARS-CoV-2 will not spread through HVAC systems. The SHASE's recommendations regarding operation of air-conditioning equipment and other 15 facilities as SARS-CoV-2 infectious disease control are as follows. 16 SHASE recommends to open the outer window regularly to increase outdoor air even if the 18 ventilation systems are on, while ensuring thermal comfort and no draft, because 95% of the 19 indoor air will be replaced when the outdoor air is three times the room volume. 20 For houses and small buildings, the ventilation systems should be kept on and supply as 21 much outdoor air as possible. For centralized air-conditioning mainly in large buildings, as a 22 general principle, it is recommended to increase the opening of the outdoor air damper and 23 exhaust air damper to as high as 100% if possible. If the airflow is inverter controlled, the current 24 value of both supply fan inverter and exhaust fans inverter should be raised, and the automatic 25 control of the outdoor air should be removed. 26 It is recommended to lower the CO 2 setpoint. It is also recommended to increase the running 28 time of air-conditioning equipment, running it continuously for 24 hours if possible. 29 The exhaust system of the toilet should be kept running continuously. In addition, to ensure 30 negative pressure in the toilet, the toilet window should be kept closed. 31 According to WHO, the SARS-CoV-2 virus can infect any community, not only in dry and 33 cold areas, but also in hot and humid areas such as Guangxi Zhuang Autonomous Region and 34 Singapore. [39] However, in a low-temperature environment, the drying of the oral mucous 35 membrane in humans decreases its defensive efficacy; therefore, in addition to ensuring the 36 necessary amount of ventilation (30 m 3 /h per person), the temperature should be controlled 37 between 17 and 28 ℃, and the relative humidity should be controlled between 40 and 70%. 38 For a system with 100% outdoor air, the filter can be operated as usual. For return air 40 operation, it is recommended to check the differential pressure of the filter more often and replace 1 the filter sooner than usual. 2 As for air cleaner, not all air cleaners can filter out the virus, and the purification efficiency is 3 also related to the volume of air. The air cleaner should be selected considering the volume of the 4 target space. Air cleaners are effective as an auxiliary device. However, the effect of ventilation on 5 reducing the concentration of viruses is more significant. 6 For the static total heat exchanger, the risk of virus leakage through the heat exchanger is 8 small, as low as approximately 5%. Therefore, it can be operated in heat exchange mode. The 9 manual recommends operating it with a large effective ventilation volume. When buildings use a 10 merged drainage system to handle drainage, it is also recommended to install a check valve for the 11 airflow in the drainpipe of the indoor unit. 12 For the rotary type, if a purge sector is set and the pressure balance is proper (return air 13 pressure < supply air pressure), the risk of virus entry is acceptable. Therefore, it is recommended 14 to operate with a large effective ventilation volume, while checking/adjusting the operation status 15 as necessary. 16 The toilet lid should be closed while flushing the toilet. The integrity of the water seal should 18 be checked regularly. The recommendations differ depending on the conditions prevailing in the rooms. For rooms 27 with openable exterior windows, such windows should be opened as much as possible. For rooms 28 without exterior windows and exhaust ventilation, two-way energy-saving ventilation machines 29 should be installed to meet the need for ventilation. For rooms with a centralized outdoor air 30 system and floor-centralized exhaust system, it is recommended that the door remain open (or 31 blinds can be set up in the door). Alternatively, a mechanical exhaust fan can be set up on the 32 partition wall to ensure that the total exhaust volume of the floor-centralized exhaust system is not 33 less than 70% of the design outdoor air volume. For rooms with a centralized outdoor air system 34 but without a floor-centralized exhaust system, addition of a mechanical exhaust system is a 35 reasonable option; or with the consent of the fire department, a fire anti-smoke exhaust system 36 could be used as a centralized exhaust system. 37 When ventilation is insufficient, the exhaust system should be turned on or a portable room 38 air cleaner with a HEPA filter should be added. Air-conditioning and mechanical ventilation 39 systems should be turned on in advance and closed later. 40 The amount of outdoor air in the air-conditioning system is recommended to be increased as 2 much as possible. For a centralized air-conditioning system, if the system is shared by multiple 3 areas, the system should be operated with 100% outdoor air. If recirculated air is necessary, the 4 ratio of outdoor air should be greater than 40%, and the system must be equipped with a return air 5 filter (at least F7 grade, a level of filters raising by the European Committee for Standardization at 6 EN779, the efficiency of which is greater than 65% for particles range 1.0-10.0 μm). [12] The 7 quality of outdoor air should be ensured in the fan coil with the outdoor air system. Rooms 8 without an outdoor air system and openable outside window should be discontinued. If "suspected 9 cases" are found in the building, all the convective terminals (fan coils, etc.) should be shut down. 10 In the operation of the air-conditioning system, the air supply temperature in heating mode is 11 recommended to be increased, and in cooling mode, it is recommended to be decreased.[40] 12 The filter in the HVAC system should be cleaned and replaced as usual. For office buildings, 14 "chemical disinfection" should not be used in air-conditioned rooms and air-conditioning plant 15 rooms. UV devices should not be installed in the air-conditioning system. During working hours, 16 the indoor air cleaner should be operated. 17 Indirect heat exchangers and other heat exchangers that are not associated with the risk of 19 mixing outdoor air and exhaust air can operate as usual. Rotary heat exchangers are not 20 recommended to be used.[40] 21 The dining room should be separated from the kitchen, and the pressure in the kitchen should 23 be slightly higher than in the other areas. To maintain the positive pressure in the kitchen, the 24 pressurized ventilator should be turned on while the kitchen exhaust fume fan runs. The exhaust 25 systems of the toilets, sewage rooms, etc., are recommended to operate continuously to maintain 26 negative pressure.[40] 27 For the maintaining of the HVAC system, regular inspection and cleaning of the system 29 should be carried out. The position of the outdoor air vents should be checked to ensure the quality 30 of the outdoor air, to avoid outdoor air and exhaust air short circuit. 31 For the water system, it is recommended to check whether the water seals of each drainage, 32 wastewater, medium water, and condensate system, and of the drainage apparatus, are effective. 33 Keep the uplift ventilation pipe in the sewage system unobstructed, and set up silver ions, the 34 photocatalytic oxidation sterilizer, and other equipment in the supply water pipe to ensure the 35 safety of the water system. guidelines are of great benefit for guidelines updating. It also helps to implement reasonable 3 countermeasures, rapidly respond to the outbreak and carry out further studies related to 4 SARS-CoV-2. 5 The main countermeasures to mitigate the risk of the indoor transmission of SARS-CoV-2 6 issued by different guidelines are shown by Table A .1 in appendix A. 7 Guidelines or documents released in different countries exhibit commonalities regarding the 8 transmission mechanism of COVID-19 in buildings. Air-conditioning and ventilation systems 9 could minimize the airborne transmission of viruses. In regard to the operation of the HVAC 10 system, the specific content in the guidelines varies slightly. 11 As for the operation of the HVAC system, all the guidelines or documents mentioned above 13 emphasize the importance of increasing the outdoor air ratio and ventilation. They all agree that 14 the ventilation system should operate before the room is occupied, and that it should operate for as ASHRAE also recommends increasing the filter level in the air-conditioning system to Other guidelines suggest that the filters used in the normal operation and maintenance of 26 air-conditioning systems should be sufficient, and no pipe cleaning is required. 27 For room air cleaners, HEPA filters are effective for controlling the spread of viruses. Both 29 REHVA and SHASE guidelines mention that most air cleaners recirculate a limited amount of air. 30 ASHRAE and REHVA both believe that ultraviolet radiation can effectively inactivate viruses. 31 ASHRAE suggests that ultraviolet sterilization irradiation equipment be used in all buildings, 32 while REHVA believes that it is more appropriate to use it in medical buildings. The Architectural 33 Society of China states that it is not appropriate to install UV lamps in air-conditioning and 34 ventilation systems for office buildings without a firm basis or supporting medical opinion. 35 All guidelines agree that the principle is to ensure airflow from areas with high cleanliness to 37 areas with low cleanliness. All the guidelines state that the exhaust system should be kept running 38 and that the outer windows should be closed to ensure negative pressure in the toilet. The Chinese 39 guidelines also mention that a slight positive pressure should be maintained in the kitchen. 40 For heat recovery devices, the guidelines in the updated REHVA guide are consistent with 2 those of SHASE. Both agree that if the return air pressure is lower than the supply air pressure, the 3 mixing amount of return air caused by the heat exchanger is acceptable, and that increasing the 4 supply air volume can further reduce the mixing amount. The current guidelines issued by China 5 state that heat recovery devices except indirect heat exchangers should be closed and bypassed. 6 For indoor temperature and humidity setpoints, the ASHRAE recommendations depend on 8 the prevailing situation and building conditions. According to REHVA, it is not necessary to adjust 9 the temperature and humidity setpoints in spring. SHASE recommends that the temperature 10 setpoint should be between 17 and 28 ℃, and that the relative humidity setpoint should be 11 between 40 and 70%. However, the Chinese guidelines only recommend that the air-conditioning 12 system should increase the supply air temperature during the heating season and reduce the supply 13 air temperature during the cooling season. It is controversial whether to change the setpoint of temperature and relative humidity in the 27 air-conditioning system. To inactivate the virus, 37 ℃ for one day and 56 ℃ for 30 minutes were 28 needed. [36] It is obviously impossible for people to stay in such a high-temperature environment 29 for a long time. So, there is no need to change the temperature setpoint. As for relative humidity, 30 the viability of SARS-CoV-2 will not decrease when the relative humidity is 40-60%. [32] 31 However, studies have shown that relative humidity below 40% can increase 32 infections. [32]( elaborate in section 3.2.3). Thus, it is plausible that humidification is needed when 33 the relative humidity is lower than 40%. 34 2) The main commonly agreed countermeasures from different guidelines are listed 5 following: 6 For outdoor air, it is recommended that supply as much outdoor air as possible. Open the 7 outdoor air damper as high as 100% if possible. 8 For the operation of HVAC system, it is recommended that the running time of HVAC system 9 should be increased. REHVA and ASHRAE both recommend open HVAC related devices 2 hours 10 before and after occupancies. 11 For air cleaning strategy, portable room air cleaners are recommended. It is crucial to 12 maintain the filter regularly. 13 For air conditioning devices (e.g. AHU), disable the recirculation sector if possible. 14 It is also recommended to keep negative pressure in toilets and check the water seals 15 regularly. 16 3) The following countermeasures vary from different guidelines: 17 For the temperature and humidity setpoint of the air-conditioning system, the guideline 18 issued by REHVA suggests there is no need to change it in the forthcoming climatic conditions in 19 Europe while SHASE recommends to control the temperature between 17 and 28 ℃ and control 20 the relative humidity between 40 and 70%. 21 For the operation of heat recovery equipment, if the leakage rate and pressure differential are 22 reasonable, it can be operated in a particular mode while guidelines issued by China recommend 23 all rotary heat exchangers should not be installed in the HVAC system. 24 It can be observed that most suggestions in these guidelines are roughly consistent with one 26 another, except for a few conflicting details, which reflects the underlying uncertainty regarding 27 the transmission of SARS-CoV-2. 2) The specific ventilation rate that can eliminate the risk of transmission of airborne 31 particulate matter remains to be studied. The authors declare that they have no known competing financial interests or personal 2 relationships that could have appeared to influence the work reported in this paper. 3 Indoor transmission of SARS-CoV-2 Heating, ventilation and air-conditioning systems in the context of COVID Airborne route and bad use of ventilation systems as non-negligible 11 factors in SARS-CoV-2 transmission COVID-19 Outbreak Associated with Air Conditioning in Restaurant Modes of transmission of virus causing COVID-19: implications for IPC precaution 15 recommendations Estimation of the reproductive number of novel coronavirus (COVID-19) 19 and the probable outbreak size on the Diamond Princess cruise ship: A data-driven analysis Transmission of SARS-CoV-2: implications for infection prevention precautions Issues Statements on Relationship Between COVID-19 and HVAC in 3 Buildings Has Released Information on COVID-19 and Promoted International 7 Cooperation on Epidemic Prevention and Control The Architectural Society of China, All kinds of guidance The State Council of China, Guidelines for the Operation and Management of 14 Air-conditioning and Ventilation Systems in Office and Public Buildings during the New 15 The Chinese Association Of Refrigeration, Recommendations for the Safe Use of 18 Air-Conditioning (Heating) Systems in Response to the COVID-19 Epidemic Guidance for Building Operations During the COVID-19 Pandemic ASHRAE, ASHRAE Position Document on Infectious Aerosols 19 Building Readiness/Reopening Guidance Betrieb von Lüftungs-und Klimaanlagen während der 12 COVID-19-Pandemie A on Ventilation in the Control of SARS-CoV-2 Infection Operation of air-conditioning equipment and other facilities as SARS-CoV-2 The SARS Epidemic in Hong Kong: What Lessons have we Learned Medical reviews. Coronaviruses Aerosol and Surface Stability of SARS-CoV-2 as Compared with 8 SARS-CoV-1 Molecular and serological investigation of 2019-nCoV infected patients: 10 implication of multiple shedding routes Clinical characteristics of 2019 novel coronavirus infection in China Evidence of airborne transmission of the severe acute respiratory 14 syndrome virus 19 Building Readiness/Reopening Guidance How can airborne transmission of COVID-19 indoors be minimised? Environmental Control for Tuberculosis: Basic Upper-Room Ultraviolet Germicidal 21 Irradiation Guidelines for Healthcare Settings Update of the scientific evidence for specifying lower limit relative 2 humidity levels for comfort, health, and indoor environmental quality in occupied spaces 3 (RP-1630) Low indoor-air humidity in an assisted living facility is correlated with 5 increased patient illness and cognitive decline Academic Research to Support Facility Guidelines Institute & 7 Microbes at Surface-Air Interfaces: The Metabolic Harnessing of Relative 11 Bacterial pleomorphism and competition in a relative humidity 14 gradient Low ambient humidity impairs barrier function and innate resistance 16 against influenza infection Stability of SARS-CoV-2 in different environmental conditions, The 19 Frequently Asked Questions (FAQ) NASAL MUCOCILIARY TRANSPORT IN HEALTHY-SUBJECTS IS 2 SLOWER WHEN BREATHING DRY AIR Coronavirus disease (COVID-19) advice for the public: Mythbusters The Architectural Society of China, Guidance for Office Building Operations During the What does the scientific literature tell us about the ventilation-health 10 relationship in public and residential buildings? 1. Control the temperature and humidity is beneficial. But the temperature and relative humidity setpoint should be considered on a case-by-case basis.1. There is no need to adjust the temperature and humidity setpoint.1. The temperature should be controlled between 17 and 28 ℃, and the relative humidity should be controlled between 40 and 70%.Haven't mentioned. 1. The air should flow from safe areas to unsafe areas, from personal use areas to public areas.1. Ensure the negative pressure in the toilets.1. Ensure the negative pressure in the toilets. ☒ The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.☐The authors declare the following financial interests/personal relationships which may be considered as potential competing interests:J o u r n a l P r e -p r o o f