key: cord-0897741-imrs0mpj authors: Chang, Yufan; Zhang, Xiaochen; Song, Ge; Liu, Jing; Lin, Chen; Ye, Jinjun; Hu, Jie; Tang, Lei; Ai, Zhengtao title: Evaluation of airborne transmission risk in university towns based on IEQ surveys date: 2022-03-23 journal: Energy and Built Environment DOI: 10.1016/j.enbenv.2022.03.006 sha: 80e964575f521c505d0620720a344894da5c0f38 doc_id: 897741 cord_uid: imrs0mpj This study aims to evaluate airborne transmission risk in university towns during the COVID-19 pandemic based on surveys of indoor environmental quality (IEQ). Both on-site measurements and questionnaire surveys were carried out in public buildings in university towns in Changsha, China. Air temperature, relative humidity, and CO2 concentration in one library, ten classrooms, eight canteens, seven restaurants, and sixteen malls were measured. 2220 valid questionnaires concerning occupants’ sensation on thermal environment, air movement, and indoor air quality were collected. A 3-level evaluation method of airborne transmission risk that is dependent on building type and indoor CO2 concentration was developed. Excessive CO2 concentration is found in library (1045 ppm), classrooms (1151 ppm), restaurants (1242 ppm), and malls (1057 ppm). The percentage time of “high risk” accounts for 18-100% in these buildings. The results reveal a serious problem: numerous public buildings in China and probably other resource limited countries are not basically prepared and equipped to cope with airborne transmission. This fact should be taken into account when developing guidelines and formulating mitigation measures. Real-time monitoring and displaying IEQ and thus the transmission risk level should be an important way to be widely implemented in public buildings. restaurants and malls, are where students and teachers spend their majority of time. The IEQ of these public buildings is a crucial factor affecting the comfort and health of students and teachers [1, 2] . Indoor air temperature, relative humidity (RH), air speed, and indoor air quality (IAQ) are the most important parameters of IEQ. It has been reported that the public buildings in university towns are generally characterized by high occupant density. The density of students in classrooms reached 0.9 person/m 3 , and the IAQ in schools was unacceptable due to inadequate fresh air [3] . In addition, more than half of the classrooms have CO 2 levels above 1000 ppm [4, 5] . The combination of high occupant density and insufficient ventilation would put the indoor environments into a high risk of cross-infection during the outbreaks of respiratory infectious diseases. The severe acute respiratory disease COVID-19, which is caused by the virus SARS-CoV-2, broke out in early 2020 and rapidly spread over the world. To the time of submitting this paper, it has caused more than 20 million confirmed cases and 4 million deaths [6] . During January 26 -February 10 of the year 2020, a small outbreak occurred in a restaurant of Guangzhou, China, causing 10 confirmed cases. Short social distances between diners and poor ventilation were identified as the important driving forces of this outbreak [7] . Starting on February 21, a 16-day SARS-CoV-2 outbreak swept through a call center in South Korea, resulting in the infection of 94 workers. It was found that the infected area was rather concentrated, and the crowded workplaces and the heavy talking were believed to be the reason for this outbreak [8] . It is worth noting that aforementioned outbreaks happened in crowded indoor spaces with relatively poor ventilation, which is the typical characteristics of public buildings in university towns. Shen' study [9] confirmed that universities and restaurants are facing a high risk of airborne transmission. Among others, classrooms and libraries, which are intensively occupied by students, are places of high risk of exposure [10] . Colorado Department of Public Health and Environment (CDPHE) reported that school is one of the places with the highest number of confirmed cases per outbreak, where each outbreak would cause 90 cases on average. The public buildings in university towns therefore present a challenge in the mitigation of COVID-19 transmission [11] , which should be paid special attention when formulating control measures for university towns. There are three confirmed routes that play a decisive role in COVID-19 transmission: (1) fomite through surface contact, which can be effectively dealt with by appropriate surface cleaning hand hygiene; (2) droplet-borne transmission with droplets emitted during human breathing, talking, sneezing and coughing, which can be prevented by face masks and social distance; (3) air-borne transmission, through virus-laden aerosols that can suspend in the air over a long period and are capable of traveling farther than the usual social distances [12] . ASHARE and CDC have raised their concern about air-borne transmission [13, 14] . IAQ control strategies such as ventilation dilution and air cleaning are considered to be efficient solutions to reduce the risk of airborne transmission [15] [16] [17] . According to Wells-Riley equation [18, 19] , the low infection risk can be realized by increasing the ventilation rate of virus-free air. As important parameters of IEQ, indoor air temperature and RH affect the viability and the evaporation of the droplets [20] . van Doremalen et al. [21] found that the viability of SARS-CoV-2 is high in the indoor environment with air temperature of 21 -23 o C and RH of 65%. It was reported that the viability of SARS-CoV-2 is reduced from 14 days to 30 mins by rising the air temperature from 4 o C to 56 o C [22] . The average evaporation time of 12 μm droplets under 50% RH is shortened from 1.44 s to 0.42 s, with the air temperature rising from 5 o C to 35 o C [23] . RH has been proven sensitive to many air-borne viruses [24] , and an increase in RH would reduce the evaporation speed of a droplet [25] . Wang et al. [26] found 70 -80% of RH can reduce the number of infected cases. Redrow et al. [27] observed that the time a 10 μm droplet evaporating to a 3.5 μm nuclei shortened from 0.55 s to 0.25 s with RH decreased from 80% to 20%. In general, a well maintained IEQ can help to mitigate the risk of airborne transmission. Currently, vaccination has been widely implemented to mitigate the spread. However, infection and transmission of COVID-19 are still occurring, due to the rapid mutation of the SARS-CoV-2 virus. The recent Delta variant [28] is much more infectious and spreads much faster than its earlier generations, which also causes more severe symptoms and damages to human body [29] . Therefore, any mitigation measures and restrictions of the pandemic would still need to be implemented for a long time. Since the reopening of the universities worldwide, many governments and professional groups have actions in mitigating the airborne transmission risk in campus. Based on existing air handling units, ASHRAE [30] suggested that the outdoor air should be introduced as the maximum ratio without compromising the thermal comfort of indoor occupants, and dedicated outdoor air systems should be run two hours before and after the occupancy. REHVA [16] recommended that the fresh air should supplied in a ventilation rate of 8-10 L/s/person in classrooms. Taiwan ministry of education [31] suggests classroom windows and transoms should be opened to allow air to circulate, and the dust screen of the ventilation equipment should be cleaned frequently. Exhaust fans should be used as an auxiliary strategy if indoor spaces are confined. Chinese Ministry of Education also published COVID-19 prevention and control guidelines for higher education institutes in March, 2020 [32] , which suggested that educational buildings should be ventilated at least 3 times per day with each time exceeding 30 mins. If possible, windows can be continuously open to keep the air circulated and to obtain fresh air without compromising thermal comfort. In addition, before and after the serving time, the windows of canteens should be open for 30 mins for ventilation. However, it is unknown if these guidelines are actually followed in practice, to what extent the indoor IEQ is improved by following the guidelines, and how is the IEQ during the pandemic. In such regards, this study investigated five types of public buildings in university town: library, classroom, canteen, restaurant and mall. These public buildings were evaluated through on-site measurements and questionnaire surveys. The transmission risk of SARS-CoV-2 was also evaluated by the IAQ results. This study is intended to reveal the IEQ condition in public buildings in university towns, to identify problems, and to propose possible solutions for improvement, which may eventually contribute to safer universities. In this study, on-site measurements and questionnaire surveys were conducted in the public buildings in university town in Changsha (111.53° -114.15° East, 27.51° -28.41° North), which is the capital of Hunan province in China, the investigations were conducted during November and December of the year 2020, when the outdoor air temperature was mostly between 11 o C and 18 o C, and RH was between 67% and 76%. The public buildings of 1 library, 10 classrooms, 8 canteens, 7 restaurants and 16 malls were measured, of which typical results obtained in 1 library, 7 classrooms located in 3 buildings (abbreviated as CL-A to CL-G), 4 8 canteens located in 3 buildings (abbreviated as CA-A to CA-D), 4 restaurants (abbreviated as RE-A to RE-D), and 7 malls (abbreviated as Mall-A to Mall-G) were shown. The location of Changsha and these typical buildings and some of the indoor environments are shown in Fig. 1 . The ventilation strategies were different in these buildings. Mechanical ventilation systems were seldom installed in university public buildings. The university library and classrooms were installed with air-conditioners, which controlled only the indoor air temperature with circulated indoor air [33] , and fresh air was obtained via opening the doors and windows, with the open duration and frequency decided by indoor occupants. In canteens, air-conditioners were installed but not used during the measurements (that was a normal condition), and again the fresh air was introduced by natural ventilation that was determined by occupant behavior. In restaurants, the air-conditioners were in operation, and the windows were kept closed during the business hours in order to keep a warm indoor thermal environment, and the fresh air was only obtained by the shortly opened doors when customers entering the restaurants. As for malls, mechanical ventilation with mixing ventilation mode was applied. CO 2 is often used as a surrogate to evaluate indoor ventilation rate and indoor infection risk [34, 35] . During the measurements, all the sensors were placed around the geometrical center of the testing room at the height of human breathing zone. The measurements were performed at a 1-min interval. The instruments used in the measurements and their uncertainties and ranges are listed in Table 2 . Indoor relative humidity 15 -95% 25 -85% ± 3.5% < 25% or > 85% ± 5% Telaire 7001 0 -10000 ppm ± 50 ppm or ± 5% of readings in the range of 0 -2500 ppm Questionnaire surveys were conducted to investigate the occupants' response to indoor thermal and airflow sensation, and the data was collected by distributing questionnaires to the occupants in the measured buildings. The questionnaire mainly consisted of two parts: 1) anthropometric data of occupants, including gender, sex, and height; 2) occupants' sensation towards thermal environment, air speed and indoor air quality. The ASHRAE 7 -point scale (−3 cold, −2 cool, −1 slightly cool, 0 neutral, +1 slightly warm, +2 warm and +3 hot) was used to evaluate the thermal sensation vote (TSV). A 3 -point scale was adopted to evaluate airflow sensation, including "Want higher", "No change" and "Want smaller". For IAQ, a 7-point scale including -3 "Very bad", "Bad", "Slightly bad", "Neutral", "Slightly good", "Good", and "Very good" was adopted. The questionnaire is described in Table 3 . We prepared two forms of questionnaires, namely internet and paper based, for respondents to choose. For internet one, a link was created by a questionnaire platform (called questionnaire star) and sent out through social media. The results of questionnaires completed via internet were collected automatically by the platform, and those completed through paper were collected manually. The respondents were randomly selected from the studied public buildings, and they were all lived in Changsha. The questionnaires were continuously collected from October 26th to December 30th. [36] , which are air temperature ranging between 18 -24 o C and RH being above 30%. It was found that a considerable part of the points was outside the comfort zones. In library and classrooms, which were heated by air conditioners, indoor air temperature was relatively high, with an average temperature of 23.6 o C and 24.1 o C, respectively. The high indoor air temperature was mainly caused by three reasons: (a) air conditioners were controlled by occupants, and were usually adjusted to high air temperature; (b) the windows and doors were kept closed during the operation of air conditioners; and (c) the density of occupants in classrooms were high up to 0.9 person/m 3 . Noticeable differences appeared between the canteens and restaurants. Similar with library and classrooms, high air temperature and low RH were shown in the restaurants in university town, where air-conditioners or fan coil units were used for heating. The naturally ventilated canteens presented a low air temperature and high humidity environment. As for malls, the indoor air temperature depended on the condition if the mechanical ventilation was well running. The air temperature in Mall-A was as low as 10.2 o C, which was due to the low ventilation rate in the morning. In terms of the questionnaire results, the indoor thermal sensation of the studied public buildings was generally satisfied, as shown in Fig. 3 . In Fig. 2 , the air temperature in the canteens was relatively low. However, only 12.2% of respondents of canteens found the indoor thermal environment cold, and 85.3% of respondents accepted the indoor thermal environment. that diners wore typical winter clothes in canteens and ate to kept warm. It was noted that the questionnaires of malls were mostly distributed to respondents in afternoon, hence, the thermal sensation related to the morning of Mall-A was not shown. Airflow is also an important indicator that affects the thermal comfort perception of occupants [37] . The airflow results were obtained by questionnaire results. As shown in Fig. 4 , the percentage of people choosing "Want higher" and "No change" was almost the same in malls, canteens, and library, while that of people in restaurants choosing "Want higher" was lower than the "No change". As for classrooms, more than half of students (66%) chose "Want higher", indicated that the indoor air was really stagnated and students expected a higher air movement. Direct measurements of virus-laden aerosols are extremely difficult. Currently, tracer gas simulation is considered as a suitable technology to investigate airborne transmission in built environment under certain conditions [40, 41] , of which CO 2 concentration is widely used as an indicator and index [42] [43] [44] . In the public buildings of university town, the indoor CO 2 concentration is produced only by human exhalations, which is thus used as the tracer gas to evaluate SARS-CoV-2 transmission risk in this study. Some studies and guidelines have suggested limiting indoor CO 2 concentration to mitigate the transmission risk of SARS-CoV-2 in universities. Taiwan Ministry of Education [45] suggested that the indoor CO 2 concentration should be below 1000 ppm, and REHVA [16] proposed two warning grades with CO 2 concentration at 800 ppm and 1000 ppm for classrooms and restaurants. However, with multiple public buildings in university town, it is not suitable to use one single standard for all types of buildings. Peng and Jimenez [46] developed a CO 2 concentration based calculation method to evaluate indoor airborne transmission risk of SARS-CoV-2, the analytical expressions can be applied to various typical indoor environment. This calculation method is applied in this study, which is shown in Equation (1): where △ 2 * is the excessive CO 2 concentration beyond the ambient CO 2 concentration (ppm); P is the infection risk, which is associated with the excess CO 2 concentration ; D is the duration of the event (h), and its value varies with different events; N is the number of indoor occupants, , 2 is the exhalation rate of each occupant (m 3 /h), which is set according to Persily and de Jonge' study [47] ; is the SARS-CoV-2 immune rate of individual, which is equal to 0; is the probability of an individual being an infector, which is set to 0.001; E p is the SARS-CoV-2 exhalation rate of 1 infector (quanta/h), the value is various according to the physical and vocal levels [16, 46] ; m in and m ex are respectively the mask filtration efficiency for inhalation and exhalation, and their values are determined based on the condition whether or not to wear a mask and the type of mask. In this study, we assumed occupants were wearing ordinary medical mask in public buildings of university town, and the values are set based on Davies et al. [48] , except in canteens and restaurants, where m in and m ex are equal to 0; B is the breathing rate of the susceptible person (m 3 /h), which is different for varieties of activities [49] ; is the first-order overall rate constant of SARS-CoV-2, and 0 is the first-order loss rate coefficient of excess CO 2 . The detailed information of the values of the parameters in Equation (1) is presented in Table 5 . Based on the △ 2 * and the local outdoor background CO 2 concentration (that was 422 ppm during the measurement periods), a 3-level-risk classification scheme was developed, where the P (infection risk) below 0.02%, equal to 0.03%, and above 0.03% was classified as "Acceptable range", "High risk" and "Very high risk", respectively. The eventual boundaries of the indoor CO 2 concentration for different classification schemes are presented in Table 6 . The real-time monitoring of CO 2 concentrations can provide information for establishing effective ventilation strategies to reduce the spread of SARS-CoV-2 [50] . The monitor began at 8:00 a.m., which was the time the library opened, and the duration was 12 hours until the library closed. During the monitoring, the air conditioners continued operating at heating mode. The "acceptable range", "high risk" and "very high risk" are plotted in the figure. It was observed that CO 2 concentration quickly rose to 1327 ppm in the first 2 hours, and was stabled at a value until 12 p.m. When majority of students left for lunch, a 50-min break can let the CO 2 concentration drop rapidly down to level close to the outdoor concentration. The increase of CO 2 concentration occurred again in the afternoon and evening. Overall, the library was almost at "very high risk" and "high risk" conditions, except during the lunch and dinner times. remind indoor occupants to leave, provided that increasing fresh air supply is impossible. It is easy to apply these approaches in practice, not only for libraries in universities, but also for all types of public buildings investigated in this study. observed that the three recommendations were all not well followed, posting potential risk of cross-infection. Apart from these recommended officially, the following suggestions are made based on the present study. Firstly, students should leave the classrooms during the break times, so as to reduce the generation and accumulation of exhaled air. Secondly, personnel (could also be an in-class student) should be designated to manage the opening of windows and doors during classes, during break times, and after classes. If possible, the windows can be equipped with motorized window-opening valve, so that the real-time motoring can be coupled with the window-opening valve to manage the opening of windows automatically. This should be able to considerably improve the ventilation. it was also observed that natural ventilation alone cannot reduce indoor CO 2 concentration to a healthy level. In terms of duration, the percentage of "acceptable range" for three out of four canteens were lower than 15%, indicated that mechanical ventilation was required to assist natural ventilation. The restaurants in the university town were installed with air-conditioners or fan-coil units to condition the indoor air temperature. Outdoor air was introduced only through the doors that were opened from time to time. As depicted in Fig. 11 , the ventilation in these restaurants was rather poor, and the stable concentration value for RE-A reached 1309 ppm, which was much higher than the acceptable range. The monitors began at the opening time for malls at 10 a.m., and lasted for at least 4 hours. 27 The evolution of the CO 2 concentration was divided into two groups and shown in Fig. 12 and Fig. 13 . The ventilation strategy constant air volume (CAV) was used in the malls shown in Fig. 12 . The CO 2 concentrations were dramatically increased since the opening of the malls. The average steady value of CO 2 concentration in these malls was 1336 ppm, and the average time exposure to "very high risk" accounted for 94.0%. One reason for the relatively high CO 2 concentration in Mall-A, especially during the morning, was the incomplete operation of the mechanical ventilation systems, which was also supported by the measured results of air temperature, as described in section 3.1. Demand control ventilation (DCV) was used in Mall-F and Mall-G, as displayed in Fig. 13 . DCV is an energy efficient ventilation strategy based on the sense of the indoor parameters, including particularly CO 2 concentration [52, 53] . Once the concentration is higher than the set value, the ventilation rate is increased to reduce excessive CO 2 . ASHRAE and REHVA suggested that DCV should be disabled during the pandemic [16, 54] was obvious that the threshold value of CO 2 concentration was lower if the exposed duration was longer. As measured results showed that the average concentration in the malls was 1336 ppm, which means that it was relatively safe for customers to stay in the malls for less than 2 hours. Fig. 14 Relationship between the threshold value of excessive CO 2 concentration and safe exposed time. In order to reveal IEQ condition and airborne transmission risk in public buildings in the university town during the pandemic and then to provide suggestions for improvements, on-site measurements of indoor air temperature, RH, and CO 2 concentration were conducted in some public buildings in a university town in the winter 2020 in Changsha. The transmission risk was predicted using a 3-level transmission risk scheme that was developed based on indoor CO 2 concentration. In addition, questionnaire surveys on the thermal sensation, air speed, and IAQ were performed. Except for malls, the measured public buildings did not have mechanical ventilation ☒ The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper. ☐The authors declare the following financial interests/personal relationships which may be considered as potential competing interests: Yufan Chang Xiaochen Zhang Ge Song Chen Lin Jinjun Ye Jing Liu Jie Hu Lei Tang Zhengtao Ai Indoor environmental quality (IEQ) assessment of Nigerian university libraries: A pilot study Ten questions concerning occupant health in buildings during normal operations and extreme events including the COVID-19 pandemic Indoor air quality, ventilation and health symptoms in schools: an analysis of existing information Ventilation and indoor air quality in schools -Guidance report 202825 Classroom ventilation must be improved for better health and learning COVID-19 Outbreak Associated with Air Conditioning in Restaurant Coronavirus Disease Outbreak in Call Center A systematic approach to estimating the effectiveness of multi-scale IAQ strategies for reducing the risk of airborne infection of SARS-CoV-2 A probabilistic model to evaluate the effectiveness of main solutions to COVID-19 spreading in university buildings according to proximity and time-based consolidated criteria Environment, Operating behavior and corresponding performance of mechanical ventilation systems in Chinese residential buildings Aerosol and Surface Distribution of Severe Acute Respiratory Syndrome Coronavirus 2 in Hospital Wards Issues Statements on Relationship between COVID-19 and HVAC in Buildings Considerations for Restaurant and Bar Operators Optimal control of high-rise building mechanical ventilation system for achieving low risk of COVID-19 transmission and ventilative cooling 19 guidance document: How to operate HVAC and other building service systems to prevent the spread of the coronavirus (SARS-CoV-2) disease (COVID-19) in workplaces A new pin-to-plate corona discharger with clean air protection for particulate matter removal Airborne spread of measles in a suburban elementary school Airborne Contagion and Air Hygiene. An Ecological Study of Droplet Infections Experimental measurements of surgical microenvironments in two operating rooms with laminar airflow and mixing ventilation systems Aerosol and Surface Stability of SARS-CoV-2 as Compared with SARS-CoV-1 Stability of SARS-CoV-2 in different environmental conditions Modelling of evaporation of cough droplets in inhomogeneous humidity fields using the multi-component Eulerian-Lagrangian approach Environmental factors affecting the transmission of respiratory viruses Increasing temperature and relative humidity accelerates inactivation of SARS-CoV-2 on surfaces Study of SARS transmission via liquid droplets in air Feng, Modeling the evaporation and dispersion of airborne sputum droplets expelled from a human cough Outbreak of SARS-CoV-2 B.1.1.7 Lineage after Vaccination in Long-Term Care Facility What We Know About the Science How to Safely Reopen Colleges and Universities During COVID-19: Experiences From Taiwan Guidelines on COVID-19 Prevention and Control in Higher Education Institutes Ventilation of air-conditioned residential buildings: A case study in Hong Kong The ventilation problem in schools: literature review Influence of different ventilation levels on indoor air quality and energy savings: A case study of a single-family house Design code for heating ventilation and air conditioning of civil buildings Experimental study of local thermal comfort and ventilation performance for mixing, displacement and stratum ventilation in an office Ventilation for Acceptable Indoor Air Quality Indoor air quality analysis of 8 mechanically ventilated residential buildings in northeast China based on long-term monitoring Influence of pulmonary ventilation rate and breathing cycle period on the risk of cross-infection Tracer gas is a suitable surrogate of exhaled droplet nuclei for studying airborne transmission in the built environment Association of classroom ventilation with reduced illness absence: a prospective study in California elementary schools Ventilation in worker dormitories and its impact on the spread of respiratory droplets Observing and quantifying airflows in the infection control of aerosol-and airborne-transmitted diseases: an overview of approaches Guideline on severe special infectious pneumonia prevention on campus Exhaled CO2 as a COVID-19 Infection Risk Proxy for Different Indoor Environments and Activities Carbon dioxide generation rates for building occupants Testing the Efficacy of Homemade Masks: Would They Protect in an Influenza Pandemic? Quantitative assessment of the risk of airborne transmission of SARS-CoV-2 infection: Prospective and retrospective applications CO2 concentration monitoring inside educational buildings as a strategic tool to reduce the risk of Sars-CoV-2 airborne transmission COVID-19 prevention and control plan Energy efficient demand controlled ventilation in single family houses Energy-efficient ventilation with air-cleaning mode and demand control in a multi-residential building Position Document on Airborne Infectious Diseases