key: cord-0884241-58bitswb authors: Lizhen, Wang; Donglin, Zheng title: Integrated analysis of energy, indoor environment, and occupant satisfaction in green buildings using real-time monitoring data and on-site investigation date: 2020-07-23 journal: Build Environ DOI: 10.1016/j.buildenv.2020.107014 sha: 055a53eb307ef923d53964087b58ee7fbe0732ea doc_id: 884241 cord_uid: 58bitswb Recently, a growing literature pay attention to the green buildings, and most of them focuses on design, energy simulation, and post-occupancy evaluation but rarely involves the integration analysis of energy consumption, indoor environmental quality, and occupant satisfaction in the operational stage. In this paper, the authors propose a comprehensive quantitative study based on energy-environment-satisfaction (EES) and take a three-star green building in Shanghai as an example. Through the use of real-time monitoring data, the study analyses the distribution characteristics of the parameters of EES. Meanwhile, this study discusses the differences between operational energy consumption and design parameters and also quantifies the exponential relationship between per floor personnel density and building energy consumption. Moreover, combined with the user satisfaction survey, some improvements are suggested. Furthermore, the relationship between daily energy consumption and the environmental parameters of daily energy consumption, PM2.5, CO(2), temperature, relative humidity, and illumination is fitted, and the results indicate that there is a multivariate linear relationship with a correlation of 0.876. Through the sensitivity analysis, we found that the relative humidity affects 1.4 times as much as CO(2). Therefore, its control value is critical to reduce energy consumption in the operation of green buildings. Internal floor area not verified the green technical implementation effect in terms of the operational phase [5] . 7 Therefore, a comprehensive analysis of the operation of green buildings is considered 8 important. Building performance includes energy consumption, IEQ, including thermal, 9 indoor air quality, lighting and acoustics, and user satisfaction. Energy performance often 10 affects IEQ parameters [6] , and the relationship diagram between energy and IEQ is only 11 proposed. Peixian L.et al. [7] presents different post-occupancy evaluation (POE) methods, 12 which include the occupant survey, interview, walkthrough, IEQ in-site measurements, and 13 energy audit. Fowler K M.et al. [8] provide a detailed post evaluation of 22 buildings. 1 Nilashi M.et al. [9] propose a knowledge-based expert system based on the analytic hierarchy 2 process and fuzzy logic to assess the performance of green buildings. 3 Currently, research is focused on energy use, IEQ, and occupant satisfaction of green 4 buildings. Table 1 summarizes the current studies on green buildings. Certification USA 2013 144 ---------21477 Altomonte S et al [19] Mean and median 65 LEED concentration causes the dizziness and other symptoms of office workers, people will take the 5 initiative to ask for the adjustment of fresh air volume. 6 Energy Consumption. Aly M. Elharidi et al. [11] observed energy consumption increases 7 centrally serviced buildings, and also assessed the relative thermal comfort and environmental 8 conditions. Borong Lin et al. [15] found that the average EUI of mechanically conditioned buildings 9 was 23% lower than the constraint value in the Hot-Summer Cold-Winter zone. Agha-Hossein M M 10 et al. [20] compared user satisfaction in a previous building to that of current headquarters, and 11 found that users were more satisfied with their work environment in their new building than 12 previous office. John H. Scofield [23] Pei et al. [16] surveyed 10 green buildings in China, and the results revealed that CGBL buildings 18 have a higher satisfaction level than common buildings. Young S. Lee et al. [25] studied the thermal, 19 indoor air quality (IAQ), and the lighting environment in 5 typical LEED office buildings and found 20 that improved IAQ enhanced workplace performance. 21 Occupant satisfaction. Occupant satisfaction research is also crucial in assessing the performance 22 of green buildings. Some researchers have shown that green buildings improve occupant 23 satisfaction, while others have found the opposite. Stefano Schiavona [17] showed that impact 1 factors unrelated to IEQ significantly affected user satisfaction. Ruey-Lung Hwang et al. [18] 2 surveyed and compared IEQ and satisfaction of green and common buildings, and found that the 3 overall IEQ satisfaction was higher in the green buildings than in the common ones. In contrast, 4 Sergio Altomonte et al. [11] suggested the Building Research Establishment Environmental 5 Assessment Method (BREEAM) certification did not influence user satisfaction. Schiavon S and 6 Altomonte S [19] pointed out users in LEED-buildings reported the same overall building and 7 workspace satisfaction as users in non-LEED buildings. 8 The previous research literature is mainly focus on energy use, IEQ and occupant satisfaction of 9 operating performance in green buildings were separately. Several studies compared the energy use 10 index (EUI) of green buildings with non-green buildings, and benchmark and simulate energy 11 consumption. In the DSEEPB, personnel density is an important correction factor of office building 12 energy consumption. Regression models between energy use and outdoor air temperature 13 throughout the whole year can be classified into six models, namely 1P Model,2P Model, 3P 14 Model,4P Model, 5P Model [27] . In terms of indoor environment, researches focused on current 15 situation and improvement measures. Some studies also revealed green buildings had a higher 16 occupant satisfaction level than for common buildings, On the contrary, some 17 researchers hold negative attitudes. 18 However, there is no quantitative relationship between energy consumption and indoor 19 The review reference [28] started to emphasize the importance of combination analysis of energy 21 use, IEQ and occupant satisfaction and points out such problems should be the focus of future 22 Firstly, the quantitative relationship between energy use, IEQ and occupant satisfaction is very 24 complex. The quantitative impact of IEQ on energy consumption is still unknown. For green building, different building has different green technology, such as facility or system, different 1 operating schedules or modes, different energy efficiencies. Moreover, there are many influencing 2 factors, and the mutual influence is complex. The difference of users' individual needs for comfort 3 [29] and the indoor environment control level [30] will cause great fluctuation of energy 4 consumption. Secondly, energy consumption real-time data and indoor environment real-time data 5 need to be synchronous, collaborative and continuous, and to ensure the quality of data. If the 6 real-time monitoring data is interrupted, regression models and quantitative relationships are not 7 available. 8 The main aims of this paper are: (1) to comprehensive analyse energy consumption, environment, 9 satisfaction in green building; and (2) to conduct quantitative relationship between energy 10 consumption and indoor environment parameters. In this paper, an integrated analysis of 11 energy-environment-satisfaction (EES) was undertaken through detailed site investigation and IEQ 12 measurements for a green office building in Shanghai. This paper is composed of five sections. In 13 Section 2, the research framework of EES on green buildings is presented. Section 3 outlines the 14 results of the analysis of a three-star green office building in Shanghai. In Section 4, the results of 15 this paper are discussed. Finally, Section 5 provides the main conclusions. 16 2.Methodology 17 In this research, detailed investigation and analysis of the energy consumption, IEQ, and 19 occupant satisfaction was undertaken for a green office building. The research framework includes 20 three main steps: planning preparation, data collection, and data analysis [31] . See Fig. 1 for the 21 research framework. In this paper, we obtained quantitative and qualitative data through questionnaire surveys, field 4 surveys, and indoor environmental monitoring. The detailed survey information is shown in Table 5 2. 6 Green building design data were sourced from the consultant and the building owner. Energy 3 consumption data are derived from energy bill, monitoring platform and long-term monitoring of 4 the indoor environment by the researchers. User satisfaction results were obtained through the 5 researcher's questionnaire survey. 6 Building design information, such as the green measurements for energy and standards used for 8 IEQ, were obtained from the design documents. 9 Monthly electricity and gas use were recorded in energy bills. Realtime monitoring data was from the city energy consumption monitoring platform system (ECMPS) which records hourly 1 energy use. ECMPS can measure air conditioning, lighting and plug, power, and other special 2 energy consumption continuously. 3 The IEQ monitoring include five sensors for measuring five essential indoor environmental 5 parameters, such as air temperatures, relative humidity (RH), CO 2 , PM2.5, and horizontal 6 illumination level. IEQ monitors were installed in representative office zones, open office zones, at 7 0.75 m height, with a frequency of at least 10 minutes interval in summer, and winter for more than 8 one month. Instrument accuracy met the testing requirements. Meanwhile, a questionnaire survey 9 was undertaken, including a satisfaction survey of users. Table 3 shows the main real-time 10 monitoring parameters and reference standards. 11 Previous studies from the Centre for the Built Environment (CBE) database indicated that LEED 3 buildings had higher satisfaction ratings (Huizenga et al., 2003; 2005[32,33] ). A questionnaire was 4 designed based on the research literature [34] , and included basic information of users, IEQ, indoor 5 environmental concern and control, and building service performance, and was designed to align 6 with the corresponding interpretation indicators. The post-occupancy evaluation of the indoor 7 environment of the case office building was evaluated by comparing the results of the office site 8 monitoring and the user's subjective evaluation questionnaire. The survey questionnaire design is 9 shown in Table 4 . 10 For recent work in occupant satisfaction area, see for instance Han-His liang, Sergio Altamonte 11 [18, 19] ,the votes of "very dissatisfied"(-3), "dissatisfied" (-2), and "slightly dissatisfied" (-1) were 12 pooled into a single category of "uncomfortable" while those of "very satisfied" (+3), "satisfied" 13 (+2), and "slightly satisfied" (+1) into the category of "comfortable", the "seven-degree scale 14 method" was used for evaluation of IEQ and building service performance. In this study, 15 "seven-degree scale method" will be used in the evaluation of IEQ and Occupant satisfaction. 16 Approximately two-thirds of the CGBL projects were in the hot summer and cold winter zone in 3 China [35] . A detailed field survey was carried out for the CHT building in Shanghai, China. To The main functions of the CHT building include office, meeting, catering, underground parking, 1 and property management office. In initial design, the number of occupants was 2275, but the actual 2 number is only 181. The CHT building mainly uses the combination of ground source heat pump 3 and auxiliary cooling tower for cooling. The underground staff dining room, hall on the first floor, 4 report hall on the second floor and other large spaces adopt constant air volume system from the air 5 handling unit (AHU). Fan coil and fresh air system is used in office area and conference rooms. The GBES includes the application of energy-saving technologies. Reducing energy consumption 5 by adopting energy-saving technology is one of the most important concerns in the design of green 6 buildings. Electricity is the main energy source in the CHT building and is used for HVAC, lighting 7 and sucker, equipment, and others. The annual EUI distribution of this building is shown in Fig. 3 . 8 The monthly EUI for six years and the average EUI is shown in Fig. 4 . 9 According to the Standard for Energy Consumption of Buildings (SECB) in China [36] , the CHT 12 building is mechanically conditioned. The average EUI over six years is 99 kWh/(m 2 .a), and the 13 results of the comparison with energy consumption in similar buildings are shown in Table 5 . 1 3 From Table 5 , the EUI of the CHT building is 10% and 37% lower than the upper limit for the 4 Chinese standards. EUI is lower than the same type of office buildings in Shanghai Hongqiao. In 5 the CHT building, the actual operational EUI complies with the requirements of the two standards 6 and is close to the recommended value. 7 Based on the monthly EUI and outdoor air temperature from 2013 to 2018, a fitted relationship 8 can be obtained, which can be seen in Fig.5 . As shown in Fig.5 , monthly EUI increases as outdoor 9 air temperature rise in summer from June to September. However, the operation of heating system 10 from December to March, air outdoor temperatures in January and February are between 5-8 ℃ 11 and during this period the New year day holiday and Spring Festival holiday reduce monthly EUI. 12 This is also the reason why monthly EUI in Fig. 5 decreases with the decrease of temperature. On 13 this basis, the owners of the CHT building can improve energy efficiency based on the weather data. 14 The GBES requires that new green buildings should install an energy consumption sub-metering 3 monitoring platform. The results of energy consumption sub item can be seen in Table 6 . Table 6 4 shows that lighting and plug takes up 32% of the annual EUI is lower than the non-green office 5 building. In contrast, other three other energy such as HVAC, Power plant and other auxiliary 6 system energy use are higher the non-green office building. Throughout the whole year, lighting and 7 plug, power plant, other auxiliary systems take up 32%,14%, and 16% of the annual EUI is higher 8 than the non-green ones. HVAC system consumes the remaining 38% energy. 9 In the operation stage, the performance parameters of the enclosure structure have been 13 determined. The actual operation energy consumption is mainly affected by indoor environment and 14 occupant related parameters. The per capita floor area (PCFA), and IEQ parameters, such as indoor 15 temperature, RH, illumination, CO 2 concentration, and PM2.5, influence the energy consumption of 1 the building. 2 The actual number of people in the building and the relevant standards for design reference are 3 shown in Table 7 . 4 is the correction coefficient of PCFA for office buildings; T is the actual operation hours of office 14 buildings (h/a); s is the actual PCFA, which is the ratio of the building area used to the actual 15 number of personnel (m 2 /person). T s is the standard annual operation time, 2500 h/a, and S s is 16 standard PCFA, 10 m 2 / person. 17 According to formula (1) to (3), the EUI can be calculated from Table 7 . Based on the above data 18 of EUI and PCFA, we got the exponential relationship between per floor personnel density and 19 building energy consumption with the high correlation value is 0.9822. The fitted relationship is 20 shown in Fig. 6 . Office, and users of this office will frequently go out for equipment management and maintenance 6 work. Thus, air conditioning of this room is not stable. 1FIO has an RH of more than 80%. The 7 environment of the other rooms is in a comfortable range most of working time. 2FOO is above the 8 meeting room, and the IEQ is not as favourable as the similar room, 3FOO. As the 3FSO room 9 faces west and experiences occasional high temperatures due to solar radiation on summer 10 afternoons, shade curtains should be used in the afternoon. 11 Table 3 . However, there is still a certain percentage of time that the CO 2 14 concentration is above 1000 ppm, especially in 3FOO,4FFR, 1FIO rooms in the transition season 15 and in winter. In a word, in the transition season, the average CO 2 concentration in 3FOO and 4FFR 16 is 838 and 871, respectively, which is higher than other rooms. 4FFR is the front desk on the 4th floor and is located in front of the elevator lobby. A print-copy room next to the 3FOO measurement 1 point causes high CO 2 concentrations in 3FOO. In a word, the average CO 2 concentration is below 2 505 ppm in summer. 3FOO and 4FFR both have two different average values in winter. season. The average PM2.5 is lower than the standard requirement of 37.5 μg/m 3 given in Table 5 3.However, some time points in the measurement results of 4FFR and 1FIO exceed the standard 6 value. These PM2.5 are too high, caused by someone smoking. summer, and the transition season. In general, the average illuminance near the window can meet 2 the standard requirements, while the illuminance in the internal area such as 2FOO and 3FOO is 3 lower than 300 lux, so the illuminance level needs to be improved. The questionnaire was aimed at the user satisfaction related to the indoor environment parameters 2 of the building. Based on the index system, the questionnaire focused on the assessment of the 3 current performance of the building by the users in terms of the acoustic environment, light 4 environment, thermal environment, IAQ, as well as the main causes of dissatisfaction. Forty-three 5 questionnaires were distributed, completed, and collected. See Fig. 11 for the basic information of 6 the participants. 7 The seven degrees scale of -3~3 was used to evaluate satisfaction. The result of occupant 1 satisfaction for the CHT building is presented in Fig. 12 . Satisfaction rate is the proportion of the satisfaction value that is greater than 0. The statistical 8 results of IEQ satisfaction is shown in Fig. 13 . As shown in Fig. 13 , the highest satisfaction of the 9 overall indoor environment was 93%, which is higher than the other five aspects (T, RH, IAQ, 10 Illumination and Acoustic environment) due to the user's tolerance for green building . The lowest 11 satisfaction was 86%, which is consistent with the low levels of lighting measured. 12 Table 8 below presents the type of work of 1F-4F occupants. Further analysis was undertaken on 13 the satisfaction results of 1F-4F participants. The statistical results are shown in Fig. 14. As 1F 14 comprises the main property office and meeting room and has outdoor interference, the participants' 15 satisfaction with the temperature is only 0.5. The satisfaction of respondents from 2F-4F is greater 16 than 1. In general, the occupant satisfaction of 3F office area is lower than 2F and 4F. The reason is 1 that 3F has the influence of printing room and weak current room. When the indoor environmental parameters change, the building daily energy consumption (DEC) 1 will also change. For example, under cooling conditions in summer, lower indoor air temperature 2 and RH means higher energy consumption through the air conditioning system; under the same 3 conditions, with more fresh air, the CO 2 concentration is lower, and there will be higher energy 4 consumption. The higher the illumination value, the higher the energy consumption, and the smaller 5 the PM2.5, the higher the energy consumption. The author assumes that there is a relationship 6 between DEC and daily average IEQ parameters. See Table 9 for the normalization method of 7 indoor environmental parameters. Therefore, a linear equation can be formulated as follows: 8 (4) 9 Based on Eq. (5), Predicted DEC can be gained. Fig. 15 shows measured DEC and Predicted 1 DEC. It has high fitting degree and the error is within 7%. The CHT building was designed in accordance with the DSEEPB (GB 50189-2005). During the 7 design, the objectives for energy saving rate for HVAC and lighting systems were specified. The 8 actual operating energy use of the CHT building was compared with the design objectives, and the 9 results are shown in Table 10 . 10 12 Table 10 shows the total measured energy consumption is 16% higher than the initial design 13 specification. Table 6 presents the results that the measured energy use for HVAC and lighting is 6% 14 and 9% lower than the DSEEPB reference building energy-saving standard. The heating difference of the measured and the design is due to the air tightness of doors and windows, which leads to the 1 infiltration of outdoor air in winter and the excessive energy consumption of actual heating. There are many researches on sensitivity analysis in building energy analysis [43] . The sensitivity 6 analysis methods can be divided into local and global sensitivity analysis. Local sensitivity analysis 7 belongs to the class of the one-factor-at-a-time methods. Sensitivity measures are often calculated 8 when one factor is changed and all other factors are fixed. As a result, the choice of base case is 9 very important in local sensitivity analysis method. This method is easily applied to identify the key 10 variables affecting building energy use. 11 In this paper, Local sensitivity analysis of five indoor environmental factors is judged by the 12 change rate of building daily energy consumption. Combined with local sensitivity analysis, the 13 value of building daily energy consumption is calculated. Eq. (5) When considering the influence of single factors, DEC value is calculated in accordance with this 5 scenario case. Fig.16 shows the relationship between the DEC and each indoor environment 6 parameters. These three sensitivity factors (T, RH and CO 2 ) have a linear relationship with daily 7 energy consumption. The relationship between PM2.5 and daily energy consumption is 8 The sensitivity results of five indoor environmental factors to DEC are shown in Fig. 17 . The 10 sensitivity order was RH, T, illumination, PM2.5 and CO 2 concentration. The sensitivity of RH is 11 the highest, which is 1.4 times of CO 2 concentration factor. The illumination range should be 1500 to 3000 lux, according to the relationship curve between 5 the illumination and optical environment satisfaction given by the International Commission on Illumination (CIE). Domestic research [44] also shows that in non-green office buildings in 1 Shanghai, Beijing, the optimal level of illumination is 1000 to 1200 lux. In the CHT building in this 2 paper, the illumination at the height of 0.75 m was 300-600 lux, which meets the building lighting 3 design standard GB 50034-2013.However, but there was a lower satisfaction rate, and the level of 4 illumination of 2FOO and 3FOO must be improved to enhance user satisfaction. 5 In response to public health events, air conditioning must be operated by managers. Due to the 6 recent occurrence and spread of a new coronavirus in China, in the more concentrated office 7 buildings, the HVAC system operating strategy should be adapted according to the type of This paper focused on a quantitative study based on energy-environment-satisfaction, which the 16 energy consumption and environmental parameters are integrated. The main conclusions are as 17 follows: 18 (1) The study takes a three-star green building in Shanghai as an example. According to the 19 real-time monitoring data, the study analyses the distribution characteristics of parameters energy 20 consumption and environments. Then the relationship between daily energy consumption and the 21 environmental parameters of temperature, relative humidity, PM2.5, CO 2 , and illumination is fitted 22 based monitoring data, and the results indicate that there is a multivariate linear relationship with a 23 correlation of 0.876. 24 (2) Through sensitivity analysis, the sensitivity results of five indoor environmental factors to 1 DEC was RH, T, illumination, PM2.5 and CO 2 concentration. The sensitivity of RH is the highest, 2 which is 1.4 times of CO 2 concentration factor. Therefore, its control value is critical to reduce 3 energy consumption in the operation of green buildings. 4 (3) Operational energy use compared with design goal presents the results that the measured 5 energy use for HVAC and lighting is 6% and 9% lower than the DSEEPB reference building 6 energy-saving standard. The difference is due to the air tightness of doors and windows and there 7 are 2275 persons at the design, and in fact, there are only 181 persons. 8 (4) This paper quantifies the exponential relationship between per floor personnel density and 9 building energy consumption, and the high correlation value is 0.9822. Moreover, combined with 10 the user satisfaction survey, some improvements are suggested. 11 It should be emphasized that in ESS method, the relationship between DEC and IEQ should be 12 further studied. The 5 parameters have different degrees of influence on energy consumption. As a 13 next step, sensitivity analysis and weighting of the factors should be studied. Future research should 14 aim to achieve an optimal indoor environment with minimal energy consumption. 15 Beijing: Ministry of Housing and Urban Rural Development of the People's Republic of China Building Evaluation Standard. GB/T 50378-2014. Beijing: Ministry of Housing and Urban Rural Development of the People's Republic of China Beijing: Ministry of Housing and Urban Rural Development of the People's Republic of China Post-Operational Evaluation Standards for Green Buildings Beijing: Ministry of Housing and Urban Rural Development of the People's Republic of China A review of operating performance in green buildings: Energy use, indoor environmental quality and occupant satisfaction Post-occupancy evaluation: State-of-the-art analysis and state-of-the-practice review Re-assessing green building performance: a post occupancy evaluation of 22 GSA buildings A knowledge-based expert system for assessing the performance level of green buildings Analysis of indoor environment of green buildings in Chongqing area Satisfaction with indoor environmental quality in BREEAM and non-BREEAM certified office buildings Energy and indoor environmental performance of typical Egyptian offices: Survey, baseline model and uncertainties Allen, the impact of working in a green certified building on cognitive function and health Environmental Perceptions and Health before and after Relocation to a Green Building Measured energy use and indoor environment quality in green office buildings in China Comparative study on the indoor environment quality of green office buildings in China with a long-term field measurement and investigation Influence of factors unrelated to environmental quality on occupant satisfaction in LEED and non-LEED certified buildings Satisfaction of occupants toward indoor environment quality of certified green office buildings in Taiwan Occupant satisfaction in LEED and non-LEED certified buildings Post-occupancy studies of an office environment: Energy performance and occupants' satisfaction Gender differences in office occupant perception of indoor environmental quality (IEQ) Are green buildings more satisfactory and comfortable? Efficacy of LEED-certification in reducing energy consumption and greenhouse gas emission for large New York City office buildings Green occupants for green buildings: The missing link? Indoor environmental quality differences between office types in LEED-certified buildings in the US Indoor Environmental Quality Related to Occupant Satisfaction and Performance in LEED-certified Buildings Building energy performance diagnosis using energy bills and weather data A review of operating performance in green buildings: Energy use, indoor environmental quality and occupant satisfaction The underlying linkage between personal control and thermal comfort: Psychological or physical effects? Assessing Building Performance A Web-Based occupant satisfaction survey for benchmarking building quality LEED Post-occupancy evaluation: Taking responsibility for the occupants: Proceedings of Greenbuild Conference Indoor environment quality of green buildings: Case study of an LEED platinum certified factory in a warm humid tropical climate Development and technique application of green building for hot summer and cold winter climate zones in China Beijing: Ministry of Housing and Urban-Rural Development of the People's Republic of China Rational Use of Building Energy Guide for Comprehensive Building An energy saving retrofit baseline determination method for large scale building based on investigation data Investigation and analysis of operational energy consumption of green office buildings in Shanghai Measured energy use and indoor environment quality in green office buildings in China Analysis of 2018 Annual Energy Consumption Data in Shanghai Public Buildings Energy Monitoring System Beijing: Ministry of Housing and Urban-Rural Development of the People's Republic of China A review of sensitivity analysis methods in building energy analysis Study on the relationship between indoor environment quality and human comfort in public buildings The authors declared that they have no conflicts of interest to this work. We declare that we do not have any commercial or associative interest that represents a conflict of interest in connection with the work submitted