key: cord-0861133-zkmd24ei authors: Schibuola, Luigi; Tambani, Chiara title: High energy efficiency ventilation to limit COVID-19 contagion in school environments date: 2021-03-09 journal: Energy Build DOI: 10.1016/j.enbuild.2021.110882 sha: ff35e1a0e926b77c8aff987d2986c7eb410e4c47 doc_id: 861133 cord_uid: zkmd24ei This study investigates the possibility to contain COVID-19 contagion in indoor environments via increasing ventilation rates obtained through high energy efficiency systems combining thermal recovery by heat exchanger and thermodynamic recovery by heat pump. The starting point of this assessment is a procedure to evaluate in naturally ventilated environments, the current infectious risk by using measurements of indoor/outdoor CO2 concentrations to calculate actual air changes per hour. The method was applied to some typical school environments in Italy. The results indicated very infectious situations with reproduction number Ro values up to exceed 13. But, the simulations assessed an extraordinary reduction of indoor viral concentration and consequently of the infection risk by a strong mechanical ventilation. High ventilation rates make facemasks effective even with use levels (from 50%) reasonable also for pupils. This way, R0 goes down the value one. As regards energy performance, the behavior of an autonomous high efficiency air handling unit (HEAHU), to be installed in an existing naturally ventilated classroom, was simulated in the monitored days. The results highlight the ability to achieve a reduction in energy consumption between 60% and 72%. air changes per hour (h -1 ) CO 2 concentration in the beginning of interval t (ppm) mean outside CO 2 concentration during the interval t (ppm) conversion factor from viral dose in RNA copies to quanta (quanta/RNA copies) CO 2 concentration in the end of interval t (ppm) viral load concentration (RNA copies mL -1 ) primary energy (kWh) quanta emission rate (quanta/h) mean CO 2 indoor generation during the interval t (m 3 /s) high efficiency air handling unit heating ventilation air conditioning number of infectious individuals (-) indoor air quality indoor/outdoor inhalation rate (m 3 /h) infectious virus removal rate (h -1 ) final reproduction number considering the total exposure period (-) relative humidity (%) infectious risk at time t (%) quanta concentration at time t (quanta/m 3 ) time (s in eq.1 and h in eq. 3) volume of the room (m 3 ) 24 25 The disease COVID-19 caused by the virus SARS-CoV-2, is a pandemic and global emergency which has stressed, in 27 some cases overwhelmed, healthcare systems across the world. Reducing the infection transmission is a priority, even 28 because no effective pharmacological interventions or vaccine are available at this moment. Infection prevention is the 29 best approach to achieve this aim. Transmission of SARS-CoV-2 can occur by contact with infected people, through 30 infected secretions such as saliva and respiratory secretions or their respiratory droplets, which are expelled by an infected 31 person [1] [2] [3] . Respiratory droplets <5μm in diameter are more in detail called droplet nuclei or aerosols [4] . The contagion 32 by contact is possible directly by touching an infected person or indirectly by contact with surfaces previously touched 33 by infected people, or where large virus-containing droplets were spitted out [5] . However, it is acknowledged that this 34 viral infection spreads via inhalation in susceptible individuals. Therefore, the importance of viral transmission via 35 airborne droplets and in particular by aerosols has been highlighted [6, 7] . Airborne transmission is described as the 36 propagation of an infectious agent caused by spreading these droplets that remain infectious during their air suspension. 37 [4] . These aerosols can be produced in two different ways: 1) the evaporation of a number of respiratory droplets generates 38 microscopic aerosols and 2) breathing and talking generates exhaled aerosols. Therefore, a susceptible person could inhale 39 aerosols and have an infection risk if aerosols contain a sufficient virus quantity [8, 9] . Facemasks, made and worn 40 properly, can be used to protect healthy people or as source control, i.e. worn by an infected individual to prevent COVID-41 19 transmission [10, 11] . However, to wear masks for many hours can frequently cause potential headache and/or 42 breathing difficulties, development of facial skin lesion risk and irritant dermatitis or acne worsening [12] , difficulty in 43 communication and discomfort [13, 14] . Among recommended precautions, there is to avoid crowded gatherings as much 44 as possible. But there is no specific value for the number of people who could share the same space during pandemics 45 and this measure should be considered in conjunction with technical measures, like an adequate design of ventilation rates 46 [15] [16] [17] . Physical distance requirement to prevent transmission through direct contact refers to floor area per person, on 47 the other hand the ventilation rate provided and its effect are parameters to control viral concentration in the air inhaled 48 by susceptible individuals and they can guide the evaluation of safe occupancy density. fostering in order to reduce airborne transmission risk, can be provided by mechanical ventilation. In addition, mechanical 55 ventilation enables the implementation of demand controlled ventilation (DCV) systems in order to fit actual air flow rate 56 needs and consequently granting optimized health conditions. In particular CO2-based DCV systems permit a direct 57 verification of indoor air quality (IAQ) level by CO 2 sensors and consequently a precise assessment of the necessary air 58 changes, as proved in Refs. [22] [23] [24] [25] . As regards adequate indoor air changes, the school environment is of great concern. 59 In fact students spend a significant part of their school time inside classrooms characterized by an occupancy density 60 higher than the most part of other buildings, and often by inadequate ventilation rate. [26] [27] [28] . This happens especially in 61 naturally ventilated classrooms where air changes are variable and difficult to control. In fact often indoor comfort or 62 safety requirements as well as human behavior may dictate openings remain closed, particularly when outdoor climate is 63 too hot or cold. In addition, significant indoor air changes can involve a strong increment of energy consumption of 64 heating, ventilation and air conditioning (HVAC) systems. Among the various contagion mechanisms, this study is dedicated to the possibility to reduce airborne contagious by a 66 strong increment of ventilation rates. The paper deals with two problems. The first problem is the necessity to improve 67 energy recovery in ventilation systems by the introduction of solutions optimized for the new ventilation requirements 68 characterized by elevate flow rates. The aim is to remove the obstacle of an unacceptable growing of energy cost and CO 2 69 gas emissions in the atmosphere. Second problem concerns the specific, but very important issue of the intervention in 70 the existing naturally ventilated classrooms when the installation of a new centralized ventilation system is not possible. In this case an autonomous high efficiency ventilation unit is proposed. The analysis starts from the investigation of the 72 actual infectious situation in school environments with reference to COVID-19. An algorithm capable to assess the 73 average infection risk by measuring the internal CO 2 concentration is used for this aim and applied to some classrooms 74 subject of a monitoring campaign in Italian schools. The high risk levels so calculated suggest a strong increase of the air 75 changes by the introduction of mechanical ventilation in the classrooms. Consequently, the same procedure has permitted 76 to quantify the consequent benefits in terms of infectious risk reduction. But this solution can involve significant problems 77 as far as concerns energy consumption. Therefore, a ventilation system based on heat pump technology was proposed, 78 capable of achieving almost total thermodynamic recovery from the air expelled from the classrooms, transforming this 79 extraordinary ventilation increase into an opportunity. By a simulation model, the energy performance of this high 80 efficiency air handling unit (HEAHU) was assessed. The results obtained from the monitored days are here presented. In this case C i was estimated in an interval between 0.01 and 0. (2) is evident the strong influence of the values assumed for C v and C i . 154 155 (3) The infection risk R(t) is the percentage of infected in a sample of 100 susceptible subjects exposed to the contagious for Fig. 3b as a function of the capacity ratio (CR) which is the ratio of the actual capacity on the full capacity 237 that the machine is able to provide at the same levels of operating temperatures. Table 5 . Calculation procedure of the HEAHU performance Section 1 -step 1 -recovered capacity P rec If t exro > t dp = f(t i ,X i ) then h exro = f(t exro ,X i ) If t exro ≤ t dp = f(t i ,X i ) then h exro = f(t exro ,RH = 100%) efficiency (eq. 5) which permits to calculate the outlet temperatures from the recuperator. If this outlet temperature of the 251 exhaust air is higher than its dew point, it means there is no condensation and its absolute humidity is the same of the 252 return air. Instead, if this outlet temperature is lower than dew point, there is condensation and RH is 100%. In both the 253 cases, the total heat recovery is calculated by the enthalpy gap of the exhaust air in the recuperator (eq. 10). The second 254 step is the calculation of the heat pump circuit performance. The output capacity P is the load quota not covered by the 255 heat recovery and P fl is calculated by CF from Fig. 3a where P fl nom is the nominal capacity of the heat pump at 7°C and 256 RH 90%. Consequently, CR is the ratio P/P fl . The actual COP is obtained by multiplying the COP fl from fig. 3a by the 257 PLF calculated according to CR (Fig. 3b) . The electricity consumption of the compressor results from the ratio of the 258 output capacity on the simultaneous COP. In the third step the total heating capacity provided by the unit P tot is calculated 259 as the sum of the recovered heat P rec and the capacity P of the heat pump. The corresponding total electric absorption P el 260 is the sum of fan consumption and compressor input power. Finally, the TPF in the time step is the ratio of P tot on P el . The 261 average TPF on a monitored period is the ratio of the heating energy provided and the total electric absorption in the same The consequent R 0 are reported for classrooms 2F and 1A in Fig.7 . The coupling of high ventilation rates with acceptable 345 filtration efficiencies permits to drastically reduce R o even under 1 which is considered a safe limit to stop the outbreak. In detail, with an average filtration efficiency of 50%, R o is 0.9 by 32 l/s/pers. With 75% filtration efficiency R o goes 347 under 1 from 16 /l/s/pers, reaching 0.45 with 32 l/s/pers. The application of this approach was simulated in the monitored 348 cases. First of all, Fig.8 shows final R 0 calculated from the monitored data for the six days analysed and therefore with 349 the real natural ventilation, considering or not filtration presence. These R 0 are dramatically high values. Without 350 filtration, R 0 is in the range between 8.0 and 13.1. But even the filtration is able to reduce R 0 under one only with a 95% 351 average level which is practically unrealizable in a classroom. Fig. 8 also reports the percentage reductions of these 352 monitored R 0 obtained by the introduction of high mechanical ventilation. These reductions always exceed 28% coming 353 to touch 90% in some cases and they are mostly greater than 50%. The considerations from Fig.7 Subject: Conflict of interest statement about the submission of the paper "High energy efficiency ventilation to contrast COVID-19 contagion in school environments" 574 575 576 We wish to confirm that there are no known conflicts of interest associated with this publication and 577 there has been no significant financial support for this work that could have influenced its outcome. 578 579 We confirm that the manuscript has been read and approved by all named authors and that there are 580 no other persons who satisfied the criteria for authorship but are not listed. We further confirm that 581 the order of authors listed in the manuscript has been approved by all of us. 582 583 We confirm that we have given due consideration to the protection of intellectual property associated 584 with this work and that there are no impediments to publication, including the timing of publication, 585 with respect to intellectual property. In so doing we confirm that we have followed the regulations of 586 our institutions concerning intellectual property. 587 588 We understand that the Corresponding Author is the sole contact for the Editorial process (including 589 Editorial Manager and direct communications with the office). He is responsible for communicating 590 with the other authors about progress, submissions of revisions and final approval of proofs. We 591 confirm that we have provided a current, correct email address which is accessible by the 592 Corresponding Author and which has been configured to accept email from the Editor. First known person-to-person transmission of severe acute 398 respiratory syndrome coronavirus 2 (SARS-CoV-2) in the USA Community 401 transmission of severe acute respiratory syndrome Coronavirus 2 A familial cluster of pneumonia associated with the 2019 novel coronavirus indicating person-to-406 person transmission: a study of a family cluster Infection prevention and control of epidemic-and pandemic-prone acute 409 respiratory infections in health care Droplet fate in indoor environments, or can we prevent the spread of infection? Airborne transmission of SARS-CoV-2: The world should face the reality Is the coronavirus airborne? Experts can't agree Respiratory virus RNA is detectable in airborne and 417 droplet particles The Infectious Nature of Patient-420 Effectiveness of surgical masks against influenza 422 bioaerosols Advice on the use of masks in the context of COVID-19 Surgical mask contact dermatitis and epidemiology of contact dermatitis in healthcare workers Inconveniences due to the 427 use of face masks during the COVID-19 pandemic: a survey study of 876 young people Physical distancing, face masks, and eye 434 protection to prevent person-to-person transmission of SARS-CoV-2 and COVID-19: a systematic review and 435 meta-analysis World Health Organization, Considerations for public health and social measures in the workplace in the context 437 of COVID-19 World Health Organization, Considerations in adjusting public health and social measures in the context of 439 COVID-19, World Heal World Health Organization WHO , Key planning recommendations for Mass Gatherings in the context of the 441 current COVID-19 outbreak Measurement of ventilation and airborne 443 infection risk in large naturally ventilated hospital wards Airflow analysis of Pyeongtaek St Mary's Hospital during 446 hospitalization of the first Middle East respiratory syndrome patient in Korea Evidence of respiratory syncytial 449 virus spread by aerosol time to revisit infection control strategies? Healthcare 453 personnel exposure in an emergency department during influenza season Literature review on CO2-based demand-controlled ventilation Application of CO2-based demand-controlled ventilation using ASHRAE 458 Standard 62: optimizing energy use and ventilation CO2 based ventilation control in energy retrofit: An experimental 460 assessment Performance optimization of a demand controlled ventilation system by 462 long term monitoring Natural Ventilation Level Assessment in a School Building by CO2 Concentration Measures Indoor environmental quality classification of school environments by monitoring PM 466 and CO2 concentration levels Experimental investigation of the air flow and indoor carbon dioxide 469 concentration in classrooms with intermittent natural ventilation Natural Ventilation Level Assessment in a School Building by CO2 Concentration Measures A review of CO2 measurement procedures in ventilation research Indoor environmental quality of classrooms in Southern European climate CO2 concentration in naturally ventilated 478 classrooms located in different climates-Measurements and simulations Control of CO2 in a naturally ventilated classroom Carbon dioxide generation rates for building occupants, Indoor Air Size distribution and sites of origin of droplets expelled from the human respiratory tract during 486 expiratory activities SARS-CoV-2 viral load in sputum correlates with risk of 488 COVID-19 progression Viral load of SARS-CoV-2 in clinical samples Aerosol and surface stability 493 of SARS-CoV-2 as compared with SARS-CoV-1 Development of a dose-response model for SARS 496 coronavirus Measurement of breathing rate and volume in routinely performed daily activities Physical Education Department Estimation of airborne viral emission: Quanta emission rate of SARS-501 CoV-2 for infection risk assessment Dynamics of Airborne influenza A viruses indoors and dependence on humidity Assessment of the impact of particulate dry deposition on soiling of indoor 505 cultural heritage objects found in churches and museums/libraries Airborne spread of measles in a suburban elementary school Using a Mathematical Model to Evaluate the Efficacy of TB Control Measures Review and comparison between the Wells-Riley and dose-response approaches to 512 risk assessment of infectious respiratory diseases Heat recovery units with cooling circuit: selection, use, installation and maintenance manual, 515 technical bulletin 0313 Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and 517 process chillers Modelling of HVAC system components for building dynamic simulation Simplified models to simulate part load performances of air 521 conditioning equipments ASHRAE STANDARD 62.1 Ventilation for Acceptable Indoor Air Quality, Health Care (Don Simple respiratory protection -Evaluation of the filtration performance 525 of cloth masks and common fabric materials against 20-1000 nm size particles Standard Specification for Performance of Materials Used in Medical Face Masks Respiratory protective devices -Filtering half masks to protect against particles National Institute for Occupational Safety and Health (NIOSH), Guide to the Selection and Use of Particulate 534 Department of Health and Human Services A modelling framework to assess the likely 537 effectiveness of facemasks in combination with 'lock-down' in managing the covid-19 pandemic ASHRAE Position 540 Document on Infectious Aerosols EN 16798-1, Indoor environmental input parameters for design and assessment of energy performance of 542 buildings-addressing indoor air quality, thermal environment, lighting and acoustics Ventilation for buildings -Part 3: For non-residential buildings -Performance requirements for 544 ventilation and room conditioning systems UNI/TS 11300:2, Energy Performance of Buildings, Technical Specification, Italian standard 2020 551 Subject: CRediT author statement about the submission of the paper "High energy efficiency ventilation to limit COVID-19 contagion in school environments