key: cord-0841584-e6ke9fef authors: Srivastava, Shubham; Zhao, Xingwang; Manay, Ati; Chen, Qingyan title: Effective ventilation and air disinfection system for reducing coronavirus disease 2019 (COVID-19) infection risk in office buildings date: 2021-09-29 journal: Sustain Cities Soc DOI: 10.1016/j.scs.2021.103408 sha: 2f7e2a82d88b751aaa29ff204842c795973f024f doc_id: 841584 cord_uid: e6ke9fef During the COVID-19 pandemic, an increasing amount of evidence has suggested that the virus can be transmitted through the air inside buildings. The ventilation system used to create the indoor environment would facilitate the transmission of the airborne infectious diseases. However, the existing ventilation systems in most buildings cannot supply sufficient clean outdoor air for diluting the virus concentration. To reduce the airborne infection risk and minimize energy consumption, especially in existing buildings with well-mixed ventilation systems, this investigation used an ultraviolet-C (UV-C) air disinfection device (Rheem's third generation products, RM3) with 99.9% disinfection efficiency to clean air carrying the COVID-19 virus (severe acute respiratory syndrome coronavirus 2, SARS-CoV-2) which could help promote environmental sustainability and create healthy cities. This investigation assessed the impact of the RM3 UV-C units on the infection risk, the number of RM3 UV-C units required, and the strategy for decreasing the infection risk, with the use of computational-fluid-dynamics (CFD) numerical simulations. An actual office building with a combination of individual offices and workstations was selected as an example for the research. According to the numerical results, the best strategy would be to use a combination of 100% outside air and UV-C in heating, ventilation and air-conditioning (HVAC) ducts with air disinfected by the RM3 UV-C units. The infection risk in the office building could thus be reduced to a negligible level. These findings could provide theoretical basis and engineering application basis for COVID-19 epidemic prevention and control. Since the outbreak of COVID-19 in 2019, more and more evidence has suggested that the virus can be transmitted through the air from a sick patient and that the virus in small aerosol droplets can survive in the air for hours (Doremalen et al., 2020; Liu et al., 2020; Morawska and Cao, 2020) . Some studies have also indicated that the ventilation systems (Ding et al., 2020; Pei et al., 2021) used to create the indoor environment in buildings would affect the transmission of airborne infectious diseases (Blocken et al., 2021; Li et al., 2007) . For example, in a Dutch nursing home, 17 out of 21 residents and 13 out of 34 healthcare workers wearing surgical masks in the same ward were infected. In addition, to save energy, this ward was ventilated using recirculated air without filtration when the CO 2 concentration was lower than 1000 ppm. However, the occupants of six other wards ventilated by outside air in the same facility were not infected. The researchers' findings indicated that the airborne transmission (Crema, 2021; Rahmani, 2020; Yao et al., 2020) resulted from an inadequate supply of outside air (Man et al., 2020) . The outside air supply rate to offices, conference rooms, shops, libraries, restaurants, etc., was much lower than that in hospitals, and thus the infection probability in those spaces would be higher. The epidemiologic analysis, experimental measurements, and simulation results from Li et al. (2021) indicate the high probability of airborne transmission in a poorly ventilated and crowded restaurant. Moreover, people spend more than 87% of their daily lives inside buildings (Klepeis et al., 2001) . It is particularly important to improve air quality indoors (Agarwal et al., 2021; Cao et al. 2020) and reduce indoor exposure to airborne infectious diseases (Kenyon et al., 1996; Moser et al. 5 1979; Olsen et al. 2003) in the existing buildings. To improve indoor air quality during the COVID-19 pandemic, the most common recommendation has been to supply sufficient outdoor air to minimize the infection risk of COVID-19 in buildings (ASHRAE, 2020; CDC, 2020 ; European Centre for Disease Prevention and Control, 2020) . More fresh air needs extra energy to handle outdoor air, such as heating, cooling and (de)humidifying. However, not all the ventilation systems in buildings can handle the heating and cooling load with 100% outside air. There are no ventilation standards for the amount of outdoor air required in buildings for the control of SARS-CoV-2 infection (ASHRAE Standard, 2019) . Other studies Rahmani et al., 2021; Xu et al., 2020) have proposed intermittent occupancy with ventilation (Melikov et al. 2020 ), a decrease in occupancy density , or a reduction of working hours . All these measures could help in principle, but they are not permanent solutions. The purpose of the present investigation was to provide a simple and energy saving method for reducing the SARS-CoV-2 infection risk with minimal changes to existing ventilation systems, so as to create a healthy indoor environment and enable people to return to work. One promising technique is the use of local air cleaning systems (Morawska and Milton, 2020) in combination with ventilation. Therefore, this investigation aims to using an ultraviolet-C (UV-C) disinfection device to clean air carrying SARS-CoV-2. To assess the virus airborne transmission mechanism and the performance of the device, this study calculated the infection risk with the spatial distribution of SARS-CoV-2 in a large office building. To investigate the infection risk of SARS-CoV-2 in a large office building and the performance of the disinfection device, this study would firstly validate the numerical simulation method with experimental data. Then the validated simulation method was used to solve N-S equation for the flow field and Eulerian method was used to predict the spatial distribution of the SARS-CoV-2 virus concentration. With the SARS-CoV-2 virus concentration, this investigation further adopted the Wells-Riley equation to evaluate the spatial distribution of the infection risk and explore the effect of air disinfection device on reducing the probability of infection. The investigation used computational fluid dynamics (CFD) to calculate the spatial distributions of airflow , air temperature, and SARS-CoV-2 concentration (Ren and Cao, 2020; in an office building. Accurate prediction of indoor airflow distribution is essential for studying the spatial distribution and transmission of airborne infectious diseases. The indoor air distribution in this study was predicted by CFD solving the Reynolds-averaged Navier-Stokes (RANS) equations closed with the renormalization group (RNG) k-ε model (Choudhury, 1993 ). This turbulence model has the best perforpance among many evaluated in the literature (Chen, 1995; for airflow in the indoor environment. To predict the spatial distribution of SARS-CoV-2 in a large office building, both Euler's method Liu et al., 2021; You et al., 2019; and Lagrangian method with CFD are widely used. However, Lagrangian method may not be easy 7 to achieve a stable solution for different factors, such as the number of the released virus, uncertainty, and random factors . So, this investigation used the Eulerian method for the further study. The Eulerian method treats the particle (droplet or virus) phase as a continuum phase and solves the spatial distribution of SARS-CoV-2 virus by solving the following scalar transport equation: where Φ is the SARS-CoV-2 quanta concentration, t is time, x i and x j are coordinates in the i and j directions, respectively, ρ is air density, U i is air velocity, Γ Φ is the diffusion coefficient, and S Φ is the quantum generated by an index patient. Here "quanta" are the hypothetical infectious dose units proposed by Wells (1955) and used to signify the strength of the infection produced by an infected patient. The quanta are usually back-determined from the outbreak cases. This investigation used ANSYS 2019R3 Fluent, a widely used commercial CFD program, to predict indoor air distributions (Cao, 2018; Feng et al. 2019 ) and quanta concentration. Since it is commercial software, the source code cannot be modified directly. User defined function (UDF) always needs to be written by users according to requirements and connected with the software through the interface provided by the software. For solving Eq. (1), this study ignored the Brownian diffusivity and adopted the homogeneous assumption which assume the Stokes number of a particle equal zero. The turbulent Schmidt number was 8 set at 1.0 (You et al., 2019) . All the above assumptions were used in previous studies Liu et al., 2021; You et al., 2019; . This study first employed the finite volume method to discretize the RANS equations closed with the RNG k-ε model and Eq. (1), and then solved the discretized equations with the SIMPLE algorithm (Patankar and Spalding, 1972) . To simulate the buoyancy effect, Boussinesq approximation (Boussinesq, 1903 ) was adopted in this investigation. All the CFD simulations were conducted on a computer cluster with 128 processor cores (processor base frequency: 2.0 GHz) and 256 GB of memory. To assess the quantitative infection risk, the spatial distribution of SARS-CoV-2 quanta calculated by CFD was used in the Wells-Riley equation and the dose-response model (To and Chao, 2009 where I represents the number of index patients; q the quanta produced by each patient (h -1 ); p the pulmonary ventilation rate of each susceptible person (m 3 /h), in a seated position or doing light activity, p = 0.3 m 3 /h; t 1 the duration of exposure (h); and Q the ventilation rate of clean air supplied to the room (m 3 /h). The quanta range for COVID-19 estimated by Dai and Zhao (2020) was 14-48 h -1 , and this investigation used the median value of 31 h -1 . This study assumed that each susceptible person was exposed for 8 hours in an office and that the office space had four infected occupants. To solve the individual infection risk probability for each person, this study needed to determine the local average quanta concentration Φ k,θ in the breathing zone θ of person k. Based on the CFD simulation results, this investigation calculated the local average quanta concentration Φ k,θ by means of Eq. (4). The breathing zone θ was assumed to be a spherical space centered at the nose of each person, with a radius of 0.2 m which was determined according to Shi et al. (2019) study. where Φ k,ii and Vol k,ii are the quanta concentration and volume of cell ii in the breathing zone θ, respectively; and m is the total number of cells in the breathing zone. With the average quanta concentration in each susceptible person's breathing zone, this investigation then estimated the infection risk for each susceptible person P k through the following equation: An effective method for reducing the infection risk for each susceptible person is to increase the number of air changes per hour (ACH) in an indoor space. However, this approach causes a steep rise in HVAC operating costs. The same objective can be achieved by installing localized air disinfection devices. The localized air-cleaning techniques include air purifiers with fibrous filter, electrostatic removal system (Mo et al., 2020) , UV system, etc. HEPA filters are commonly used for particles filtration (Ding et al. 2020 The UVGI light in this investigation employed the short-wavelength UV-C range, from 100 to 280 nm, as the principal mode for disinfecting from the SARS-CoV-2 virus. It works by permanently destroying the DNA structure of the pathogens, rendering them non-virulent. Fortunately, the SARS-CoV-2 has been found to be particularly susceptible to radiation in this range (Narita et al., 2020) . Note that, UV-C light, although being fatal to microorganisms, does not pose significant health risks to humans (Buonanno et al. 2017 ). The aim of using the RM3 UV-C unit was to kill 99.9% of the viruses (kill efficiency η = 99.9%) with the UVGI light. To achieve a given kill efficiency, the required UV irradiance I can be determined from First et al. (1999) : where N s represents the number of virus particles that survived the RM3 UV-C unit; N o the number of virus particles exposed; K the UV-C inactivation rate constant (cm 2 /μW·s); I the UV irradiance (μW/cm 2 ); and τ the exposure time (s). Buonanno et al. (2020) thought that all coronaviruses would respond similarly to the UV-C light, and thus the inactivation rate constant K for SARS-CoV-2 could refer to the K of human coronavirus 229E (HCoV-229E) or human coronavirus OC43 (HCoV-OC43). The RM3 UV-C air disinfection unit, shown in Fig. 1(a) , draws in the surrounding air at the base and discharges treated air at the top. The height of RM3 UV-C unit is 2.29 m (7.5 ft) and the diameter of the main body is 0.2 m (8 inch). It can handle 200 CFM of air with the kill efficacy of 99.9%. Fig. 1(b) depicts the simplified RM3 UV-C unit model used for the CFD simulation. Fig. 1(c) illustrates the operation of an RM3 unit when integrated with the ventilation system in an office. The unit designed in such a way has two main advantages. One is that the unit works on the principle of a unidirectional downward flow as shown in Fig. 1(b) , thus it can exert a downward push on the microdroplets to force them to drop to the floor before landing on surfaces or being inhaled by occupants. Another one is that it can prevents stirring up of microdroplets that have dropped to the floor level. Compared with the displacement ventilation system (Kong et al., 2021) with higher contamination discharge efficiency, the RM3 UV-C air disinfection unit design is most effective in a well-mixed ventilation configuration. Since the shortwave UV-C in the RM3 unit can effectively eradicate the pathogens in the return air, it can inhibit the transmission of airborne diseases to occupants in close proximity in the office space. Thus, the 6-feet social distancing rule (Feng et al., 2020) could be reduced in indoor environments. This section describes our validation of the CFD simulation results and our use of the CFD tool to study the performance of ventilation systems and RM3 UV-C units in buildings. This investigation validated the CFD simulations by comparing the numerical results with measured data from Srebric and Chen (2002) , where flow characteristics were typical for office buildings. The experiment was conducted in a full-scale environmental chamber, as 14 shown in Fig. 2 conditions. Other detailed geometry information is available from Srebric and Chen (2002) . In this investigation, the environmental chamber model was discretized by about 4.3 million non-uniform triangular pyramid cells, with which this study achieved grid-independent results. Three black lines in Fig. 2 represent the measurement locations. Most office buildings in the United States use conventional well-mixed ventilation systems, which dilute contaminated air with supply air to achieve an acceptable, uniform contaminant concentration. Many offices use recirculated air that is filtered by conventional, low-grade filters (primary filters) and these primary filters mainly for filtration particles above 5 μm. Such filters have close to 0% filtration efficiency for the SARS-CoV-2 virus which is usually less than 5 μm. The problem could be remedied with the use of auxiliary air disinfection devices. This study used RM3 units together with a mixing ventilation system for a one-floor building with a combination of individual offices and workstations as shown in Fig. 4(a) . The dimensions of each office were 47.2 m × 14.3 m × 5.6 m. The doors to the individual 17 offices were closed, and a 3 cm gap between the floor and the lower door frame allowed air exchange between the individual offices and the larger space with workstations. This study used actual information measured at diffusers as inputs. The flow rate of outdoor air through the ventilation system was 946 m 3 /h or 0.46 ACH, which accounted for only 10% of the total ventilation rate (9460 m 3 /h). The remaining 90% was recirculated air. As depicted in Fig. 4(b) , the office had a total of 59 occupants, and the 4 occupants shown in red were assumed to be COVID-19 patients. The viruses were released through the patients' mouth, as shown in Fig To evaluate the performance of the RM3 UV-C units and assess whether the existing ventilation system provided sufficient outdoor air, this study used the existing system without RM3 units as the reference case (or Case A in Table 1 The average infection risk probability and quanta concentration calculated by Eqs. (2) and (3) for Case A were 26.99% and 0.13 per m 3 , respectively, for an eight-hour stay in the office. The black histograms in Fig. 6 -6, 9, 26, 27, 38, 39, 40 , and 42 had a higher infection probability than others, because these people were in close proximity to infected occupants 8, 23, and 43. With the higher outdoor air ventilation rate in Case B, the average infection risk was sharply reduced to only 3.10% for an 8-hour stay. The corresponding average quanta concentration for Case B was 0.013 per m 3 . Note that, since the difference between Case B and Case A is the outdoor air ratio, the flow field of Case B is exactly the same as that of Case A as shown in Fig. 7(c) . The blue histograms in Fig. 6 indicate the infection risk for each susceptible person. Among the occupants of the individual offices (31, 32, 48-56, 58, 59) , the infection risk for the majority (48-56, 58, 59) was reduced to almost 0%. The infection risk for occupants 31 and 32 was 1.58% and 1.50%, respectively, because their offices did not have any air supply diffusers or outlets, and the indoor air could be exchanged only through the gap between the floor and the door frame. Meanwhile, Fig. 8 (2.23%) was smaller than P B (3.10%), which occurred because the amount of outdoor air (9460 m 3 /h) used in Case B was smaller than the amount of equivalent clean air (946 + 12221 = 13,167 m 3 /h) used in Case C. Note that the infection risk difference among the susceptible occupants, as depicted by the red histograms in Fig. 6 , was much smaller than that in Case B, because the RM3 UV-C units were almost evenly distributed in the building. The distribution of quanta concentration, infection risk, air velocity in Case C is displayed in Fig. 9 . A comparison of Figs. 7 and 9 indicates that RM3 UV-C units can decrease the quanta concentration and infection risk obviously. Note that, with higher amount of recirculation air, the air velocity as shown in Fig. 9 (c) is higher than Fig. 7(c) . Ideally, buildings with an infection risk of lower than 2% (Sun and Zhai, 2020) would be a better indoor environment for people to return to the workplace during the epidemic. Cases B and C were still above the threshold. Therefore, this investigation used 100% outdoor air and 36 27 RM3 UV-C units simultaneously in Case D. This effort reduced the average infection risk probability and quanta concentration in the office to be only 1.36% and 0.00575 per m 3 , respectively. The infection risk for each susceptible person in Case D is depicted by the green histograms in Fig. 6 . Although the distribution of the RM3 UV-C units was fairly uniform, occupants benefited differently due to the non-even distribution of the air supply diffusers, local air patterns, and proximity to the index patients. Fig. 10 shows the quanta concentration and infection risk distribution in the breathing zone. This figure also clearly demonstrates that the occupants located near the index patients were exposed to a high quanta concentration and infection risk. The use of 100% outdoor air would significantly increase the energy costs for air handling and employing RM3 UV-C units could be preferrable. In Case C, where the infection probability was close to 2%, additional RM3 units could be used to reduce the probability below 2% while still using minimal outdoor air as in the current design. Since the office building was very large, the use of a model with realistic human geometry for the occupants would have dramatically increased the number of computer cells required. Therefore, this investigation used a rectangular column to represent an occupant. Cheng and Lin (2016) studied different geometries for the human body and found the simplified rectangular model to be satisfactory. The quanta value provided by Dai and Zhao (2020) was based on previous data. As the COVID-19 epidemic continues, future studies can assess the infection risk based on the latest quanta value using the same method. RM3 UV-C units developed in this study only handle the indoor air using the UVGI light and then send back into the room. Since the RM3 UV-C units do not need extra energy to heat, cool or (de)humidify the indoor air (Sha et al. 2021) , it can achieve lowers investment and operational costs. The RM3 UV-C units as shown in Fig. (1) draws the air from the bottom and discharges the treated air from the top. However, it would be worse for the indoor comfort and indoor air quality when the treated air discharged from the bottom. That was because it may raise the settled virus again which would pollute the air in the breathing zone and cause draft sensation. Since it is too difficult to conduct the experiment using the SARS-CoV-2 virus, this investigation did not directly measure the kill efficiency of RM3 UV-C units by experiment but designed the RM3 UV-C units according to the research results of Narita et al. (2020) and the calculation formula as shown in Eq. (6) from First et al. (1999) . The proposed RM3 UV-C unit was designed with a 99.9% kill efficiency by the utilizing optimum powered UV-C lights 30 in the assembly. In addition, the effectiveness of RM3 is mostly affected by the air filter, the filter may get clogged up and lesser air would be drawn in after prolonged use. It will certainly lower the effectiveness of the RM3 UV-C units, so it is necessary to clean the filter regularly. The methodology used to evaluate the infection risk in the office building was based on the steady state assumption, however, unsteady boundary conditions and the movement of the occupants would form unsteady flow filed which may further affect the transmission of the SARS-CoV-2 virus. Future study would explore the transmission of the SARS-CoV-2 virus under the unsteady state. In this study, four infected persons were evenly and randomly distributed to study the probability of infection. For real cases, the locations of the infected people need to be determined according to the actual situation. This investigation added one more case, Rheem office with 49 occupants, as shown in (2) based on the requirements. In addition, the locations of RM3 UV-C units were randomly and evenly distributed in this investigation which may not be the optimal locations. Future study would adopt the inverse design method Zhao et al., 2021) to identify the optimal locations of the RM3 UV-C units. The communication mechanism of COVID-19 includes air transmission, contact transmission and droplet propagation. This study only explores the probability of airborne infection. Future study will investigate the deposition of virus on the surface, the risk of contact infection and droplet transmission. Based on the above results and findings, this study would suggest that the enclosed indoor environment install air purification device or supply enough fresh air to create a healthy indoor environment and people wear surgical or N95 mask in the office to reduce the infection risk. The simulation assumed that the efficiency of RM3 UV-C units is 99.9%, but its efficiency may decrease with the increase of service time. Therefore, the influence of this factor should be considered in practical application. This investigation used CFD simulations and the Wells-Riley equation to assess the infection risk for susceptible people in a large office building that consisted of individual offices and a workstation area. The study compared four different ventilation/disinfection strategies: (1) with 90% recirculated air in the ventilation system, (2) with 100% outdoor air, (3) with 90% recirculated air and thirty-six RM3 UV-C units, and (4)  UV-C units are highly recommended due to the minimal changes to existing ventilation systems and the minimal energy cost increase. For example, bringing the infection risk in the office below 2% which is the suggested targeted infection probability in Sun and Zhai's (2020) study would require a combination of 100% outside air and the use of the RM3 UV-C units. An alternative would be the use of more RM3 UV-C units with only 10% outside air to achieve the energy saving.  The infection risk in well-mixed indoor environment directly depends on the amount of clean air (outside air or the treated indoor air). Indoor air quality 37 improvement in COVID-19 pandemic American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Ventilation for Acceptable Indoor Air Quality Fluent 12.1 Documentation ASHRAE 2020. ASHRAE Issues Statements on Relationship between COVID-19 and HVAC in Buildings Ventilation and air cleaning to limit aerosol concentrations in a gym during the COVID-19 pandemic Theorie Analytique de la Chaleur Germicidal efficacy and mammalian skin safety of 222-nm UV light Far-UVC light (222 nm) efficiently and safely inactivates airborne human coronaviruses Challenges of using CFD simulation for the design and online control of ventilation systems Heating, ventilating and air conditioning system and environmental control for wellbeing Evaluation of an ultraviolet C (UVC) light-emitting device for disinfection of high touch surfaces in hospital critical areas CoV-2 & Potential Airborne Transmission Application of polyhedral meshing strategy in indoor environment simulation: Model accuracy and computing time Comparison of different k-ε models for indoor air flow computations Experimental investigation into the interaction between the human body and room airflow and its effect on thermal comfort under stratum ventilation Introduction to the Renormalization Group Method and Turbulence Modeling, Canonsburg, Fluent Inc The SARS-COV-2 outbreak around the Amazon rainforest: The relevance of the airborne transmission Association of the infection probability of COVID-19 with ventilation rates in confined spaces HVAC systems for environmental control to minimize the COVID-19 infection Aerosol and surface stability of SARS-CoV-2 as compared with SARS-CoV-1 European Centre for Disease Prevention and Control, Heating, Ventilation and Air-Conditioning Systems in the Context of COVID-19 Influence of wind and relative humidity on the social distancing effectiveness to prevent covid-19 airborne transmission: A numerical study Removal of SARS-CoV-2 using UV+Filter in built environment Indoor airborne disinfection with electrostatic disinfector (ESD): numerical simulations of ESD performance and reduction of computing time Fast prediction for indoor environment: Models assessment. Indoor and Built Environment Guidelines for the application of upper-room ultraviolet germicidal irradiation for preventing transmission of airborne contagion-part II: Design and operation guide Assessing and controlling infection risk with Wells-Riley model and spatial flow impact factor (SFIF) Susceptibility of SARS-CoV-2 to UV irradiation Transmission of multidrug-resistant Mycobacterium tuberculosis during a long airplane flight Experimental study on the control effect of different ventilation systems on fine particles in a simulated hospital The National Human Activity Pattern Survey (NHAPS): A resource for assessing exposure to environmental pollutants Role of ventilation in airborne transmission of infectious agents in the built environment-A multidisciplinary systematic review Probable airborne transmission of SARSs-CoV-2 in a poorly ventilated restaurant Aerodynamic analysis of SARS-CoV-2 in two Wuhan hospitals Outbreak of Coronavirus disease 2019 (COVID-19) in a nursing home associated with aerosol transmission as a result of inadequate ventilation Intermittent occupancy combined with ventilation: An efficient strategy for the reduction of airborne transmission indoors New electrostatic precipitator with dielectric coatings to efficiently and safely remove sub-micro particles in the building environment Airborne transmission of SARS-CoV-2: The world should face the reality It is time to address airborne transmission of coronavirus disease 2019 (COVID-19) An outbreak of influenza aboard a commercial airliner Inactivation 42 of bacterial and fungal spores by UV irradiation and gaseous iodine treatment applied to air handling filters Ultraviolet C light with wavelength of 222 nm inactivates a wide spectrum of microbial pathogens Transmission of the severe acute respiratory syndrome on aircraft A calculation procedure for heat, mass and momentum transfer in three-dimensional parabolic flows Human exposure to respiratory aerosols in a ventilated room: Effects of ventilation condition, emission mode, and social distancing Coronavirus disease (COVID-19) prevention and treatment methods and effective parameters: A systematic literature review Sampling and detection of corona viruses in air: a mini review Implementation and visualization of artificial intelligent ventilation control system using fast prediction models and limited monitoring data Construction of linear temperature model using non-dimensional heat exchange ratio: towards fast prediction of indoor temperature and heating, ventilation and air conditioning systems control Mitigating COVID-19 infection disease transmission in indoor environment using physical barriers Airborne spread of measles in a suburban elementary school Optimal control of high-rise building mechanical ventilation system for achieving low risk of COVID-19 transmission and ventilative cooling Indoor airflow and contaminant transport in a room with coupled displacement ventilation and passive-chilled-beam systems Simplified numerical models for complex air supply diffusers The efficacy of social distance and ventilation effectiveness in preventing COVID-19 transmission Review and comparison between the Wells-Riley and dose-response approaches to risk assessment of infectious respiratory diseases The 2019-nCoV epidemic control strategies and 44 future challenges of building healthy smart cities On airborne transmission and control of sars-cov-2 Evaluating the commercial airliner cabin environment with different air distribution systems Occupant-density-detection based energy efficient ventilation system: Prevention of infection transmission Airborne Contagion and Air Hygiene Occupancy-aided ventilation for both airborne infection risk control and work productivity Comparison of the eulerian and lagrangian methods for predicting particle transport in enclosed spaces Evaluation of various turbulence models in predicting airflow and turbulence in enclosed environments by CFD: Part 2 -comparison with experimental data from literature Inverse design of an indoor environment using a filter-based topology method with experimental verification Inverse design of indoor radiant terminal using the 45 particle swarm optimization method with topology concept With the submission of this manuscript, I would like to undertake that I have consulted the Guide for Authors in preparing my submitted manuscript. And I also acknowledge that I have prepared the manuscript in compliance with the Ethics as described in the Guide for Authors.No conflict of interest exits in the submission of this manuscript, and manuscript is approved by all authors for publication. I would like to declare on behalf of my co-authors that the work described was original research that has not been published previously, and not under consideration for publication elsewhere, in whole or in part. All the authors have approved the manuscript that is enclosed.