key: cord-0807635-gztdmqns authors: Risbeck, Michael J.; Bazant, Martin Z.; Jiang, Zhanhong; Lee, Young M.; Drees, Kirk H.; Douglas, Jonathan D. title: Modeling and Multiobjective Optimization of Indoor Airborne Disease Transmission Risk and Associated Energy Consumption for Building HVAC Systems date: 2021-09-23 journal: Energy Build DOI: 10.1016/j.enbuild.2021.111497 sha: 08d3164082ac8813d9737ae1ffd99d60c7a1c215 doc_id: 807635 cord_uid: gztdmqns The COVID-19 pandemic has renewed interest in assessing how the operation of HVAC systems influences the risk of airborne disease transmission in buildings. Various processes, such as ventilation and filtration, have been shown to reduce the probability of disease spread by removing or deactivating exhaled aerosols that potentially contain infectious material. However, such qualitative recommendations fail to specify how much of these or other disinfection techniques are needed to achieve acceptable risk levels in a particular space. An additional complication is that application of these techniques inevitably increases energy costs, the magnitude of which can vary significantly based on local weather. Moreover, the operational flexibility available to the HVAC system may be inherently limited by equipment capacities and occupant comfort requirements. Given this knowledge gap, we propose a set of dynamical models that can be used to estimate airborne transmission risk and energy consumption for building HVAC systems based on controller setpoints and a forecast of weather conditions. By combining physics-based material balances with phenomenological models of the HVAC control system, it is possible to predict time-varying airflows and other HVAC variables, which are then used to calculate key metrics. Through a variety of examples involving real and simulated commercial buildings, we show that our models can be used for monitoring purposes by applying them directly to transient building data as operated, or they may be embedded within a multi-objective optimization framework to evaluate the tradeoff between infection risk and energy consumption. By combining these applications, building managers can determine which spaces are in need of infection risk reduction and how to provide that reduction at the lowest energy cost. The key finding is that both the baseline infection risk and the most energy-efficient disinfection strategy can vary significantly from space to space and depend sensitively on the weather, thus underscoring the importance of the quantitative predictions provided by the models. With the recognition that airborne exchange of respiratory aerosols may be the primary means of transmission 28 for COVID-19 and other diseases [1] [2] [3] [4] ✿✿✿✿ [1] [2] [3] [4] , it is crucial to understand how HVAC systems can affect this infection Unfortunately, each option leads to increased energy use, and their effect on indoor-air quality can vary significantly 32 based on outdoor-air conditions. In this paper, we propose a theoretical HVAC ✿✿✿✿✿✿✿✿✿✿✿ model-based optimization framework 33 to determine the combination of clean-air sources that can achieve a given reduction in infection risk in the most cost-effective manner. The optimization can recommend a spectrum of possible operational profiles ranging from 35 minimum infection risk to minimum energy, providing predicted energy consumption and infection risk for each. 36 This information can empower building managers to make informed decisions about how to operate their buildings 37 given current cost and disinfection priorities. 38 Underpinning the proposed optimization is a set of dynamic models for zone temperature, humidity, and the 39 expected transmission rate, which are parameterized in terms of physical and usage characteristics of the zone (e.g., 40 floor area, ceiling height, design occupancy, HVAC equipment sizes) that are representative of typical commercial 41 buildings. These models can then be used to predict the effect of various design and operational variables on energy 42 and infection risk, thus allowing actionable and informed recommendations to be made. We begin by reviewing the 43 relevant background for airborne transmission modeling in buildings along with the associated energy analysis, and 44 then we present the main goals of this paper. 50 distribution of the particles covers several orders of magnitude [8, 9] , with significant dependence on vocalization 51 volume [2, 10] and respiratory mode [11, 12] . The largest of these droplets, produced primarily by coughs and 52 sneezes [13] can be up to 1 mm in diameter. However, because they settle rapidly to the ground, these large droplets 53 generally do not pose a risk for long-range airborne transmission [14, 15] . By contrast, the smallest droplets are sized 54 between 0.1 and 10 µm and are produced in high concentrations by standard respiration. Because these particles 55 settle much more slowly, they tend to remain suspended in the air for long periods of time that exceed the time scales 56 for turbulent mixing and air change in an indoor space [4] . Such aerosol particles are of primary concern for airborne 57 transmission, as they can spread over long distances due to the air circulation provided by natural convection and 58 HVAC systems [16] [17] [18] , thus leading to new infections if inhaled by susceptible individuals. 59 Although infectious aerosols can remain airborne for long periods, their concentration does decay over time due to 60 a variety of removal mechanisms [4] . For example, the particles naturally deposit onto surfaces (with a size-dependent 61 rate [19, 20] ) as fomites, thus rendering them unlikely to transmit the disease [21] . In addition, the particles may 62 simply be removed from the air via outdoor-air ventilation (with particle-laden air exhausted to the ambient and 63 replaced with a similar volume of outdoor air free from respiratory particles) or filtration (by which some fraction 64 of the particles become trapped in a filter) [22] [23] [24] ✿✿✿✿✿✿ [22] [23] [24] . In addition, the infectious material in the particles can both aspects can be considered. 246 The remainder of this paper is structured as follows. In Section 2, we present the full set of dynamic models 247 for airborne infection, thermal dynamics, and the regulatory control system. All variables are defined, and possible In this section, we present various dynamic models that can be used to estimate and predict infection risk and 257 HVAC energy consumption within an indoor zone. All models are defined in the standard continuous-time state-space for states x, inputs u, outputs y, and static parameters θ. (Note the distinction between u and θ is that values of 260 u vary throughout the simulation period, whereas values of θ are held constant.) Models are simulated using the 261 standard 4th order explicit Runge-Kutta method assuming a piecewise-constant hold on u and calculating y as the 262 average value over the integration interval, which for our purposes is ∆ = 15 min. 263 Performance metrics are all calculated for each timestep as functions ℓ θ (y, u) that are then integrated as appro-264 priate over the simulation interval. In various contexts, they are used as optimization objectives or constraints. With this general approach, the main dynamic model for the airborne infectious quanta concentration C is as 275 follows: From these variables, we then calculate the primary metrics via where N T is the expected number of transmission events that occur and E aux the energy consumption associated 278 with UV and auxiliary disinfection, both over the time period t ∈ [0, τ ]. Descriptions and units of all variables are 279 given in Table 1 . We discuss key model features and parameters in the following sections. 280 Table 1 : Variables in the infectious particle concentration model. States C airborne concentration of infectious particles q/m 3 µ I attenuation factor for infector generation rate (e.g., due to masks) − µ S attenuation factor for susceptible dose rate (e.g., due to masks) − τ evaluation time for metrics s βq hazard rate for transmissions q −1 w UV power consumption of in-duct UV at maximum activation kW w aux,j power consumption of in-zone disinfection device j at maximum activation kW To model the time variation in infection quanta concentrations, we note that infectious particles are released into 282 the air by the infectious individual and then removed by a variety of mechanisms. To standardize modeling of these 283 effects, we define the concept of "clean-air delivery" to the space as follows: for a piece of equipment or physical 284 process j that deactivates or captures infectious particles at a total rate r j (measured in units of ) from an air stream 285 with concentration C (measured in units of ), the corresponding clean-air delivery rate is defined as 286 f clean,j = r j C which thus has units corresponding to a hypothetical volumetric flow (and can be converted to air-change rates 287 by dividing by the space volume). We use this definition because for most disinfection processes, r j is directly 288 proportional to C, and thus f clean,j can be expressed as a simple fraction of airflow through the device. In addition, 289 this formulation provides a common basis for comparison of different disinfection devices: multiple devices providing 290 the same clean-air delivery rate thus become fungible from an infection-risk perspective and can be assessed in terms 291 of energy consumption or other considerations to choose the best among them. One complication of this clean-air framework is that for devices and processes that operate at the particulate 293 level (i.e., deposition and filtration), the removal rate r j depends on the size distribution of the particles containing 294 the infectious material [4] . When the inlet size distribution is known, accounting for size-dependent effects is 295 straightforward for a single device. However, because their action leads to changes in the airborne size distribution, 296 it is not longer possible to fully and exactly describe the clean-air characteristics of a device without knowing (and 297 accounting for the inherent recirculation effects on) the size distribution of airborne particles.For simplicity, our 298 current approach is to assume a representative particle diameter (e.g., 1 to 3 ) , close to the effective aerosol size 299 defined by Bazant and Bush [4] for typical respiratory activities and room conditions. With this value, we calculate 300 all clean-air delivery rates assuming a narrow unimodal distribution of particles at that size. However, see discussion 301 in the next section for how this effect could be modeled more accurately without significant changes to the existing 302 framework. Aside from size-dependent effects, the calculation of the clean-air delivery rate for most processes and devices is 304 straightforward. For example, airborne particles naturally deposit on the ground at a given velocity ν deposition due 305 to gravity. Thus, in a room with volume V and height h, the removal rate of such particles by deposition is given by Similarly, due to natural decay of the viruses (assumed to occur with a first-order rate constant k decay ), the removal 307 rate due to natural decay is thus given by 308 r decay = k decay V C In practice, this decay rate may vary with temperature and humidity within the space [4], but for simplicity here 309 we assume it is truly constant. As modeled above, we combine these two effects as "natural" disinfection sources in 310 Eq. (1) with 311 f clean,natural = k natural V, k natural = k decay + 1 h ν deposition Note that they scale with the total volume of the space and occur independently of any HVAC operational decisions. For standalone filtration devices, the clean-air calculation is also straightforward: assuming a total volumetric 314 flow f filter through the filter, which captures a fraction η filter of the particles the total removal rateis given by 315 r filter = η filter f filter C and so the clean-air delivery is simply 316 f clean,filter = η filter f filter Effective filtration efficiencies for various filter grades are known [44] , modulo uncertainty in size dependence. 317 Similarly, for UV devices that kill a given fraction η UV of the microbes passing through them, the clean airproduction 318 is 319 f clean,UV = η UV f filter If properly designed, UV disinfection tunnels can achieve very high disinfection rates η uv ≈ 1 [28] , but the performance 320 of smaller standalone devices may vary. For devices operating in parallel, their total clean-air delivery is a simple sum of their individual values. Since 322 all auxiliary in-zone devices are effectively in parallel, we thus include the summation term in Eq. (1) , noting that 323 the maximum clean-air capacity f max aux,j of a given auxiliary device needs to be scaled by the extent a aux,j to which 324 it is currently active. Note that for some devices a aux,j may vary continuously, while for others, it may take only a 325 binary value indicating whether the device is on or off. 326 For devices operating directly in series, however, the total clean-air delivery must account for the fact that the 327 clean-air delivery for each device must be calculated in terms of the original inlet concentration rather than that 328 device's particular inlet concentration. The canonical example of this configuration is in the AHU: when air is 329 returned to the AHU, a given fraction x a is vented to the ambient (and replaced with a corresponding volume of 330 outdoor air), after which it passes through a filter with disinfection efficiency η filter and possibly also through a UV 331 kill tunnel that kills a fraction a uv η UV of microbes in the airstream.Taken individually, the clean-air rates of each 332 device would be given as 333 f clean,vent = x a f AHU f clean,filter = η filter f AHU f clean,UV = a uv η UV f AHU However, because these devices operate in series, we must account for the fact that each device processes the outlet 334 of the previous device. Thus, the inlet concentration to the filter is only 1 − x a times its initial value, and thus the with P s giving that individual's infection probability in terms of the individual's infectious dose rate q s , which is 349 itself given by We note that at steady-state conditions (i.e., dC/dt = 0), the model in Eq. (1) gives C = q I /f clean . Substituting 351 these values (and converting the time-varying integral to a simple multiplication) gives we are interested in the HVAC operation of the zones, it is more practical to adopt a zone-based approach in which 365 infection risk is associated with spaces rather than individuals. To address these limitations, we take an approach similar to Bazant and Bush [4] and make a linear approximation 367 as follows: Noting that Eq. (1) has already defined q S = s q s (t) in the model, substituting this value gives the equation for 369 N T presented in Eq. (1). The main benefit of this formulation is that we can now split the whole-building R on a 370 zone-by-zone basis. Thus, separate actions can be taken in each zone based on that zone's contribution to overall 371 infection risk. In arriving at this formulation, we have made use of the fact that 1 − exp(−x) ≈ x for small values of x, which 373 allows us to remove the nonlinearity and shift the summation inside the integral. We note also that the linear 374 approximation is conservative, i.e., uniformly over-estimating N T , due to concativity of the exponential function. and humidity. Note that throughout this discussion, we use "humidity" to mean the "absolute humidity ratio" 466 (commonly denoted ω) unless otherwise specified. ODE equations for the mass and energy balances are as follows: The AHU outlet conditions and loads are calculated from simple heating and cooling coil models with the following 469 functional form (and described in more detail in Section B.2): Finally, from all of these outputs we the main metrics associated with energy consumption and thermal comfort in 472 the space: Descriptions and units of all variables in these equations can be found in in which H(T, ω) gives the specific enthalpy of an air stream at temperature T and humidity ω, while T (h, ω) 509 gives the temperature of an air stream at specific enthalpy h and humidity ω. From here, if T in ≤ T sp AHU , the air is 510 heated directly to the setpoint with no change in humidity. Thus, the AHU outlet conditions are T out = T sp AHU and 511 ω out = ω in . Alternatively, if T in > T sp AHU , the air is cooled as discussed next. Because of the possibility of condensation, the cooling coil requires some additional modeling to determine the 513 outlet humidity. For this purpose, we follow the common "contact mixture analogy" (e.g., as in Seem and House [59] ). With this formulation, we assume that a fixed fraction of air (x bypass ) bypasses the cooling coil completely, while 515 the remaining fraction (1 − x bypass ) equilibrates with the coil. As before, we assume that the cooling coil meets the 516 setpoint, which gives T out = T sp AHU . From this value, we can back-calculate the coil-equilibrating conditions as in which ω sat (T ) gives the saturation humidity at temperature T . This term is responsible for modeling the 518 dehumidification provided by the coil, which is often a significant fraction of energy consumption in humid climates. Note that the first equation assumes linear mixing for the recombination of coil and bypass streams. We calculate 520 the outlet humidity as 521 ω out = x bypass ω in + (1 − x bypass )ω coil which will always be less than or equal to the inlet humidity ω in ✿✿✿✿✿✿✿✿ accurate Summarizing the heating and cooling models, we thus have the following relationships: From these conditions, we can thus calculate the thermal loads on the coils as follows: in which H(T, ω) is the specific enthalpy of wet air at temperature as before, and H w (T ) is the specific enthalpy of 526 liquid water. Note that this expression is written so that it gives the heat gained by the air stream, with a positive 527 value indicating the stream was heated and a negative value indicating the stream was cooled. We can thus split 528 into individual heating and cooling components as The calculated T out , ω out , ∆h h coil , and ∆h c coil then become the AHU conditions T AHU , ω AHU , ∆h h AHU , and ∆h c AHU 530 indicated in Eq. (4). As above, we do not consider humidification equipment, but where present, it could be accounted 531 for by increasing ω AHU up to a given setpoint. Physically, the energy consumed by the fan is given by where η fan is the mechanical efficiency of the fan, and ∆P fan is the pressure rise across the fan. The cubic dependence 536 on f comes from the fact that the pressure rise of the fan is equal to the pressure drop through the ductwork, which 537 is commonly modeled as proportional to the square of flow. These considerations suggest that w fan ∝ f 3 . In practice, 538 the mechanical efficiency of the fan will vary over its operating range, and thus the cubic term alone is not sufficient 539 to match the actual performance of the fan. By adding the additional linear and quadratic terms, this variation can 540 be captured. Note that some sources will suggest adding an additional constant term to better match experimental 541 behavior. However, we require for our application that w fan is zero when f is zero (e.g., during unoccupied hours 542 when the HVAC system is shut off), and so we do not include this term to avoid artificial inflation of predicted 543 electricity consumption. The most accurate way to determine the coefficients c i in the fan model is to obtain a dataset of (f, w fan ) pairs 545 from the actual fan and use standard regression. Unfortunately, it is uncommon to directly measure w fan is real 546 buildings, and so this approach is not practical. Instead, we define one set of coefficientsc i to match a representative according to explicitly defined control laws, those laws often consist of complicated rule-based logic that operates on 567 much faster timescales than desired simulation timestep. Thus, rather than try to replicate the control laws directly, 568 we instead choose a phenomenological approach in which we attempt to model the outcomes of the controllers' 569 actions. For example, rather than trying to model the (heavily modified) PI control law within the VAV controllers 570 to specify airflow as a function of setpoint tracking error, we instead assume that the controller is well-designed and 571 thus maintains temperature setpoints within the space whenever possible. This overall approach The main controller output variables are calculated using the following equations: Note that the clip function is defined as clip(x, a, b) = min(max(x, a), b) for a ≤ b. Variables used in this model are 577 described in Table 3 . Specific equations are discussed in the following sections. Overall, the main functionality of the controller model is that it allows prediction of the internal quantities ✿✿✿✿✿ HVAC 579 ✿✿✿✿✿✿ control ✿✿✿✿✿✿✿✿ variables ✿ that ultimately determine infection risk and energy consumption in the space. We can thus adjust 580 the static controller parameters θ and predict how the HVAC control system will respond, which allows us to optimize 581 for energy consumption or infection risk depending on our current priorities. In an ideal system, we would be able to 582 manipulate (and thus optimize) the airflow f AHU and outdoor-air fraction x a directly, but in existing HVAC systems, 583 these quantities reflect the response of the regulatory control system and thus can be adjusted only indirectly. in which the "..." represent the remaining model inputs (which would not all be known in a real system but are 598 known to the model). Note that for physical reasons, both variables must be nonnegative, but since that restriction 599 is enforced by clipping after the fact, we place no sign restrictions onf AHU andQ h . From the model structure, we 600 know that a suitable valueQ h always exists and a suitablef AHU exists under standard operating conditions (i.e., T AHU < T z ). Unfortunately, because f AHU enters the ODE in a product with the state variable T z , an exact solution to the 603 first equation requires iterative methods. The use of such algorithms can lead to slow and inconsistent solution times, 604 and so we would like to avoid them. Thus, we instead opt for an approximate solution that is non-iterative. To T AHU and T z are constant during the integration interval, this calculation is exact, and the accuracy deteriorates as 611 T AHU and/or T z vary within the interval. By assumption, T AHU will be equal to its setpoint T sp AHU , and so there is 612 little to no approximation error there. Similarly, during occupied hours, T z will generally be near the cooling setpoint 613 T max z or heating setpoint T min z depending on the season. However, during transitions at the beginning of the occupied 614 period, T z can change very quickly as the controller tries to restore setpoint, and so it is generally a good idea to 615 replace T z with an average value (T z + T max z )/2 to avoid overshoot. In any case, as long as the zone temperature 616 setpoint stays reasonably constant throughout the occupied period, this calculation is sufficient to accurately model 617 airflow to the space. Note that it is in Eq. (C.1) where the primary impact of the supply-temperature setpoint T sp AHU is considered. Specifically, when T AHU is higher and thus closer in value to T z , we see that the denominator becomes smaller, and 620 so the delivered airflowf AHU increases. A similar effect would also be possible by decreasing T z (via its setpoint 621 T max z ), but due to the potential impact on occupant comfort, we do not directly consider that as a manipulated 622 variable. In any case, the key observation is that the impact of T AHU on airflow (and thus also on infectious-particle 623 concentration) is implicit due to the action of temperature control in the space. After clippingf AHU to find the true f AHU as in Eq. (7), we can thus determineQ h via the discretization of Here, we can solve forQ h using the exact linear formulas as forQ c above. The resulting 626 value is then clipped to Q h as in Eq. (7). simply the minimum fraction of f AHU that will deliver the required minimum outdoor-air ventilation rate f min vent (which 636 cycles between zero and the pre-configured boundf vent based on the occupancy flag σ). As discussed in the previous 637 section, we always have that f AHU ≥ f min vent , and so we know that x min a = f min vent /f AHU will always be between 0 and 1. For x max a , the bound is calculated as the maximum fraction of f AHU that will keep the temperature of the resulting 639 mixture below the supply temperature setpoint T sp AHU (so as to avoid an unnecessary heating load). Assuming linear 640 mixing, this condition is exactly satisfied when which gives a valid 0 ≤ x max a ≤ 1 whenever T a < T sp AHU < T z . However, because those constraints are not always satisfied (in particular due to seasonal variation in T a ), we modify the calculation to clip both temperature differences to zero, i.e., with the convention that x max a = 1 in the singular case T z = T a . With these modifications, the calculation gives can be guided in accordance with current priorities. We discuss these two use cases in the following sections. To simulate the infection model, we require values for the airflow inputs f AHU and x a , as well as the activation 676 fractions a UV and a aux,j for the relevant disinfection devices. The numbers of infectors and susceptibles N S and N I 677 can be chosen from a typical occupancy profile as discussed in Section A.4. If the evaluation period begins during unoccupied hours, then the initial condition for the infection quanta concentration C can be set to zero; otherwise, a 679 "warmup" period of roughly 5 hours should be simulated to obtain a more accurate initial condition. From there, the 680 hypothetical infectious particle concentration in the space can be simulated via Eq. (1), and the expected number of 681 transmissions can be calculated using Eq. (2). Where estimates of energy consumption are required, the AHU and fan models from Eqs. (4) and (5) can be 683 used, since their inputs are generally all known. In addition to f AHU and x a , these models also require the zone 684 conditions T z and ω z , the ambient conditions T a and ω a , and the AHU conditions T AHU and ω AHU (although ω AHU 685 can also be estimated from the AHU model Eq. (4), as its value is often not measured in real buildings). In-zone 686 heating energy can also be included where Q h is known, although its value generally cannot be directly measured 687 and must be estimated from other sources (e.g., heating-coil activation commands). We discuss some additional use 688 cases in the following sections. Thus, the (time-varying) value of the infection quanta concentration C is an affine function of this group. We know 698 also that if C I = 0, then C ≡ 0, and thus we have that C is directly proportional to these parameters. Second, the 699 performance metric N T is proportional to the product of parameters (1 − µ S )f breathe,S that multiply C to determine 700 q S , and thus its value is directly proportional to them. Combining these two facts, we find the relationship it is desirable to have a more accurate forecast of Q z and w z , which ultimately determine the response of the HVAC 717 system. To infer the values of these parameters, we note that all other terms in Eq. (3) are generally known with higher 719 accuracy, either via direct measurements from the building or based on simple physical characteristics of the space. In particular, the derivative terms dT z /dt and dω z /dt can be estimated from data through appropriate filtering. Thus, we can back-calculate values on a pointwise basis as generally with additional filtering to minimize the impact of measurement noise. Once these disturbance trajectories the goal of the optimization is to identify the most efficient clean-air sources, which can vary from day to day based 734 on ambient conditions. In addition, it may be the case that some spaces already provide adequate disinfection under 735 standard operation, and thus there is no motivation to further increase clean-air delivery. In order to address these needs, we formulate a multiobjective optimization problem using the dynamic models 737 to predict the necessary decision metrics. Mathematically, the overall structure of the optimization problem is as That is, we perform multiobjective optimization over a set of model parameters θ ∈ Θ with each scalar objective 740 function and constraint z k , calculated from the inputs u t and outputs y t of the simulation model. Note that in this 741 context, the models f ( · ), h( · ), and ℓ k ( · ) represent the coupled models, i.e., the combination of infections quanta, 742 thermal, and controller models as mentioned in the previous paragraph. Owing to the multiple objectives, the goal is not to find just a single optional point θ * but rather the set of 744 non-dominated points also referred to as the "Pareto set". All values in this set are efficient in the sense that it is not possible to improve the The primary operational variables to optimize are the supply temperature setpointT sp AHU , the minimum ventilation 770 setpointf vent , economizer threshold temperatureT econ , and the activationsā UV andā aux,j for disinfection devices. Note that all of these variables are parameters of the controller model from Section 2.3. For simplicity, we assume 772 that the operational variables are all held constant over the simulation interval (e.g., each day) so as to keep 773 the optimization space reasonably small. Various extensions are possible that would adjust these variables more 774 frequently (e.g., every hour), but care would be needed to account for the transient dynamics of the control layer 775 after setpoint changes, as these effects are not included in the current models. The primary design variables to optimize are the in-duct filter type, which implicitly adjusts η filter and the fan- 2) and (6)). i.e., choosing 11 values between 13 • C and 18 • C forT sp AHU , 11 values between 0.5 m 3 /s and 1.5 m 3 /s forf vent , and 826 two values forā UV corresponding to "on" and "off" respectively. Thus, to optimize over this set, we need perform 827 11 × 11 × 2 = 242 simulations. Once the setΘ has been chosen, the Pareto ✿✿✿✿✿✿ overall optimization algorithm is straightforward: To illustrate the potential uses of our proposed modeling and optimization framework, we start by applying the 864 models to real building data. For these examples, we will use datasets from two zones in a real building: (1) total supply air flow is reasonably constant throughout the occupied period on a given day, but that the amount of 896 flow provided does change from week to week, likely corresponding to seasonal changes. The provided ventilation 897 varies much more significantly, perhaps due to the action of the economizer, but it still covers a fairly narrow range. By contrast, we see that there is much greater variation in the Gym zone, both within a given day and from week to 899 week. We almost always see a large spike in airflow at the beginning of the occupied period, which indicates that the system is inactive in the Office zone but active in the Gym zone during these days. To assess the infection risk present in these zones, we take the data from the previous plot and simulate the 909 dynamic infectious-particle models from Section 2.1 to calculate average clean-air delivery rate and expected trans- Before moving on, we briefly discuss the uncertainty associated with the two variables. For the clean-air delivery 930 rate, the only uncertain terms are the passive decay rate for the infectious particles (due to both deactivation and 931 deposition) and the filtration efficiency for the in-duct filter. Because both effects exhibit particle-size dependence, 932 their actual effect will depend slightly on the specific particle distribution produced by the infector. We turn now to showing how these models can be used for the purposes of prediction and optimization. In this 945 use case, we wish to predict the operation of the HVAC system one day in advance, which means we do not have 946 access to flow measurements from the BMS and must predict them using the controller and zone-temperature models. Thus, we start by showing example day-ahead predictions of clean-air delivery using the models from Section 2. Important inputs to the thermal models include the internal heat and moisture disturbances. To predict these 949 values in advance, we use the following procedure: back-calculate disturbances on the prior 7 days of data as discussed policy. We will use this feature to more thoroughly assess the available control space and the accuracy of our models. For this purpose, we consider the first floor of the "Large Office" reference building provided by EnergyPlus, Fig. 6 . For the purposes of energy accounting, we assume cooling 1009 is provided via electricity at a COP of 3, while heating is provided by gas at 90% efficiency. We use an electricity 1010 price of 0.12 $/kW h and a gas price of 0.80 $/therm. For brevity, we do not show thermal discomfort, although all from the new optimization variable. First, we note once again that infection rate is generally higher in the winter 1018 months and lower in the summer months, simply due to variation in the average airflow provided by the HVAC 1019 system. We note that this effect is much more pronounced in the Cold climate compared to Hot due to the weather-1020 dependent cooling loads (and resulting airflow differences). Second, we see that for reducing infection risk, increasing 1021 the supply temperature setpoint is less effective than increasing the ventilation rate in the heating season but more 1022 effective in the cooling season. This observation is consistent with the fact that the HVAC systems often operate near 1023 minimum-flow constraints during the heating season due to the small cooling load, and thus adjusting the supply 1024 temperature setpoint has little to no effect on total airflow in these conditions. By contrast, adjusting the supply temperature setpoint in the cooling season can have a significant impact on total airflow, thus providing greater reduction in infection rate. (Note that there is essentially no heating season in the Hot climate, and thus increased supply temperature is always more effective in this case.) Third, we see that increased ventilation almost always requires additional energy consumption, and the magnitude is much higher in particularly hot or cold weather. The 1029 explanation for this effect is that because the building is equipped with an economizer using an aggressive suitability 1030 threshold, the system will automatically increase ventilation above its minimum value when energetically favorable. Thus, any additional ventilation that results from increasing the minimum ventilation setpoint necessarily requires an 1032 energy penalty. By contrast, increasing the supply temperature setpoint can potentially reduce energy consumption, 1033 and so it tends to be much less costly. Finally, we note that the HVAC system by itself has a somewhat narrow range to reduce the infection rate. Comparing the maximum and minimum infection rates on each day, we see less than a factor of two reduction. a sharp point in the upper left corner, it is evident that the value of the minimum ventilation rate becomes nearly 1064 degenerate at high values of the supply temperature setpoint. The explanation for this behavior is that the higher 1065 supply temperatures result in increased total supply airflow, and so the economizer will naturally increase outdoor-air 1066 flow (to maintain roughly a constant outdoor-air fraction). Thus, increasing the minimum ventilation rate essentially 1067 has no effect because the economizer is already providing more than that amount of ventilation. Second, we note that 1068 increasing the ventilation rate uniformly leads to an increase in energy use. As observed in the previous examples, this 1069 behavior is due to the aggressive economizer on this building: any time extra ventilation is energetically favorable, 1070 it will be supplied automatically by the economizer; thus, any increased ventilation that results from changing the 1071 minimum setpoint is necessarily at an energy penalty. We note that the use of energy-recovery ventilation systems 1072 could significantly reduce this cost [45], but installation of such devices would be costly and perhaps not worthwhile 1073 solely for reducing infection risk. Third, we see that increasing the supply temperature setpoint can decrease energy 1074 cost at first but then eventually begins to increase it. This is generally due to the tradeoff between latent cooling load 1075 (which decreases at higher supply temperatures) and fan power (which increases at higher flows caused by higher 1076 supply temperatures). Because both of these effects are nonlinear, their resulting sum can take on the wide variety 1077 of shapes observed in the figure depending on ambient and internal conditions. Finally, we note that the unique 1078 behavior observed in the Cold Climate Winter case is due to the fact that the system is operating at minimum-flow 1079 conditions. Thus, increasing the supply temperature setpoint above its minimum bound initially does not change the 1080 flow rate (since it is still at minimum) but requires additional energy consumption to heat the air to that temperature. Only after a sufficiently high supply setpoint does airflow rise above its minimum abound ✿✿✿✿✿✿ bound ✿ and we see more 1082 typical behavior. 1083 Overall, we see in these example cases that the Pareto-optimal set generally (but not always ) contains points with for each climate and season (corresponding to the eight cases in Fig. 7) and solve the Pareto optimization for each weekday. Note that this Pareto search accounts for thermal comfort constraints, and so on some days, there may be very few feasible points. From the set of Pareto-optimal solutions, we choose three representative points: the point A key challenge with this approach is that due to the simplistic disturbance forecast used (which essentially just 1105 reuses the disturbances from one week ago), it is likely that the model predictions may be systematically off due 1106 to week-to-week changes in disturbances (primarily due to solar radiation and heat exchange with the ambient). However, because the model predictions are being used for optimization, any linear re-scaling does not affect the 1108 location of the optimal solutions. Thus, to avoid the poor disturbance forecast influencing accuracy metrics, we 1109 re-scale the model's predictions to match the actual data using one single scale factor for the entire week. This 1110 procedure will correct for the effect of the disturbance schedule, but any other model deficiencies will still appear in 1111 the plots. These results are shown in Figs. 9 and 10 for the Cold and Hot climates respectively. From these results, we see that after correcting for the poor disturbance forecast, the models accurately predict the 1113 resulting metrics for each representative solution. Although there are some cases where accuracy is not satisfactory 1114 (in particular, the winter energy cost in Fig. 9 and the spring clean-air delivery in Fig. 10 ), the dynamic models do relative simplicity of the proposed models, they can nevertheless capture the key behavior of real buildings and 1120 ultimately lead to actionable insights for building operators. It is time to address airborne transmission of COVID-19 Aerosol emission and 1502 superemission during human speech increase with voice loudness Quantitative assessment of the risk of airborne transmission of 1505 -2 infection: Prospective and retrospective applications A guideline to limit indoor airborne transmission of COVID-19 A paradigm shift to combat indoor respiratory infection Speech can produce jet-like transport relevant to 1513 asymptomatic spreading of virus The mechanism of breath aerosol formation Air-borne infection The size and the duration of air-carriage of respiratory droplets and droplet-nuclei Effect of voicing and 1522 articulation manner on aerosol particle emission during human speech Size distribution and sites of origin of droplets expelled from the human respiratory tract during 1526 expiratory activities Modality of human expired aerosol size distributions Violent expiratory events: on coughing and sneez-1533 ing Fluid dynamics of covid-19 airborne infection 1535 suggests urgent data for a scientific design of social distancing Effects of ventilation on the indoor spread of 1537 COVID-19 The fluid mechanics of natural ventilation Estimating covid-19 exposure in a classroom setting: A comparison between mathe-1541 matical and numerical models Toward understanding the risk of secondary airborne infection: 1543 emission of respirable pathogens Dynamics of infectious disease transmission by inhalable respiratory 1545 droplets Covid-19 rarely spreads through surfaces. so why are we still deep cleaning Airborne Contagion and Air Hygiene. An Ecological Study of Droplet Infections Using a mathematical model to evaluate the efficacy of TB control measures Mathematical models for assessing the role of airflow on the risk of airborne 1553 infection in hospital wards Humidity-dependent decay of viruses, but not bacteria, in aerosols and droplets follows 1555 disinfection kinetics Back to normal: An old physics route to reduce SARS-CoV-2 transmission in indoor spaces Ultraviolet irradiation doses for coronavirus inactivation-1560 review and analysis of coronavirus photoinactivation studies Ultraviolet germicidal irradiation handbook: UVGI for air and surface disinfection Response to letters to the editor 1564 on aerosol filtration efficiency of common fabrics used in respiratory cloth masks: Revised and expanded results Puff trains in speaking produce long-range turbulent 1567 jet-like transport potentially relevant to asymptomatic spreading of viruses Towards improved social distancing 1570 guidelines: Space and time dependence of virus transmission from speech-driven aerosol transport between two 1571 individuals Asymptomatic transmission, the achilles heel of current strategies 1573 to control covid-19 Effectiveness of three versus six feet of physical distancing for controlling spread of covid-19 among primary 1576 and secondary students and staff: A retrospective, state-wide cohort study Mask use and ventilation improvements to 1580 reduce covid-19 incidence in elementary schoolsgeorgia Airborne spread of measles in a suburban elementary school The transmission of tuberculosis in confined spaces: 1585 an analytical review of alternative epidemiological models HVAC filtration for controlling infectious airborne disease transmission in indoor 1588 environments: predicting risk reductions and operational costs Risk of indoor airborne infection transmission estimated from carbon dioxide 1591 concentration Association of the infection probability of COVID-19 with ventilation rates in confined 1593 spaces A systematic approach to estimating the effec-1595 tiveness of multi-scale IAQ strategies for reducing the risk of airborne infection of SARS-CoV-2 The efficacy of social distance and ventilation effectiveness in preventing COVID-19 1598 transmission Exhaled co2 as covid-19 infection risk proxy for different indoor environments and 1600 activities Investigation of potential aerosol transmission and infectivity of SARS-CoV-2 through central 1603 ventilation systems Building readiness Economic, environmental and 1607 health implications of enhanced ventilation in office buildings Method for measuring performance of protable household electric room air cleaners Core recommendations for reducing airborne infectious aerosol exposure Development and testing of the characteristic curve fan model The relationship between filter pressure drop, indoor air quality, and 1618 energy consumption in rooftop HVAC units Estimates of the energy impact of ventilation and associated financial expenditures Energy vs. ventilation rate in buildings: A comprehensive scenario-based assess-1622 ment in the European context Why enthalpy economizers don't work Energy standard for buildings except low-rise residential buildings A simplified dynamic model for chilled-water cooling and dehumidifying coilspart 1: 1629 Development A simplified dynamic model for chilled-water cooling and dehumidifying coils-part 2: Experimental 1631 validation Dynamic modeling and self-optimizing operation of chilled water systems 1633 using extremum seeking control Development and evaluation of optimization-based air economizer strategies Optimizing the design of room air filters for the removal of submicrometer particles Exposure Factors Handbook Indoor occupancy estimation from carbon dioxide concentration Predicting occupancy 1643 counts using physical and statistical CO2-based modeling methodologies Bayesian filtering for building occupancy estimation 1646 from carbon dioxide concentration Hourly thermal load prediction for the next 24 hours by 1648 Scaling and related techniques for geometry problems Monitoring carbon dioxide to 1652 quantify the risk of indoor airborne transmission of COVID-19