key: cord-0801653-aheg8yaz authors: Sousan, Sinan; Fan, Ming; Outlaw, Kathryn; Williams, Sydney; Roper, Rachel L title: SARS-CoV-2 Detection in Air Samples from Inside Heating, Ventilation, and Air Conditioning (HVAC) Systems- COVID Surveillance in Student Dorms date: 2021-10-22 journal: Am J Infect Control DOI: 10.1016/j.ajic.2021.10.009 sha: 99dd54c0ccdea61049d3ee48d94d9dbd4924ef88 doc_id: 801653 cord_uid: aheg8yaz BACKGROUND: The COVID-19 pandemic affected universities and institutions and caused campus shutdowns with a transition to online teaching models. To detect infections that might spread on campus, we pursued research towards detecting SARS-CoV-2 in air samples inside student dorms. METHODS: We sampled air in two large dormitories for 3.5 months and a separate isolation suite containing a student who had tested positive for COVID-19. We developed novel techniques employing four methods to collect air samples: Filter Cassettes, Button Sampler, BioSampler, and AerosolSense sampler combined with direct qRT-PCR SARS-CoV-2 analysis. RESULTS: For the two large dorms with the normal student population, we detected SARS-CoV-2 in 11 samples. When compared with student nasal swab qRT-PCR testing, we detected SARS-CoV-2 in air samples when a PCR positive COVID-19 student was living on the same floor of the sampling location with a detection rate of 75%. For the isolation dorm, we had a 100% SARS-CoV-2 detection rate with Aerosol Sense sampler. CONCLUSION: Our data suggest air sampling may be an important SARS-CoV-2 surveillance technique, especially for buildings with congregant living settings (dorms, correctional facilities, barracks). Future building designs and public health policies should consider implementation of HVAC surveillance. Results: For the two large dorms with the normal student population, we detected SARS-CoV-2 in 11 samples. When compared with student nasal swab qRT-PCR testing, we detected SARS-CoV-2 in air samples when a PCR positive COVID-19 student was living on the same floor of the sampling location with a detection rate of 75%. For the isolation dorm, we had a 100% SARS-CoV-2 detection rate with Aerosol Sense sampler. Conclusion: Our data suggest air sampling may be an important SARS-CoV-2 surveillance technique, especially for buildings with congregant living settings (dorms, correctional facilities, barracks). Future building designs and public health policies should consider implementation of HVAC surveillance. • HVAC air sampling was performed in a multi-floor student dorm to detect SARS-CoV-2. • Three out of four air sampling methods with qRT-PCR analysis detected SARS-CoV-2. • We detected SARS-CoV-2 in multiple air samples and correlated with clinical testing. • HVAC air sampling provides surveillance for subclinical COVID infection detection. • HVAC air sampling may be used to prevent and control disease spread. Keywords: SARS-CoV-2, COVID-19, HVAC air sampling, student dorms, qRT-PCR analysis, coronavirus The COVID-19 pandemic caused institutions and universities worldwide to shut down and move to online models during Spring 1, 2 . However, online models established due to emerging circumstances are different from traditional online teaching models and in-person interactions 3 . Pandemic distance work and online teaching presented educational challenges and effects on mental health due to isolation and lack of social interaction 1, 4, 5 . Businesses and college campuses put mitigation methods into practice, including wearing masks, social distancing, isolation and contact tracing, and hand and surface sanitizing [6] [7] [8] . In addition, various surveillance methods were developed, including quantitative detection of SARS-CoV-2 in wastewater from student dorms 9 . For example, the University of Arizona 10 implemented a surveillance program that successfully contained campus outbreaks using wastewater sampling and nasopharyngeal swab sample testing. In order to keep the campus open and detect any virus before widespread transmission could occur, we investigated SARS-CoV-2 detection in air samples from HVAC systems inside student dorms, since the virus is known to spread in the air 11 . SARS-CoV-2 airborne detection inside buildings is a challenge, and researchers are actively pursuing different air sampling methods 12 . Air samples may be collected using several filters and devices, and the virus can be detected by reverse transcriptase quantitative polymerase chain reaction (qRT-PCR). Borges, et al. 13 reviewed some SARS-CoV-2 air sampling methods in indoor settings and highlighted the efficacy of each method based on positive detected samples. Chia, et al. 14 , Kenarkoohi, et al. 15 , and Zhu, et al. 16 performed air sampling in COVID-19 infection isolation rooms with solid and liquid collections. These studies used primers to detect different gene sequences using different amplification kits and showed that detecting COVID-19 in air samples in clinical settings may provide random and unreliable results. Further research should be conducted in this area. In addition, there are no reports of sampling air directly from the HVAC system to perform surveillance for COVID inside a large building. We report here the successful detection of SARS-CoV-2 in student dorm HVAC air samples by qRT-PCR. The study was conducted in two parts 1) a 3.5-month period that represented air sampling inside HVAC of two dorms without specific knowledge of a COVID-19 case; and 2) air sampling from HVAC associated with a suite containing one student who tested positive for COVID-19 by nasal swab RT-PCR. Two student dorms were selected for the current study, designated here as Dorm1 and Dorm2. The HVAC floor plan for Dorm1, where sampling was performed, is shown in Figure S1 in the Supplemental Material, where Dorm2 has a similar layout. The buildings have five floors and contain 225 rooms each, including student units, offices, common bathrooms, professional staff apartments, and storage units. In addition, Dorm1 and Dorm2 are connected on the second floor with an indoor hallway bridge. These two buildings were chosen for monitoring where the return air inside the HVAC system for all the rooms is connected at one location inside locked mechanical rooms. We chose sampling locations in the mechanical room before the air passes through multiple filters and outside makeup air is added. Sampling inside Dorm1 and Dorm2 was conducted during the Spring semester from January 19 to April 29, 2021, except for the week between March 1 to 5, because we had a COVID case in the lab and were required to quarantine. By early March, there were few COVID-19 cases in the surrounding county (see Supplemental Material Figure S2 ), and on campus, so we selected the isolation dorm to collect additional air samples. The dorm contained suites, and each suite contains a common room, a kitchen, and two bedrooms. The HVAC system for each suite was located adjacent to the suite inside a locked mechanical room. The HVAC floor plan for the IsolationDorm, where sampling was performed, is shown in Figure S3 in the Supplemental Material. Therefore, we used different sampling methods for one suite, while a COVID-19 RT-PCR positive student occupied one of the rooms inside the suite. Sampling inside the IsolationDorm was conducted for two weeks, from April 19 to April 29. Four bioaerosol sampling methods were used for this study, three SKC samplers, and one ThermoFisher Scientific sampler. The specifications for the four methods are shown in Table 1 . Methods 1-3 were used at Dorm1, Dorm2, and the IsolationDorm. In late April, we began using an additional collection device, Method 4, which was only used at the IsolationDorm. Methods 1-3 collected air samples from the HVAC system using isokinetic sampling probes inserted inside the duct, and Method 4 used a 3" tube to sample directly from the HVAC system. Different filter types and PBS solutions (dilutions of normal physiologic saline solution, which is defined as 1 x) were tested for Method 3, as shown in Table 2 . Sampling was performed on Monday, Tuesday, and Thursday of each week, beginning at 8 am, and samples were retrieved after 30-min, 90-min, or 24-hrs, depending on the method and filter used. Weekly samples were placed inside test tubes, stored at -20°C, and analyzed by qRT-PCR within 10 days. AerosolSense sampler flow rate was at least 50 times higher than Methods 1 and 2 within the same collection time (24-hrs). The AerosolSense sampler is a new device released in Spring 2021, therefore, the sampling duration was only performed in April. The collection media for Methods 1-4 are listed in Table S1 in the Supplemental Material. For Dorm1 and Dorm2, we used one device for Methods 1-3, with different collection media and sampling times. We performed measurements from the return air of the HVAC system in Dorm1 and Dorm2, as shown in Figure S4 in the Supplemental Material. Liquid from impingers and dry filters were collected in microfuge tubes and stored at -20° C prior to PCR analysis (up to 10 days). On the day of analysis, we added 1 ml of water to the filters 1 hour before the PCR to liberate the samples from the filter. Tubes were vortexed vigorously for 5 seconds, and 16.2 ul of samples were taken from the dirty side of the filter while scraping the filters with the pipette tip gently to use in a 40 uL PCR reaction. Because these samples are dilute and low copy number, viral genome was often detected around 28-30 cycles, but sometimes up to 39 cycles. The campus conducted random and planned COVID-19 testing for students living inside dorms using saliva and nasopharyngeal PCR testing. If the student tested positive, the student was then moved to the IsolationDorm. A total of 41 sampling days were completed at Dorm1 and Dorm2 and 6 days at the IsolationDorm. The number of samples collected for each collection method are shown in dorms, as shown in Table 4 Results reported as "positive inconclusive" were cases where the viral RNA was detected but at such low levels that the software identified the results as "inconclusive". Since our multiple negative controls run each week never return an inconclusive result or any amplification, we believe the "inconclusive" cases are actually detecting quantities of SARS-CoV-2 at the limit of detection. In Shading identifies dates on which a student was PCR positive for COVID by scheduled surveillance testing. The number of floors separating the location where the identified COVID positive student was living, and the sample collection unit are shown. The dates when SARS-CoV-2 was detected both by air sampling and by human clinical testing (saliva or nasopharyngeal PCR testing) are shown in bold in italic. The student in the isolation dorm was only tested once so, a line is shown indicating that the positive test. We successfully detected COVID in 4 of the 14 weeks we collected samples. This suggests that we did not have a high false positive rate in our sampling. Our data suggest the HVAC surveillance is more sensitive when the infected individual is closer to the air sampling location as the HVAC detection correlates with cases detected on the same floor of the sampling location. Presumably, the virus concentration is diluted as it travels through the duct and is combined with clean air from different locations. In addition, it is possible that virus may be deposited on the duct walls. For the two cases identified by nasopharyngeal swab testing on March 16 and April 14, we did not detect SARS-CoV-2 in air samples. There is a possibility that these two We conducted the current study as a cleaner, easier and safer alternative method to the wastewater track tracing method 10 and we have shown that it is possible to detect viruses in HVAC air samples collected at one location from the dorm's return air. It is possible that performing air sampling for SARS-CoV2 on each floor of a large building may yield greater sensitivity. We developed methods for successful detection of SARS-CoV-2 in HVAC air samples. Compared to confirmed cases by human clinical testing, we had a success 20 rate of 75%-100%. HVAC air sampling can be an important surveillance technique for the control of viral spread in large buildings, especially congregant living settings. Such monitoring of air may allow early intervention to stop the spread of SARS-CoV-2 inside buildings. Future building designs should include HVAC access for such sampling, and public health policies should consider implementation of HVAC surveillance testing either routinely or during times of contagion. Our data suggest air sampling at each floor would be beneficial, and that more distant sampling is less sensitive. More frequent sampling would detect the virus more quickly, but this must be balanced against cost and the level of concern for viral transmission at the time. This research did not meet federal definition of Human Subjects research because the research team had no intervention or interaction with human subjects and had no identifiable private information on the specimens, which were collected by housing staff acting as an honest broker. The authors declare no conflict of interest. Covid-19 pandemic and online learning: the challenges and opportunities US Faculty and Administrators' Experiences and Approaches in the Early Weeks of the COVID-19 Pandemic The difference between emergency remote teaching and online learning Stress and coping during COVID-19 pandemic: Result of an online survey Closure of Universities Due to Coronavirus Disease 2019 (COVID-19): Impact on Education and Mental Health of Students and Academic Staff. Cureus Understanding On-Campus Interactions With a Semiautomated, Barcode-Based Platform to Augment COVID-19 Contact Tracing: App Development and Usage College Campuses and COVID-19 Mitigation: Clinical and Economic Value Norwich COVID-19 testing initiative pilot: evaluating the feasibility of asymptomatic testing on a university campus Tracking COVID-19 with wastewater COVID-19 containment on a college campus via wastewater-based epidemiology, targeted clinical testing and an intervention. Science of The Total Environment Viable SARS-CoV-2 in the air of a hospital room with COVID-19 patients Live SARS-CoV-2 is difficult to detect in patient aerosols. Influenza and other respiratory viruses SARS-CoV-2: a systematic review of indoor air sampling for virus detection. Environmental Science and Pollution Detection of air and surface contamination by SARS-CoV-2 in hospital rooms of infected patients Hospital indoor air quality monitoring for the detection of SARS-CoV-2 (COVID-19) virus. Sci Total Environ A Novel Coronavirus from Patients with Pneumonia in China Rapid Preparation of Poxvirus DNA for PCR Cloning and Analysis Rapid preparation of vaccinia virus DNA template for analysis and cloning by PCR Development of improved therapeutic mesothelin-based vaccines for pancreatic cancer Severe acute respiratory syndrome vaccine efficacy in ferrets: whole killed virus and adenovirus-vectored vaccines Poxvirus orthologous clusters: toward defining the minimum essential poxvirus genome Discontinuation of Transmission Precautions for COVID-19 Patients: Polymerase Chain Reaction Diagnostics, Patient Delays, and Cycle Threshold Values. Infectious Diseases in Clinical Practice Surface Environmental, and Personal Protective Equipment Contamination by Severe Acute Respiratory Syndrome Coronavirus From a Symptomatic Patient Exploring Integrated Environmental Viral Surveillance of Indoor Environments: A comparison of surface and bioaerosol environmental sampling in hospital rooms with COVID-19 patients