key: cord-0789198-pk98f1be authors: Hampton, T; Everett, S; Sharma, S; Krishnan, M title: Noise in the operating theatre date: 2021-02-28 journal: Br J Surg DOI: 10.1093/bjs/znab059 sha: 048577d5693977328dc45b8564ac20731bf04c1e doc_id: 789198 cord_uid: pk98f1be nan Healthcare workers have reported difficulties in communicating within operating theatres as a result of using personal protective equipment (PPE) during the COVID-19 pandemic 1 . Here, the noise levels in the local operating theatre environment were assessed following best practice acoustic industry guidelines. Noise is defined by work safety regulations as a sound that may have a negative impact on health (such as impairment of hearing ability) 2 . Noise is reported in the literature with various decibel (dB) weightings. Decibel is not a unit of loudness. It is log base 10 of the sound pressure (measured in pascals). Therefore, decibel is a relative logarithmic ratio to a reference sound level of 0 dB (where the sound pressure is 2 Â10 À5 Pa or 0.000002 Pa), which is also the lowest sound pressure level that can be perceived by average human ears 3 . Where reported in healthcare or acoustic settings, dB is usually accompanied by an 'A' weighting (dBA) to indicate the sound frequency perception of humans. Two meta-analyses 4,5 have offered oversight on operating theatre noise. In 2010, Hasfeldt 4 and co-workers reported on 16 papers assessing theatre noise, with average levels between 51 and 75 dBA, and maximum noise levels between 80 and 119 dBA. focused on measurement techniques rather than outcomes; among 76 studies measuring environmental noise in hospitals since 2008, they found that only 14.5 per cent achieved recommended technical reporting standards. The present study is written in accordance with the Control of Noise at Work Regulations, which came into force for all industry sectors in Great Britain in 2005 2 . The noise level at which employers must provide hearing protection is 85 dB (daily or weekly L Aeq ) and the level at which employers must assess workers' health risk, and provide information and training, is 80 dB 2 . Noise measurements were made using a class 1 integrating sound level meter (Fusion with Pre22 preamplifier and Cal31 calibrator 01dB; ACOEM, France; provided by Hydrock). The sound level meter was calibrated to 94 dB at 1 kHz both before and after the survey. Long-term noise measurements were made at the room perimeter, with a tripod and microphone placed approximately 1.2 m from the floor. Short-term noise measurements were made using class 2 multichannel noise dosimeters (40CD Microphone; G.R.A.S, Denmark; provided by Hydrock). The dosimeters were positioned at mid-chest height on surgeons, anaesthetists and circulating staff. Noise recording took place across 4 consecutive days during October 2020 (total 68 h). The L AFmax (loudest) levels increased significantly with theatre use (Fig. 1) . The in-use L Amax was 100 dB, and the L Aeq,12 h (logarithmic average over 12 h) was between 62 and 64 dB. The L A90 (average over 90 per cent of the time) values ranged from 53 to 54 dB, with a vacant theatre level of 41 dB. All values are comparable with those in existing literature, and Health and Safety Executive standards 2 . Staff dosimeters recorded a mean of þ3 dB experienced by staff during procedures. Therefore, the L Aeq level (or ambient noise) over which staff were communicating was approximately 65 dB. Clarity is required, with reporting of terms such as peak, max, intensity, level, and average, which have explicit acoustic meanings that differ from common usage. The present findings echo suggestions to adopt standardized reporting guidelines for noise in operating theatres 5 . It is recommended that future studies report a minimum data set including L A90 , L Amax , and L Aeq in sound pressure levels (dBA weighting), not intensity. Documentation should report recording equipment manufacturer/model, location, and calibration. Clinician-mounted dosimeters should compare sound levels at the position of staff with central recording levels. An ambient noise L Aeq of 65 dB should be considered for any communication devices or studies as the benchmark noise level over which healthcare staff communication can be assessed in operating theatres, particularly in an era of worsening communication owing to increasing use of PPE. Theatre Comm'-optimising communication in surgical theatres during COVID-19 Noise at work: A Brief Guide to Controlling the Risks Loudness, its definition, measurement and calculation Noise in the operating room-what do we know? A review of the literature Environmental noise levels in hospital settings: a rapid review of measurement techniques and implementation in hospital settings T.H. is supported by a Wellcome Trust grant (unrelated to this research).Disclosure. The authors declare no other conflicts of interest, financial or otherwise.