key: cord-0780111-p8dwutcv authors: Ren, Juan; Wang, Yue; Liu, Qibo; Liu, Yu title: Numerical Study of Three Ventilation Strategies in a prefabricated COVID-19 inpatient ward date: 2020-11-17 journal: Build Environ DOI: 10.1016/j.buildenv.2020.107467 sha: da991982a0431d3d80d76e8f09daf415e2353e41 doc_id: 780111 cord_uid: p8dwutcv Prefabricated inpatient wards have been proven to be an efficient alternative to quickly extend the caring capacity for patients. In this study, three typical ventilation strategies were studied using computational fluid dynamics in a prefabricated Coronavirus disease 2019 double-patient ward. Pollutants are the respiratory droplets and aerosols injected from two manikins. They are modelled as particles with different diameters (3 μm, 6 μm, 12 μm, 20 μm, 45 μm and 175 μm) by the Eulerian–Lagrangian model. Three ventilation strategies with an identical air change rate of 12.3 h(−1) but different layouts of inlets and outlets are implemented. The flow field, flow structures and particle trajectories have been analysed and compared among the three ventilation strategies. The fate of particles is analysed and compared quantitatively. It is found that small particles (<20 μm) can move along with the main flow streams. Most of them are removed by ventilation to the outlet(s). Large particles (>45 μm) cannot move with the flow streams over a long path. Most of them deposit on solid surfaces in different regions of the ward in each ventilation strategy. Health workers should pay close attention to these polluted areas. Targeted cleaning of the polluted areas is necessary in a prefabricated inpatient ward. To promote the removal of some large particles (e.g., 45 μm) by the outlet(s), the outlet(s) should be installed inside the landing area of large particles and close to the polluted source(s). Due to the circumstances of the Coronavirus disease 2019 (COVID- 19) , prefabricated health care facilities are in urgent need to combat the coronavirus. The modular construction of prefabricated health care facilities demonstrates a high degree of composability and replicability. As a result, it is an efficient alternative to meet patients' emergency needs in COVID-19 outbreak areas. In prefabricated infectious health care facilities, isolation wards are the main therapeutic space. Due to the limited space size of prefabricated wards and strong infectiousness of coronavirus, the ventilation strategy should be carefully designed for prefabricated COVID-19 inpatient wards. As reported by the World Health Organization on 9 July 2020 [1] , coronavirus is primarily transmitted between people through respiratory droplets (>5-10 μm in diameter) and contact routes [2] [3] [4] [5] [6] . Some recent publications indicate that COVID- 19 J o u r n a l P r e -p r o o f aerosols (<5 μm in diameter) [7] [8] . Both respiratory droplets and aerosols can survive in air for a certain time and move with the air flow for a certain distance. Sufficient evidence has demonstrated the association between ventilation strategies and dissemination of nosocomial pathogens in wards [9] . Since a large number of nurses have been infected while providing health care for COVID-19 patients [10] , the ventilation strategy in a COVID-19 isolation ward must reduce the infection risk as much as possible. In addition, providing good ventilation and air quality in a ward is not only critical for inpatients' health but also important for nursing work. COVID-19 inpatient wards are expected to have better and stricter ventilation strategies than general hospital wards. When patients are coughing or sneezing, the droplets containing pathogens can be sprayed as air jets with velocities greater than 11 m/s [11] [12] . These pathogens can spread in the air and deposit on the surface of nursing equipment or on the floor close to the entrance door. This is very dangerous for the working doctors and nurses. Because of the outbreak of the COVID-19 pandemic, these health workers suffer from a shortage of personal protective equipment (PPE) [13] . Poor ventilation strategies in general hospital wards amplify the infection risk. It is widely assumed that increasing the air change rate (ACH) can reduce the infection risk. However, some researchers have reported that the infection risk could increase with increasing ventilation rates due to an inappropriate ventilation strategy [14] [15] . Hence, several studies have emphasized the ventilation strategy as a determinant controlling contaminant flow paths [16] [17] [18] . Compared to general hospital wards, COVID-19 inpatient wards have their special requirements of ventilation systems. The COVID-19 inpatient ward should have negative pressure in an isolation room. The minimum air change should be over 12 per hour [19] . The isolation room should be well sealed. The doors should be self-closing. The windows are normally sealed in a prefabricated hospital. The outlets in the ward should have air filtration systems. The ideal ventilation strategy shall supply a mass of fresh air to health care workers and collect pathogens at the outlets in the ward. The pathogens can be collected and well-disposed in the air filtration system. In the engineering field, the airborne transmission between occupants indoors is usually investigated using both experiments and Computational fluid dynamics (CFD) methods [20] . Experimental methods include quantitative measurement of the concentration field [21] [22] and imaging visualization of expiratory flows [11] [12] . Chamber experiments using breathing J o u r n a l P r e -p r o o f thermal manikins and ancillary machines [23] [24] have been the primary method of investigating airborne transmission between occupants and quantifying the risk of cross-infection. In general, chamber experiments can provide reliable results since they take full account of the indoor aerodynamics of real ventilation flows and tracer gas/particles. Liu et al. [25] studied the boundary conditions and flow fields in the first-class cabin of a functional MD-82 commercial airliner. Their results can provide high quality data for validating CFD models. In recent study, Liu et al. [26] developed fast fluid dynamics with the Markov chain method to model the transient particle transport in transient indoor airflow. With this new method, the computational time was 7.8 times less than that of the CFD + Eulerian method. Bolster and Linden [27] focused on transient contaminant transport by modelling three transient contamination scenarios, namely, the so called 'step-up', 'step-down', and point source cases. They found that, on average, traditional and low-energy systems can be similar in overall pollutant removal efficiency. Zhang et al. [28] injected a large number of newly created nano-particle aggregates into a chamber for the purposes of removing harmful contents in an indoor environment. With the development of computational techniques, CFD has been increasingly used in the analysis of indoor environments. In CFD simulations, the airflow in a room is generally described mathematically by a set of coupled differential equations, known as the Navier-Stokes (NS) equations. These equations can be solved directly only at a very low Reynolds number. For the general flow, e.g., in a ventilated room, it is necessary to employ turbulence models, such as k-ε, k-ω, and v2-f models and many other models. J o u r n a l P r e -p r o o f [48] conducted an experimental and numerical study on particle distribution in a two-zone chamber. Chen et al. [49] Lagrangian multiphase analysis according to the characterizations of coughing [12] . During the post-processing, airflow velocities, air temperatures and airborne contaminant distributions are analysed and compared with each other. The predicted fate of particles is studied and analysed quantitatively. In this study, the airflow movement and the airborne transmission in the ward are investigated using an open-source CFD code (OpenFOAM v1906) [55] . The SprayFoam solver is modified and used to simulate the particle (respiratory droplets and aerosols) injection in a three-dimensional compressible turbulent non-reaction flow. (The chemistry and combustion components have been deactivated in the running simulations.) To investigate the dispersed flow of inert particles, the numerical simulation employs an Eulerian-Lagrangian model that includes a continuum phase (air) and a discrete phase (particles). In an Eulerian-Lagrangian model, the governing equations for the continuum (fluid) phase are based on an Eulerian framework, and the discrete (particle) phase is modelled by a Lagrangian framework [56] . The mass and momentum transport equations in the fluid phase can be simply described by the Reynolds-averaged Navier-Stokes (RANS) equations. In RANS equations, the Reynolds stresses are commonly modelled using an eddy-viscosity approach. According to Zhang's study and summary [36] , the RNG k-ε model works well within forced convection and mixed convection cases. Hence, the RNG k-ε model is adopted in running the simulations. However, turbulence modelling will be still verified and validated by benchmark cases in the next section. For the dispersed phase, the particle motion is solved by integrating the force balance in a Lagrangian frame. In this study, the particles (respiratory droplets and aerosols) are very small compared to the ward length and their concentration is not very high in coughs. Therefore, the particles are modelled as spherical, with no heat and mass transfer balls. According to studies by Chao [11] and Bourouiba [12] , the particle (respiratory droplets and aerosols) density is 993 kg/m -3 . The measured diameters of these particles range from 3 μm to 750 μm [11] . Hence, the particles can be modelled as the following equations: where is the particle velocity and is the particle mass. The term is the drag force, is the buoyancy force and is the gravitational force. The particle trajectory is controlled by these forces. The drag force implemented in SprayFoam can be described as follows: J o u r n a l P r e -p r o o f where & is the particle diameter and ! is the drag coefficient. According to Crowe's book [57] , the drag coefficient ! is a function of the particle's Reynolds number '( and is calculated as given below: The buoyancy and gravitational force are calculated as follows: where > is the gravitational acceleration and the value is 9.81 m/s -2 . In particle-laden simulations, the dispersed and continuous phases should be well coupled. The coupling scheme is decided by the volume fraction of the particles according to Backhander's study [58] . According to the studies of Chao [11] and Bourouiba [12] , the volume fraction of the particles is low in coughs. Therefore, in this study, the particles are considered to be moving in diluting flows. In such a case, the particle's motion is primarily influenced by the aerodynamic forces acting on the particle. The particle-particle interactions and the effect of the dispersed phase on the fluid flow are negligible. Hence, a one-way coupling scheme is sufficient to model the fluid flow's influence on the dispersed phase. The integration of particle trajectories from Equations (1) to (4) requires information about the instantaneous fluid velocity (u = u + ? ). However, there is only Reynolds-averaged velocity (u) in the RANS equations. Therefore, the fluctuating velocity ? has to be estimated in order to model the turbulent dispersion of the particles by either stochastic or deterministic methods. In SprayFoam, the stochastic eddy lifetime method is applied, which is also referred to as a where @ is a normally distributed random number, d is a random vector to depict the spatial randomness of turbulence, and the remainder of the right-hand side is the local RMS value of the velocity fluctuations. Since the kinetic energy of turbulence is known when using the RNG k-ε model, these values of the RMS fluctuating components can be defined (assuming isotropy) as The SprayFoam is a pressure-based solver using a finite volume method to discretize the NS equation. The pressure-velocity coupling is accomplished with the SIMPLE algorithm [55] . A bounded second order upwind scheme is used for the advection terms. Discretized equations are solved with the geometric algebraic multigrid (GAMG) method in conjunction with the Gauss-Seidel solver. Three benchmark experimental cases from Wang and Chen were chosen for verification and validation [33] . Case 1 is an isothermal forced convection case in an empty room, as shown in There is an exhaust slot located near the floor on the right wall. The exhaust slot has a height of 0.08 m. In the simulations, the exhaust slot is set as the pressure outlet at one standard atmospheric pressure (1 atm). As stated by Wang and Chen [33] , the model room is built using insulation materials. Hence, the wall boundaries with the exception of the heated box are approximated to adiabatic walls in the simulations. Chen's article [33] , the coarse grid in our simulations is finer than the finest grid in their study. The fine grid in our simulations has a grid resolution close to 0.01 m in the main flow domain. Compared to the grids in Wang and Chen's article [33] , the coarse grid in our simulations is finer than the finest grid in their study. The fine grid in our simulations has a grid resolution close to 0.01 m in the main flow domain. In Wang and Chen's work, they measured ten probe lines (positions) on two sections (see Fig. 1 ). One section was the cross-plane perpendicular to the inlet and exhaust slots (z-axis). The [33] . Red solid lines denote the simulation results using the fine grid. Red dot dash lines denote the simulation results using the moderate grid. Red dash lines denote the simulation results using the coarse grid. Magenta dash lines denote the simulation results using the same RNG k-ε model in reference article [33] ). (a) Velocity profiles at position 5 that had the worst prediction in reference article [33] . (b) Velocity profiles at position 6 that had an average prediction in reference article [33] . (c) Velocity profiles at position 10 that had the best prediction in reference article [33] . To verify the grid sensitivity in our simulations, their experimental data and simulation results using the RNG k-ε model are used in the comparison with our simulation results (see Fig. 3 and As introduced by Wang and Chen [33] , the heated box in Case 3 is equivalent to the reasonable amount of heat generated by 10.5 passengers. Case 3 was designed to study the influence of thermal buoyancy flow in a room with a forced convection. It is same as the flow pattern in a ward. Therefore, Case 3 would be more appropriate than the Case 1 for the validation of our study. In can be found in Chao and Wan's article [54] . In this validation, droplets of 87.5 μm and 137.5 μm are adopted as injection particles. In this study, both respiratory droplets and aerosols are modelled as injected particles with different diameters. On the basis of experimental observations on coughing [11] [12] , a cone injector model is used to make sure that coughing flow is simulated correctly. In Chao's [11] experiments, the average expiration air velocity was 11.7 m/s for coughing. In Bourouiba's [12] study, the average coughing velocity was measured to be 11. In ventilation strategy I, both the inlet and the outlet are located in the same sidewall at z=0 m. The inlet locates on the upper left corner. The outlet locates on the lower right corner. The contaminated air is pumped out from the outlet with a uniform speed of 1 m/s. The fresh air is supplied from the inlet due to the negative pressure circumstance in the ward. As can be observed in Fig. 10 (a) , the inlet flow is sucked into the ward and resembles a jet that is normal to the sidewall. The inlet flow is colder than the air in the ward, see Fig. 10 Fig. 10 (e)). As a result, the temperature field is divided into two regions. The temperature in the region above the patients is clearly higher than the temperature in the region below patients. The flow field above the patients is quite steady. In such a steady flow field, the respiratory droplets and aerosols would remain in suspension in the air for a long time. The contaminated air cannot be refreshed in time. As reviewed in reference article [20] , the spread of droplet nuclei between occupants of the same indoor space is strongly influenced by the complex interaction of ventilation flow, body plumes, and respiratory flow (coughing flow in this study). Though ventilation is widely recognized as the most conducive to engineering methods for controlling airborne transmission indoors [9] [61] [62] , the body plumes and the coughing flow may also have important roles. In this study, the characterizations of actual coughing flow [11] [12] are employed. The boundary conditions of injected flow have been introduced in the case description. Fig. 11 shows the validation of coughing flow. The selected coughing flow is on the cross-section of patients' mouths (see the left figure in Fig. 11 ). The initial speed of coughing flow is 11.7 m/s. This illustrates that the boundary conditions are loaded correctly for particle movements in the simulations. The coughing flow is a cone. The opening angle is 23° in the right figure of Fig. 11 . Fig. 14(a) , the coloured balls denote the particles and the grey curves denote the trajectory of each particle. When the particles fall on any solid surface, they will disappear but their trajectories will be retained, for example, in Fig. 14 In ventilation strategy I, the main flow structures can be assessed in Fig. 13 . Fig. 13 (a) is the superimposed streamlines of the three main flow structures, which can give an overall view of the three flow structures. To show the main flow structures more clearly, Fig. 13 (b) gives the streamlines seeded from the inlet to the outlet, Fig. 13 (c) gives the streamlines seeded from the mouth of patient 1, and Fig. 13 (d) gives the streamlines seeded from the mouth of patient 2. As can be found in Fig. 13 (b) , the inlet flow is sucked into the ward and forms a jet-like flow. The ventilation strategy II, these two coughing jet flows in ventilation strategy I incline slightly to the outlet. This is due to the main stream of the inlet flow. As seen in Fig. 13 (c) , the coughing jet flow from patient 1 diffuses similar to a cloud near the ceiling. The speed of this coughing jet flow decreases nearly to zero. Some of the coughing cloud is involved in the inlet flow. Some of the coughing cloud goes to the outlet. As seen in Fig. 13 (d) , the coughing cloud from patient 2 is also involved in the inlet flow as a "U" type of structure. Particle trajectories in ventilation strategy I are shown in Fig. 14 . In Fig. 14(a) , the particle diameter is 3 μm. There are 19 coloured balls, which is less than the injected 20 particles. Hence, one particle has fallen on a solid surface. Observing the particle trajectories one by one, we can find this particle has fallen on the outlet and disappeared. As seen in Fig. 14 (a) , these particles move along with the main flow structures. When they are sprayed in the mouths of the two patients, they follow the coughing jet flow and will be curled near the ceiling. When they move inside the coughing cloud, they will be involved in the main stream of the inlet-outlet flow. In Fig. 14 (b) , the particle diameter is 6 μm. The particle trajectories in Fig. 14 (b) are similar to Fig. 14 (a) . However, there are 17 coloured balls shown in Fig. 14 (b) , which means three particles have fallen on a solid surface and disappeared. In Figs. 14 (c) and (d), the particle diameters are 12 μm and 20 μm, respectively. Their particle trajectories look similar to each other. The particle trajectories form a "U" type of shape following the main stream of the inlet-outlet flow. However, there are only 14 coloured balls in Fig. 14 (d) , which is much less than that in Figs. 14 (a), (b) and (c). In Figs. 14 (e) and (f), the particle diameters are 45 μm and 175 μm, respectively. There are no coloured balls found in Figs. 14 (e) and (f). The particles are too large to move with the main flow structures. Due to gravity, the particles have fallen down. In Fig. 14 (e) , the particles have fallen down on two zones. One zone is the region between patient 1 and the sidewall at z=0 m. The other zone is the region between the two patients. In In ventilation strategy II, the main flow structures can be seen in Fig. 15 . Fig. 15(a) shows the superimposed streamlines of the three main flow structures. Fig. 15(b) gives the streamlines seeded from the inlet to the outlet. Fig. 15(c) gives the streamlines seeded from the mouth of patient 1. Fig. 15 (d) gives the streamlines seeded from the mouth of patient 2. In ventilation strategy III, the main flow structures (see Fig. 17 ) are quite different from the ventilation strategies I and II. As shown in Fig. 17(b) , the inlet flow is sucked into the ward from the ceiling to the ground. When the inlet flow hits the ground, it scatters to the surroundings. Because the inlet flow is colder than the original air, the inlet flow diffuses on the ground and has less effect on the two coughing jet flows. The inlet flow moves under the bed and exits from the two inlets. In Fig. 17(c) , the coughing jet flow of patient 1 sprays vertically to the ceiling and scatters similar to a coughing cloud. Most of the coughing cloud diffuses to the sidewall z=0 m. A small part of the coughing cloud is involved into the inlet flow. In Fig. 17(d Particle trajectories in ventilation strategy III are shown in Fig. 18 . The trajectories of small (< the particles meet the sidewalls and change their directions to the ground. Some of them change their direction back to the patients. Some of them are involved in the inlet-outlet flow. In Fig. 18 (e), the particle diameter is 45 μm, and the particles are sprayed for certain height. Then, they fall onto the solid surface and disappear. Their trajectories appear to be an umbrella. They fall onto the bed, the outlet and the ground near the patients' heads. In Fig. 18 (f) indicates that when particle diameters are large enough, the injected particles deposit near the patients mouths. In summary, for the large particles (>45 μm), the number of particles removed by deposition are much greater than by ventilation to the outlet(s). There are four limitations in the current study. The first limitation is the modelling of respiratory droplets and aerosols. Because this research focuses on the ventilation strategies, the respiratory droplets and aerosols are not accurately simulated. The complicated vapour liquid phase change is not included in the study. The particle-particle interactions are neglected. The second limitation is the setting of coughing process. Since it is more meaningful to obtain a general consideration of ventilation study, the disorderly unsteady coughing processes of different patients are not considered in the study. The individual differences of distinct patients are not considered in the model of coughing processes. The coughing process is simplified as a continuous inlet flow. The injected flow and particle's data come from the experimental data proposed by Chao [11] and Bourouiba [12] which represents averaged results of diverse people. The manikin models used in this study are rough. This is the third limitation in this study. The body plumes are quite weaker than the coughing flow and the ventilation flow (Fig. 12 ). This study focuses on the airborne transmission under different ventilation strategies but not the thermal comfort or the cross-infection of the two patients. Hence, the manikin models are simplified without unnecessary details. The prefabricated COVID-19 inpatient ward is used to isolate and cure COVID-19 patients with mild cases. It is normally not used for intensive care unit (ICU). Due to highly contagious of coronavirus, health care workers are not encouraged to stay in the COVID-19 inpatient ward for a long time. Hence, the additional presence of nurses and doctors are not considered in this study. The conclusion of this study is not applicable for ventilations in ICU cases. This would be the fourth limitation of the current study. In this paper, a comparative study of three different ventilation strategies in a prefabricated J o u r n a l P r e -p r o o f double-patient ward has been provided. Three ventilation strategies have an identical air change rate of 12.3 h-1 . This air change rate satisfies the requirement (>12 h -1 ) of COVID-19 inpatient wards [19] . Flow structures and the respiratory droplets and aerosols have been analysed and compared among the three ventilation strategies. The predicted fate of particles is listed and compared quantitatively in a table among the three ventilation strategies. Ventilation strategy I has the inlet and outlet on the same sidewall. This kind of inlet-outlet layout forms a "U" type of structure which can include a large air motion in the ward. In ward, ventilation strategy I has the best removal efficiency of small particles. When particle diameters are larger than 45 μm, the respiratory droplets cannot move with the flow structures for a long path. Most of these large particles fall onto solid surfaces in different regions of the ward. In ventilation strategy I, the particles fall onto the solid surfaces near the patients' heads, the corridor between the two patients and the region near the outlet. In ventilation strategy II, the particles have fallen on the solid surfaces near the patients' head, the ground between the two patients and the region between patient 2 and the sidewall z = 6 m. In ventilation strategy III, the particles fall onto the bed, the outlet and the ground near the patients' heads. Hence, health workers should pay more attention to these contaminated areas. Targeted cleaning on the polluted areas is necessary in a prefabricated inpatient ward. A correct layout of the outlet(s) can highly promote the removal of some large particles (e.g., 45 μm). In ventilation strategy II, the outlet is installed in the opposite direction of landing particles. None of the 45 μm particles are removed by the outlet. In ventilation strategy III, the outlets are installed in the landing area of large particles and close to the polluted source(s). Therefore, 18.1% of the 45 μm particles can be collected by the filtration systems and removed by the exhaust outlets. World Health Organization. Transmission of SARS-CoV-2: implications for infection prevention precautions Community transmission of severe acute respiratory syndrome coronavirus 2 A familial cluster of pneumonia associated with the 2019 novel coronavirus indicating person-to-person transmission: a study of a family cluster Early transmission dynamics in Wuhan, China, of novel coronavirus-infected pneumonia Clinical features of patients infected with 2019 novel coronavirus in Wuhan Active monitoring of persons exposed to patients with confirmed COVID-19 -United States COVID-19 may transmit through aerosol Aerosol and Surface Stability of SARS-CoV-2 as compared with SARS-CoV-1 Role of ventilation in airborne transmission of infectious agents in the built environment-A multidisciplinary systematic review World Health Organization. WHO calls for healthy, safe and decent working conditions for all hea lth workers, amidst COVID-19 pandemic Characterization of expiration air jets and droplet size distribution immediately at the mouth opening Violent expiratory events: on coughing and sneezing World Health Organization. Shortage of personal protective equipment endangering health workers worldwide Exposure of health care workers and occupants to coughed airborne pathogens in a double-bed hospital patient room with overhead mixing ventilation Adequacy of air change rate as the sole indicator of an air distribution system's effectiveness to mitigate airborne infectious disease transmission caused by a cough release in the room with overhead mixing ventilation: A case study Assessment of health-care worker exposure to pandemic flu in hospital rooms Human convection flow in spaces with and without ventilation: Personal exposure to floor-released particles and cough-released droplets Role of air changes per hour (ACH) in possible transmission of airborne infections World Health Organization, Infection prevention and control during health care when novel coron avirus (nCoV) infection issuspected Airborne spread of expiratory droplet nuclei between the occupants of indo or environments: A review Effects of air exchange rate, particle size and injection place on particle concentrations within a reduced-scale room Ventilation rates and airflow pathways in patient rooms: a case stu dy of bio-aerosol containment and removal Measurement and prediction of indoor air quality using a breathing the rmal manikin An experimental study quantifying pulmonary ventilation on inhalation of aerosol under steady and episodic emission Accurate and high-resolution boundary conditions and flow fields i n the first-class cabin of an MD-82 commercial airliner Modeling transient particle transport in transient indoor airflow by fast fluid dynamics with the Markov chain method Particle transport in low-energy ventilation systems. Part 2: Transients and experiments Transient Response of Particle Distribution in a Chamber to Transient Particle Injection Experiments on turbulent natural convection in an enclosed tall cavity Confined turbulent mixed convection in the presence of a horizontal buoyant wall jet. Fundamentals of Mixed Convection Model experiment of flow and temperature field in room for validating numerical simulation analysis of newly proposed ventilation effectiveness Measurement of turbulence statistics in a model fire room by LDV Assessment of Various Turbulence Models for Transitional Flows in an Enclosed Environment (RP-1271) Verification and validation in computational science and engineering Evaluation of various turbulence models in predicting airflow and turbulence in enclosed environments by CFD: part-1: summary of prevalent turbulence models Evaluation of various turbulence models in predicting airflow and turbulence in enclosed environments by CFD: part-2: comparison with experimental data from literature CFD simulation of stratified indoor environment in displacement ventilation: Validation and sensitivity analysis Prediction of Indoor Conditions and Thermal Comfort Using CFD Simulations: A Case Study Based On Experimental Data Modeling of gasper-induced jet flow and its impact on cabin air quality Validation and assessment of the CFD-0 module of CONTAM software for airborne contaminant transport simulation in laboratory and hospital applications CFD simulations of mixing ventilation at low Reynolds numbers: effect of spatial discretization scheme On the boundary conditions of numerical particle simulation in indoor environment Numerical modeling of volatile organic compound emissions from ozone reactions with human-worn clothing in an aircraft cabin A modified Brownian force for ultrafine particle penetration through building crack modeling Contaminant flow in the microenvironment between people under different ventilation conditions Distribution of exhaled contaminants and personal exposure in a room using three different air distribution strategies Modeling particle dispersion and deposition in indoor environments Experimental and numerical study on particle distribution in a two-zone chamber Comparing the Markov Chain Model with the Eulerian and Lagrangian Models for Indoor Transient Particle Transport Simulations Influence of movements on contaminant transport in an operating room Impact of moving objects on contaminant concentration distributions in an inpatient ward with displacement ventilation Development of ventilation design strategy for effective removal of pollutant in the isolation room of a hospital A numerical study of ventilation strategies for infection J o u r n a l P r e -p r o o f risk mitigation in general inpatient wards A study of the dispersion of expiratory aerosols in unidirectional downward and ceiling-return type airflows using a multiphase approach OpenCFD-OpenFOAM-Official Home of the Open Source Computational Fluid Dynamics (CFD) Toolbox Discrete particle simulation of particulate systems: Theoretical developments Multiphase flows with droplets and particles A scaling analysis for point-particle approaches to turbulent multiphase flows A calculation procedure for heat, mass and momentum transfer in threedimensional parabolic flows Flow dynamics and characterization of a cough Removal of exhaled particles by ventilation and deposition in a multi-bed airborne infection isolation room Risk of cross-infection in a hospital ward with downward The authors are grateful for the support by the virtual simulation experiment teaching project of Chang 'an University and the fundamental research funds for the central universities, CHD (No. 310841151099).