key: cord-0774310-782yful2 authors: Feng, Zhuangbo; Cao, Shi-Jie; Haghighat, Fariborz title: Removal of SARS-CoV-2 using UV+Filter in built environment date: 2021-08-03 journal: Sustain Cities Soc DOI: 10.1016/j.scs.2021.103226 sha: b98aa4bc807d3431c5113a622b454eca2e3d1205 doc_id: 774310 cord_uid: 782yful2 Air cleaning is an effective and reliable method in indoor airborne SARS-CoV-2 (Severe Acute Respiratory Syndrome Corona-Virus 2) control, with ability of aerosol removal or disinfection. However, traditional air cleaning systems (e.g. fibrous filter, electrostatic removal system) have some risks in operation process, including re-aerosolization and electric breakdown. To avoid these risks, the current study proposed an UV+Filter (ultraviolet and fibrous pleated filter) system to efficiently capture airborne SARS-CoV-2 aerosols and deactivate them in filter medium. It is challenging to quantitatively design UV+Filter due to complex characteristics of SARS-CoV-2 aerosols (e.g. aerodynamic size, biological susceptibility) and hybrid filtration/disinfection processes. This study numerically investigated the overall performances of different air cleaning devices (e.g. Fibrous-filter, UV+Filter, two-stage ESP (electrostatic precipitator) et al.) for control of SARS-CoV-2 aerosols and compared them in term of filtration efficiency, energy consumption and secondary pollution. The prediction of developed models was validated with the experimental data from literature. UV+Filter is the most reliable and safest, while its energy consumption is highest. The newly proposed design method of air cleaning systems could provide essential tools for airborne diseases control. The current outbreaks of corona-virus disease 2019 , induced by severe acute respiratory syndrome corona-virus 2 (SARS-CoV-2), have yet caused severe threats to global health and economy (Rahman et al., 2020; Wang, 2021; Xu et al., 2020; Beria & Lunkar, 2020; WHO 2020; Hosseini et al., 2020) . Reported transmission pathways of SARS-CoV-2 include: 1) direct inhalation of droplets produced by infected persons; 2) close contact with infected persons; 3) contact with polluted surfaces Loey et al., 2020) . Moreover, aerosol transmission of pathogens has been proven as an important pathway based on the recent research (Buonanno et al., 2020; Zhao et al., 2020; Liu et al., 2020) . Airborne precautions of SARS-CoV-2 have been adopted by public organizations and health authorizes (WHO 2020; CDC 2019; NCCEH 2020). For control of airborne transmission in indoor environment, ventilation and air purification are two effective ways (Cao & Ren, 2018; Correia et al., 2020; Yeo et al., 2020; Leng et al., 2020; Yüksel et al., 2020; Buonanno et al., 2020; Bhattacharyya et al., 2020; Ding et al., 2020) . However, if ventilation and air purification systems are not properly designed or operated, they may contribute to the transmission/spreading of airborne diseases and heat/moisture in indoor environment (Correia et al., 2020; . This could be the case when the filtration system cannot efficiently remove the aerosols before being mixed with supply air, resulting in accelerating the spread of virus in the indoor environment. Besides, aerosols, like SARS-CoV-2, can deposit on duct surfaces, causing resuspension risk of virus. If exhaust ducts are not equipped with air purification devices, SARS-CoV-2 aerosols can be released into atmospheric environment, which may cause a potential threat to the surrounding environment (Correia et al., 2020) . Therefore, air purification system should be effectively utilized in ventilation system to effectively control spread of SARS-CoV-2 aerosols in built environment (Correia et al., 2020; Zhao et al., 2020) . Air cleaning technologies have been proven to be effective methods in indoor air quality control (Charvet et al., 2018; Malayeri et al., 2020; Shyegan et al., 2020; Zhong et al., 2016; Wang et al., 2009; Malayeri et al., 2021) . Recently, extensive research has been conducted to optimize ventilation designs in reference to SARS-CoV-2 aerosols control (Vuorinen et al., 2020 , Leng et al., 2020 . However, available literatures are insufficient to focus on the purification/filtration of SARS-CoV-2. Fibrous filter, electrostatic removal device and ultraviolet germicidal irradiation (UV) are potential devices for SARS-CoV-2 removal/disinfection. The main control mechanism of fibrous filter and UV is physical filtration and biological disinfection, respectively (Velali et al., 2020; Charvet et al., 2018; Saleh et al., 2014; Abdolghader et al., 2018; Yang et al., 2018) . Electrostatic removal devices (e.g. ESP) are able to simultaneously remove the particle as well as deactivate it by ions. The widely used air cleaners (fibrous filter, UV and electrostatic removal devices) have some disadvantages, from the perspectives of SARS-CoV-2 aerosol control. Previous studies reported that fibrous filter (e.g. HEPA, high efficiency particulate air 6 filter) could have ultra-high filtration efficiency for SARS-CoV-2 aerosols (Charvet et al., 2018) . The disadvantages of fibrous filter include high pressure drop, energy consumption and replacement cost (Feng et al., 2016) . Besides, bacterium can propagate in fibrous filter with loaded cake layer, therefore inducing health risk/secondary contamination during maintenance and replacement due to re-aerosolization (Nakpan et al., 2019; Bahrami et al 2020) . UV has been proven to be effective for disinfection of many airborne biological species (Yang, et al., 2019; Yang, et al., 2018) . Many literatures have concluded that UV can effectively inactivate SARS-CoV-2 aerosols deposited on solid surfaces and porous mediums (Fischer et al., 2020; Sarkis-Onofre et al., 2020; Heilingloh et al., 2020) . However, research focusing on UV disinfection of airborne SARS-CoV-2 aerosols and its UV susceptibility is hardly available: without UV susceptibility coefficient, it is difficult to accurately design UV device towards SARS-CoV-2 control. Typical electrostatic removal devices include electrostatic precipitator (ESP) and hybrid electrostatic filtration system (HEFS) combining ESP and fibrous filter in series (Feng et al., 2016; Feng, et al., 2018b) . Earlier studies proved that the well-designed ESP/HEFS could have very high physical filtration efficiency for airborne aerosols (Feng, et al., 2018b) , and ions generated by corona discharge could effectively deactivate biological species (Zhou et al., 2016) . However, the ability of electrostatic devices to remove/inactivate SARS-CoV-2 aerosols has not yet been tested. In terms of control of SARS-CoV-2 aerosols with a high toxicity, the re-aerosolization risk of fibrous filter and electric-breakdown risk of ESP may significantly increase exposure and infection, causing great threat to human safety. Therefore, it is very necessary to develop a safe, reliable and high-efficient air cleaning system towards the control of SARS-CoV-2 aerosols with a high toxicity. To avoid the risks/limitations of widely used air cleaning types, the current study proposed an UV+Filter (ultraviolet and fibrous pleated filter) system to efficiently capture airborne SARS-CoV-2 aerosols and deactivate them by UV lights. It is quite challenging to quantitatively design UV+Filter due to the complex characteristics of SARS-CoV-2 aerosols (e.g. aerodynamic size, biological susceptibility) and multiple-physical phenomena (e.g. porous medium flow, UV irradiance). To accurately simulate its performance, it is urgent to develop a quantitative methodology to analyze multiple-physics fields in UV+Filter and obtain filtration/disinfection efficiency. Beside, there is a need to investigate the performance of UV+Filter and compare its overall filtration performance with various air purification types in term of filtration/disinfection efficiency, energy conservation, and exposure risk. The current study aims to propose an UV+Filter system to high-efficiently remove and disinfect airborne SARS-CoV-2 aerosols. A multiple-physics model (e.g. porous medium flow, UV irradiance, aerosol filtration/disinfection) was utilized to simulate and design UV+Filter system. First, the main characteristics of SARS-CoV-2 aerosols were summarized, including aerodynamic characteristics and susceptibility to UV lights. Next, a multiple-physics model of UV+Filter was developed which included 8 porous medium flow, aerosol filtration/disinfection, and UV dose applied to pleated filter. Then, the numerical model was adopted to properly design the UV+Filter system in order to obtain satisfactory filtration/disinfection performances. Finally, the SARS-CoV-2 aerosol removal/disinfection performance of ESP/HEFS were investigated through numerical simulation while overall filtration performances of different properly design air cleaning types (e.g. selection of fibrous medium, arrangement of discharge wires in ESP/HEFS) were analyzed/evaluated (as shown in figure 1), including energy consumption, secondary pollution generation and operation risk level. The numerical models for UV+Filter system are described and the models of two electrostatic cleaning systems (ESP and HEFS) are then briefly introduced. 2.1 UV+Filter system The UV+Filter system consists of a UV generator (lamp) and fibrous pleated filter in series. The UV light leaving the lamp reaches the pleated filter surface and deactivates SARS-CoV-2 aerosols in the filter medium. Besides, the UV light can also inactivates biological aerosols in air. Numerical models of pleated filter and UV irradiance field were individually described as follows: figure 2 shows the geometry of UV+Filter system, in which UV (ultraviolet germicidal irradiation) lamps and fibrous pleated filter were installed in series. Two cylindrical lamps were placed in duct zone. The diameter of each cylindrical lamp was 10 mm. The width of simulation domain (w 1 ) was 250 mm. The geometry of fibrous pleated filter is shown in figure 3 . In order to increase filtration efficiency, the pleat structure was adopted to effectively enlarge filter surface area and decrease filtration velocity. The aforementioned figure shows that filtration velocity (m/s) is defined as the quotient of airflow rate (m 3 /s) divided by surface area (m 2 ) of fibrous pleated filter. Due to its periodicity, only one pleat was adopted to show its structure. Different boundary types were described in figure 3, including "Inlet", "Outlet", "Symmetry" and "Porous Zone"; two structural parameters, pleat height (H) and pleat distance (D), were also defined. Numerical modeling of fibrous filters consists of two steps: air flow and particle filtration modeling. The filter media was modeled as a porous zone and its permeability constant for a porous medium was calculated by the Carman-Kozeny expression (Feng et al., 2018a) . In the porous zone, source terms (S i ) were added to the momentum equation, as described in equation (1). For the fibrous filter medium, the viscous resistance is dominant and inertial resistance could be ignored. The flow field through the porous filter medium was simulated by solving Navier-Stokes equations with viscous resistance in the porous zone. This study used SIMPLE algorithm (rather than COUPLE algorithm) to couple air pressure and velocity because of the relatively simple pleat structure. Once velocity distributions were obtained, particle trajectory and filtration effect were simulated by the Lagrangian method and filtration efficiency model (as described by equation (2-3) ). Detailed information about fibrous filter modeling could be found in (Feng et al., 2018a) . where u p is the particle velocity vector (m/s), u is the air velocity vector (m/s), t is the time (s), the i represents coordinates (e.g. x, y, z), β is the permeability of porous medium (m -2 ), C 2 is the inertial resistance factor of porous medium (m -1 ), g is the gravitational acceleration (m 2 /s), ρ is the air density (kg/m 3 ), ρ p is the particle density (kg/m 3 ), F D is the inverse of the relaxation time (m -1 ), F a stands for the additional forces (N, such as electrostatic force acting on charged particles), E T is the removal ratio for a certain particle trajectory in one time step, α is the solid ratio of filter medium, eff is the overall single fiber efficiency (including effects of diffusion, interception, impaction and electrostatics), d f is the fiber size, and Z T is the particle trajectory length in one time step. For fibrous filter simulation, C 2 is zero due to the fact that inertial resistance could be ignored. For numerical modeling of fibrous filter, the air temperature and humidity could influence air viscosity, further influence F D (Equation (2) in the modified manuscript) and particle motion/filtration in porous filter medium (Zhao et al., 2010 ). In the current study, room air parameters (25 °C, 60%) were adopted. In our future study, the effects of air temperature/humidity on air filtration will be investigated by using experiments and numerical simulation. The key design parameters of fibrous pleated filter are the mean fiber diameter (d f , µm), the mean packing density (α), and the filter thickness (Z, µm). The index of MERV (Minimum Efficiency Reporting Value) was adopted to classify different types of fibrous air filter (ASHRAE 52.2, 2017) . In this study, five filter types were tested: Filter A ( respectively set as 100 mm and 10 mm. The average filtration velocity was close to 2.5 cm/s, which is in the range recommend by engineering standards (GB/T 13554-2020). Filter A was a high-efficient type, while Filter B/C and Filter D/E were medium-efficient and coarse filter types, respectively. Numerical models were adopted to study the performance of the five filter types from the perspective of SARS-CoV-2 aerosols control. The best type was selected in reference to evaluations of different air cleaning devices. In order to simulate disinfection efficiency of UV+Filter system with cylindrical UV lamp, UV irradiance field should be solved first, based on equation (4). The view factor V i-L is function of L, L N and L X , as described in figure 4 . Detailed formula expression of equation (4) could be found in (Yang et al., 2019) . The influences of UV irradiance field on air flow field are ignored and air momentum equations were directly solved by using CFD (Computational Fluid Dynamics). If fibrous filter was coated with photo-catalytic catalysts (deposited on fiber surface), UV light intensity may begin to attenuate across filter thickness (photon absorption) (Malayeri et al., 13 2021) . Based on previous researches (Malayeri et al., 2021) , UV absorption in fibrous pleated filter (without catalyst) could be negligible. We also utilized experimental method (Yang et al., 2019) to investigate the influences of fibrous filter (Filter A, without catalyst) on UV light intensity in duct system, and the UV absorption in Filter A was negligible. Overall, absorption of UV light in pleated filter without catalyst were assumed negligible in the current study In equation (4), I i is the spatial irradiance for point i (W/m 2 ), f is the efficiency of cylindrical lamp power to be converted into the UV output power, P is the cylindrical lamp power (W), A L is surface area of the cylindrical UV lamp (m 2 ), L L is the length of UV lamp (m), V i-L is the view factor which represents the fraction of radiative energy leaving from viewpoint i and reaching the UV lamp. Once UV irradiation field and turbulent airflow field were obtained, equation (5) was used in order to simulate disinfection efficiency of UV+Filter system. Disinfection efficiency could be determined based on biological particle concentration of where C i is the activated biological particle concentration (N/m 3 ), v si is the particle settling velocity (m/s), u is the air velocity (m/s), t is the physical time (s), D is the Brownian diffusion coefficient (m 2 /s), ε p is the particle eddy diffusivity (m 2 /s), I R is the irradiance intensity (W/m 2 ), A is the susceptibility (disinfection coefficient) due to irradiance intensity (m 2 /J). In the current study, two-stage ESP and HEFS was investigated towards the control of airborne SARS-CoV-2 aerosols. Traditional one-stage ESP, only including ionization stage, was not considered in the current study due to its high ozone generation . The geometry of two-stage ESP is shown in figure 5 . The ionization stage and collection stage were adopted to charge and capture incoming particles/aerosols, respectively. For the ionization stage, the Poisson equation and continuity equation were simultaneously solved to obtain distributions of electric potential and space charge density, as described by equation (6-7). For the collection stage, equation (6) without space charge density (so-called Laplacian equation) was used to simulate electrostatic field intensity. The Lagrangian model (equation (2)), and particle charging model (equation (8)) were simultaneously utilized to simulate particle motion and charging in two-stage ESP and HEFS. , ε 0 is the air permittivity (F/m), and k i is the ion mobility (m 2 /Vs), where q P is the particle charge amount (C), K p is the particle dielectric constant, d p is the particle diameter (m), t is the physical time ( This study also investigated the performance of two-stage ESP with single discharge wire (installed in the central point) in the ionization stage. The applied voltage (V i ) in the ionization stage was 6.5-8.5 kV (positive voltage). The voltage (V c ) between two collection plates was 3 kV. The inlet air velocity of ESP was 1 m/s, as shown in figure 5 . The configuration shown in figure 5 was a system unit of two-stage ESP. In practical conditions, more channels are needed and many units should be added together in order to meet practical requirements. The geometry of hybrid electrostatic filtration system (HEFS), consisting of ionization stage and pleated filter, is shown by figure 6 . The ionization stage of HEFS is the same as that of two-stage ESP. An electrostatic field was added across the thickness of fibrous filter medium. For the ionization stage, numerical models of ionized electric field and particle charging/motion were the same as the two-stage ESP. The Lagrangian model with electrostatic-enhanced single fiber efficiency model were adopted to simulate charged particle removal in the fibrous filter medium (Feng et al., 2018b) . In HEFS, the design parameters of fibrous filters found in literature were used: fiber diameter of 10 µm, solid packing density of 0.1, filter thickness of 2 mm (Feng et al., 2016) . For the filter medium in HEFS, its level was MERV-9 (ASHRAE 52.2, 2017). Pleat height and pleat distance was 100 mm and 22.3 mm, respectively. The average filtration velocity was close to 0.1 m/s, which was higher than that of UV+Filter system (2.5 cm/s, 0.025 m/s). In UV+Filter and HEFS, high-efficient and medium-efficient filters were used respectively. Therefore, the values of filtration velocities were different due to the two different filtration grades. In HEFS, the electrostatic intensity across filter medium thickness was 1.2E+06 (V/m). Two-stage ESP For the UV+Filter system, three dimensional geometry and meshing strategy were utilized (Yang et al., 2018) . The two-staged ESP and HEFS had two dimensional characteristics, and previous study proved that the two dimensional meshing strategy could provide satisfied simulation results (Feng et al., 2018b) . Therefore, two dimensional geometry and meshing strategy were adopted in the current study to investigate the performance of ESP and HEFS. For UV+Filter system, the ANSYS-FLUENT platform was utilized to simulate UV field, turbulent air flow and biological particle disinfection/filtration. User-Defined Functions (UDF) were developed to simulate the distributions of UV irradiance intensity. Figure 7 shows the mesh distributions in XY plane (as described in figure 3 , 5, 6 in this paper). The mesh distributions of XY plane remain the same pattern along Z direction. The hexahedral meshes were used, and total element number was 4.2 million. Local meshing refinement was used in the pleated filter medium zone. Mesh independence test was conducted to ensure reliability. The disinfection efficiency and aerosol concentration approximately remained the same if total element number was refined to 7.4 million and 10.2 million. For two-stage ESP/HEFS system, the COMSOL platform was adopted to simulate corona discharge (ionized electric field), and ANSYS-FLUENT platform was utilized to simulate turbulent air flow and biological particle removal. Figure 7 shows the mesh distributions of HEFS system. The hexahedral meshes were used. Local meshing refinement was adopted around discharge wires and in the pleated filter medium zone. For simplicity, mesh distribution of two-stage ESP was not shown in this paper. The ionization ozone of two-stage ESP was the same to that of HEFS, and the same meshing strategy can be applied. For collection zone of ESP, the structural meshes were applied due to its regular geometry. The boundary conditions for airflow modeling were straightforward: grounded plates, surfaces of discharge wire/UV lamp acted as stationary walls. The "Velocity Inlet" and "Pressure Outlet" types in ANSYS-FLUENT was respectively adopted for inlet and outlet of various system. For biological particle concentration, the dimensional inlet particle concentration (1×10 04 (#/m 3 )) was defined in each case, and "Outflow" type was applied for outlet. The problem of the corona discharge modeling was governed by two partial differential equations with unknown electric potential and space charge density. The boundary conditions for the electric potential were straightforward: a given applied voltage (V P ) on the discharge wires, zero potential on the grounded plates, zero-gradient boundary for surfaces of pleated filter. The Kaptzov hypothesis was used to calculate the boundary value of space charge density over the discharge wires (Admiak, 2013). This study used standard k-ɛ model to simulate air turbulence characteristics, and the SIMPLE algorithm to couple the pressure and velocity. The PRESTO! scheme was adopted for pressure discretization and the first-order upwind scheme for all the other variables. The enhanced wall 20 functions were adopted with standard k-ɛ model since the y+ value was less than 30. The characteristics of SARS-CoV-2 aerosols are necessary for numerical simulation of air cleaning devices. This includes aerodynamic characteristics and susceptibility to UV lights. Figure 8 shows SARS-CoV-2 RNA concentration and aerodynamic size which were measured in Fangcang Hospital . The results indicate that SARS-CoV-2 aerosols were mainly found to include two size ranges, one in the sub-micron region (d p between 0.25 and 1.0 µm) and the other in super-micron region (d p > 2.5 µm). Based on sizes of SARS-CoV-2 aerosols and nature of RNA, the targeted aerosol size range in the current study was 0.1 µm to 2.5 µm. For airborne SARS-CoV-2 aerosols, there was no available experimental data on its susceptibility to UV lights. However, the effects of UV lights on the inactivation of SARS-CoV-2 aerosols deposited on solid surfaces and porous mediums were investigated experimentally (Fischer et al., 2020) . The related experimental data was used in simulation of UV+HEPA system which was described in the following section. . Extensive numerical simulations were performed in order to study the filtration efficiency of the four filters, including: flat fibrous filter (HEPA), ESP, HEFS and UV. Figure 9 compares the experimental and simulated filtration efficiency/disinfection efficiency of four air cleaning devices. The experimental data were based on previous research (Feng, et al., 2018b; Long & Yao, 2010; Yang, et al., 2018) . Figure 9(a) shows that there is agreement in terms of the filtration efficiencies predicted by numerical models and the experimental data. Filtration efficiency of a clean, flat filter was investigated, without considering the particle clogging process. The discrepancies between numerically simulated and experimentally measured data shown in figure 9 (a) resulted from model errors induced by single-fiber efficiency formulas, as reported by (Park et al., 2011) . Figure 9 (b) shows that the numerical model could reasonably predict disinfection efficiency of UV system (Yang et al., 2018) . Staphylococcus epidermidis (ATCC 12228) was the selected bacteria type, with susceptibility of 0.37 (m 2 /J). The disinfection efficiency decreased with increase of inlet air velocity due to different residence time. Figure 9 (c) compares simulated and measured particle removal efficiency of one-stage ESP (Long & Yao, 2010) . Only one discharge wire was installed in ESP channel, and applied voltage varied from 6 kV to 13 kV. The seeded particle had a size of 4 µm. The discrepancies between simulated and experimental efficiency data were caused by errors of particle charging model (Long & Yao, 2010) , which can be used to estimate electric charges carried by particles in ionized electric field. In figure 9 (d), the "electric increase of efficiency" means filtration efficiency difference of fibrous filter in HEFS with/without applied voltage (Feng et al., 2016) . In the numerical simulation of fibrous filter medium in HEFS, only the electrostatic effect of the target single fiber on charged particle motion was considered and the interaction with other charged fibers are ignored. The comparisons in figure 9 indicate that all numerical models could reasonably predict filtration/disinfection efficiency of each air cleaning device type. The validated simulation models were then used for the optimization and design of various air cleaning systems for indoor applications. In UV+Filter system, airborne biological aerosols were treated (remove/disinfect) by three processes: 1) physical capture by fibrous filter due to filtration mechanism, 2) UV disinfection before reaching fibrous filter, and 3) UV dose applied to aerosols deposited in filter medium. These three processes could be analyzed individually because of different physical fields. Firstly, physical filtration performance of UV+Filter system was described. Figure 10 shows the simulated distributions of air velocity in one pleat channel of pleated fibrous filter. The maximum velocity magnitude (1.6 m/s) was observed in the entrance zone, which was higher than the inlet velocity (1.0 m/s). In filter medium, air velocity (so-called filtration velocity) values become much lower due to large area of pleated filter medium. For filters with relatively high viscous resistance, filtration 24 velocities were uniformly distributed along the surface of filter medium. For fibrous filters with a lower flow resistance, filtration velocities varied along the filter surface. Airflow field is the base of particle motion and filtration in filter. Figure 11 shows the simulated filtration performance of the five pleated fibrous filter: Size-dependent filtration efficiency and pressure drop were analyzed and compared. From Figure 11 (a), it can be observed that filtration efficiency was higher for very small (< 0.3 µm) or large (> 1.0 µm) particles. This trend was caused by the phenomena of particle diffusion and interception/impaction effects. Particle diffusion efficiency decreases with particle size while interception/impaction efficiency increases with particle size. For HEPA (Filter A), filtration efficiency was close to 100% for the whole particle size range. The MPPS (most penetrating particulate size) of Filter A was 0.3 µm and its filtration efficiency was 99.58%. For medium filter types, Filter C had a relatively high efficiency. The MPPS value of Filter C and the corresponding efficiency were 0.3 µm and 79.7%, respectively. The quality factor of Filter C was 0.38 which was much higher than that of Filter A (0.006). Quality factor is an index simultaneously integrating filtration efficiency and energy consumption (Feng et al., 2018b) , as shown by equation (9). The overall performance of Filter C is better than Filter A (see Figure 11 (a)). However, Filter C could not be recommended for the removal of SARS-CoV-2 aerosols due to its relatively low efficiency in the particle range of 0.2-0.6 µm (see Figure 11 (a)). SARS-CoV-2 aerosols were mainly found in two size ranges: 1) in submicrometre region (particle size between 0.25 and 1.0 µm) and 2) in supermicrometre region (particle size > 2.5 µm) . Therefore, it is necessary to utilize size-dependent efficiency curve to design fibrous filters in the SARS-CoV-2 control. Overall, pleated fibrous filter is a safe measure to use in ventilation systems for its high efficient removal of SARS-CoV-2 aerosols. where ΔP is the pressure drop across the fibrous filter medium (Pa), Q 0 is the unit air flow volume rate (1 m 3 /s), the eff is the filtration efficiency for 0.3 μm particles. higher efficiency also have higher pressure drop. Filter A has a higher filtration efficiency while its pressure drop is much higher than those of other filter types. Utilization of Filter A (e.g. HEPA) in large quantities may cause considerate energy consumption therefore making it very necessary to develop high efficiency and energy-saving air cleaning devices towards the control of SARS-CoV-2 aerosols. Different from UV and ionized electric field, fibrous filter removes SARS-CoV-2 aerosols by physical filtration mechanisms (diffusion, interception and impaction) without biological disinfection effect. Survival and growth of SARS-CoV-2 in filter medium still remain unclear; some risks exist in the processes of air filter maintenance and replacement (Fischer et al., 2020) . In the event of leakage in the filter medium, SARS-CoV-2 aerosols may penetrate filters and can cause serve danger to building occupants. It is therefore necessary to consider the risks of pleated fibrous filter in the operation process. Figure 12 shows the simulated distributions of irradiance intensity (I R ) in UV+Filter systems. Numerical results indicated that irradiance intensity decreased from lamps to duct surface. For UV disinfection simulation, the most challenging issue is to determine susceptibility "A", as shown in equation (5). Previous research utilized experimental methods to obtain the "A" value of five airborne biological bacteria types (Serratia marcescens, Pseudomonas alcaligenes, Escherichia coli, Salmonella enterica, and Staphylococcus epidermidis), which were exposed to UV light (Yang et al., 2018) . The available literature has not yet reported disinfection experiments of ultraviolet germicidal irradiation on airborne SARS-CoV-2 aerosols in ventilation systems. Therefore, it is quite difficult to directly obtain accurate "A" value from available experimental research, which focused on UV inactivation of airborne SARS-CoV-2. Previous studies made some assumptions regarding an appropriate value of the "A" value in order to investigate the effects of upper-room ultraviolet air disinfection system on the reduction of COVID-19 transmission (Beggs & Avital, 2020) . Based on the published literature regarding UV inactivation of different aerosolised corona-viruses, the range of "A" value was 0.377-0.590 (m 2 /J). If "safety factor" was considered in the analysis, the range of "A" value was expanded to 0.0377-0.590 (m 2 /J) (Beggs & Avital, 2020) . This range of "A" value (0.377-0.590 (m 2 /J)) was adopted in simulation of COVID-19 disinfection by using upper-room ultraviolet air disinfection system (Beggs & Avital, 2020) . Based on previous study, the current study simulated disinfection efficiency of an in-duct UV+Filter system with two "A" values: 0.0377 and 0.590 (m 2 /J). Figure 13 shows the numerically simulated dimensionless concentration distributions of airborne SARS-CoV-2 aerosols in in-duct UV+Filter devices with different susceptibility values. C and C 0 were SARS-CoV-2 aerosols concentration of interior space and inlet, respectively. When "A" was 0.59, 81% of incoming SARS-CoV-2 aerosols were disinfected before reaching the pleated filter, and this efficiency decreased to 15% with "A" of 0.037. The upper-room UVGI disinfection efficiency reported by previous research was higher than those of the in-duct UV device in this study, as shown in figure 13 (Beggs & Avital, 2020) . The reason was that particle residence time (several minutes) of upper-room UVGI system was much higher than that (lower than one second) of in-duct UV devices. Due to the uncertainty of "A" value of airborne SARS-CoV-2 aerosols, it is difficult to reliably design in-duct UV system towards control of SARS-CoV-2. Therefore, it is necessary to investigate the accurate "A" value of airborne SARS-CoV-2 aerosols. For airborne bacteria/virus, if the applied UV irradiation dose is enough, aerosols/particles are effectively inactivated. UV irradiation dose is the product of UV irradiation flux (W/m 2 ) and exposure time (s) (Beggs & Avital, 2020 found that UV light (260-285 nm) effectively inactivated SARS-CoV-2 virus in fabric filter medium with irradiance intensity of 5.5 W/m 2 , and they reported that after 100 min, almost all the virus was inactivated in contaminated fabric medium. While pleated fibrous filters are capable of removing aerosol particles including dust and microorganisms from indoor air environments, they can become reservoirs for potentially hazardous particles, including bacterial and fungal spores (Nakpan et al., 2019; Bahrami et al., 2020) . Several studies have shown that stress-resistant spores can remain viable over a prolonged period of time and even grow in the filter media (Forthomme et al., 2014) . The spores collected on filters can be re-aerosolized during replacement or maintenance (Morisseau et al., 2017) , thereby posing a health risk. In order to overcome this disadvantage of pleated fibrous filter, UV+Filter system is developed for indoor ventilation systems. In a ventilation system, pleated filter loaded with virus/bacteria can be exposure to UV radiation for long time (e.g. several days/hour, operation time). For biological species deposited in filter medium, exposure time is long enough to deactivate virus/bacteria. Overall, UV generator in UV+Filter system could improve the safety level of fibrous filter due to biological inactivation effect. Figure 14 shows the simulated distributions of irradiance intensity (I R ) on pleated filter surface of UV+Filter system. The minimum I R value on the pleated filter surface was 5.5 W/m 2 , which was approximately the same as critical irradiance intensity value in previous literature (Fischer et al., 2020 ). In UV+HEPA system, SARS-CoV-2 aerosols were removed/destroyed by three mechanisms: 1) physical capture by fibrous filter due to filtration mechanism; 2) UV disinfection before reaching fibrous filter; and 3) UV dose applied to aerosols deposited in filter medium. Although the susceptibility "A" could be assumed by relevant experimental data, it is very necessary to obtain an accurate "A" value for engineering/operation safety. In the current design, only mechanisms (1-2) were considered. Mechanism (3) was not considered due to the lack of reliable susceptibility "A". with single wire and applied voltage of 6.5 kV, all the values of size-dependent filtration efficiency were 100%, as shown in figure 16 . The size-dependent efficiency of 0.1 µm particles was 57.7%, with applied voltage of 6.5 kV and one discharge wire. Considering the energy consumption and ozone generation, the optimal parameters for two-stage ESP were: applied voltage of 6.5 kV, and three discharge wires in ionization stage. Based on the previous study, the extra ozone generation (difference of ozone concentrations between ESP inlet/outlet) was lower than 8 ppb (Feng et al., 2016) . Once the corona breakdown occurs (applied voltage decreases to zero), size-dependent particle removal efficiency decreases to 0, as shown by figure 16 . Therefore, product quality of high-voltage generator/monitor must be guaranteed. Figure 17 describes simulated particle removal performance of HEFS. When the applied voltage was 0 kV, particle removal efficiency equaled mechanical filtration efficiency. If three discharge wires were adopted, size-dependent filtration efficiency was close to 100%. Based on numerical results shown in figure 17 , three design patterns of HEFS have filtration efficiency of 100%, including 8.5 kV/single wire, 8.5 kV/three wires, 6.5 kV/three wires. Energy consumption and ozone production of the HEFS design (6.5 kV/three wires) was found to be the least due to its low applied voltage. In regard to energy consumption and ozone generation, the HEFS with three discharge wires and applied voltage of 6.5 kV was selected as the optimal design. Different from fibrous filter with mechanical filtration mechanism, HEFS or two-stage ESP have two air cleaning mechanisms: physical removal and biological disinfection. The biological disinfection mechanism on airborne microorganisms is associated with density of space charge or ions (Zhou et al., 2016) . For numerical simulations of biological disinfection by ions, the most challenging issue is in determining the susceptibility values. Previous studies utilized experimental data to obtain susceptibility for a certain type of airborne biological aerosols (Zhou et al., 2016) . However, the experimental data for airborne SARS-CoV-2 aerosols is lacking and previous research used assumed values to predict disinfection efficiency (Beggs & Avital, 2020) . In order to ensure engineering safety, only physical removal mechanisms were considered in design of two-stage ESP and HEFS in this study. This study numerically investigated the overall performances of different air cleaning devices (Fibrous-filter, UV+Filter, two-stage ESP and HEFS) for removal of SARS-CoV-2 aerosols and compared them in term of filtration efficiency, energy consumption and secondary pollution. In comparison, designs of pleated fibrous filters in Fibrous-filter and UV+Filter systems were kept the same (Filter type A, high-efficient filter, pleat height of 100 mm, and pleat distance of 10 mm). For HEFS, the medium-efficient filter materials were used, which was described in detail in the methodology part. In numerical simulations of all air cleaning devices, inlet velocity was 1 m/s, and incoming air flow rate was 1 m 3 /s. For two-stage ESP, critical design parameters were: applied voltage in ionization stage was 6.5 kV, collection length was 1 m, three wires was installed in ionization stage. For HEFS, critical design parameters were: applied voltage in ionization stage was 6.5 kV, three wires was 35 installed in ionization stage. For all the four systems with proper design parameters, the filtration/removal efficiency of 0.1-2.5 µm particles was approximately 100%. Table 2 compares the four proposed systems in terms of energy consumption, system space, and operation risk. The total required power (W) of air cleaning system includes the fan, high-voltage generator, and UV lamp. Detailed information about energy consumption calculation could be found in previous literature (Feng, et al., 2018b; Yang, et al., 2018) . Fibrous-filter. Due to UV irradiation, energy consumption of UV+Filter system was higher than Fibrous-filter. Two-stage ESP occupied much more space than the other system because of its length of collection plates. Although ESP was energy-efficient, its risk level was high. Once electric breakdown occurred, removal efficiency for all particle sizes decreased to zero. It is therefore necessary to adopt real-time monitoring of electric breakdown during the operation stage. The energy saving rate of HEFS was not as high as the two-stage ESP while its risk level was also lower. Once electric breakdown occurred, removal efficiency of HEFS was the same to that of medium-efficient filter, as shown in figure 17 , and a large portion of incoming particles could be captured by the non-electrostatic fibrous filter. The risk of Fibrous-filter is re-aerosolization of deposited particles (e.g. spore) during replacement or maintenance (Morisseau et al., 2017) . Professional property service and system maintenance were needed for Fibrous-filter users. In electrostatic removal systems (two-stage ESP and HEFS), airborne SARS-CoV-2 aerosols could be removed by electric force acting on charged particles. Once the biological aerosols are captured by electrostatic removal systems, these aerosols are considered to be filtered and not harmful for indoor environment. Actually, the ionized electric field could disinfect airborne biological aerosols and biological particles deposited in electrostatic removal systems. In the current study, only the aerosol removal performances of ESP/HEFS was considered. In future research, the biological disinfection effect (SARS-CoV-2 aerosols expose to ions and electric field) should be investigated. Except for two-stage ESP and HEFS, many advanced types of electrostatic assisted air filtration systems have been developed (Tian et al., 2018; Mo et al., 2020) , including electrostatics assisted metal foam coarse filter, ESP with dielectric coatings et al. The experimental results indicated that these newly developed systems can reduce energy consumption without sacrificing particle removal efficiency. Besides, these advanced electrostatic assisted air filtration systems may be capable of high-efficiently disinfecting airborne species due to ion generation. Compared to the 38 ESP/HEFS, these newly proposed electrostatic removal systems may have potential to be much more effective in control of airborne SARS-CoV-2 aerosols. Therefore, it is necessary to evaluate these systems from the perspectives of aerosol removal, disinfection efficiency and energy consumption. However, the numerical models utilized in the current study could not completely predict the complex multiple physical fields (e.g. foam filter) in these newly developed electrostatic filtration systems. In future, complete experiments will be conducted to evaluate removal/disinfection performance of various electrostatic assisted air filtration systems. Besides, numerical models will be improved to be capable of reasonably/accurately predicting the removal/disinfection efficiency of different electrostatic filtration systems. Previous study (Luo & Zhong, 2021) concluded that air parameters (air temperature, relative humidity and air velocity) significantly influence the performance of UV system, including germicidal source output, UV rate constant, system inactivation efficiency, and system energy consumption. However, the effects of various air parameters were not considered in our current simulation study. In future, the numerical models will be improved to reasonably predict the performance of UV system under different air condition. In available literature, fibrous filters coated with photo-catalytic catalysts have been proven to be effective in air purification process (Zhong et al., 2013; Zhong et al., 2018) . Perhaps, the "UV+Filter" system with photo-catalytic catalysts coating may have much better performance from the perspectives of SARS-CoV-2 aerosol control. In our future study, we will investigate air purification performance of advanced fibrous filters (coated with photo-catalytic catalysts) towards the control of SARS-CoV-2 aerosols. Considering the characteristics of SARS-CoV-2 aerosols (aerodynamic characteristics, susceptibility to UV lights), this study proposed a multiple-physics model to simulate overall performance of UV+Filter system, including aerosol filtration/disinfection efficiency and UV dose distribution on pleated filter medium. Besides, performances of different air cleaning systems (Fibrous-filter, ESP, HEFS, UV+Filter) were numerically simulated and compared. The following conclusions can be drawn as follows: (1) For proper design (e.g. filter medium selection, pleat structure and UV configuration), filtration efficiency of UV+Filter was 100%, and UV dose applied to filter medium was sufficient to deactivate deposited SARS-CoV-2 aerosols. (2) After proper design of each air cleaning type (e.g. filter medium selection, arrangement of discharge wires and applied voltage in ESP/HEFS), filtration/removal efficiency for particles sizing in [0.1 µm, 2.5 µm] could be as high as 100%. UV+Filter system could significantly reduce re-aerosolization risk of fibrous filter. The optimal systems were sorted based on potential risk: UV+Filter> Fibrous-filter>HEFS >ESP. (3)The optimal systems were sorted based on energy consumption: UV+Filter> Fibrous-filter>HEFS>ESP. ESP and HEFS could save 97.8% and 84.6% of the energy consumed by Fibrous-filter. However, ESP/HEFS releases low-concentration ozone (below the critical value in standards) and induce risk of electric breakdown. Based on simulated overall filtration/removal performance of different air cleaning types, their advantages/disadvantages and usage recommendations were summarized. The systematic selection, optimization and evaluation method of air cleaning systems proposed in the current study could provide essential tools and quantitative results for control of SARS-CoV-2 aerosols and other airborne disease types. For electrostatic removal systems, the biological disinfection effect (SARS-CoV-2 aerosols expose to ions and electric field) should be investigated in future research. The author(s) declared no potential conflicts of interest with respect to the research, authorship, and/or publication of this article. biological aerosols. The UV generator consisted of twin tubes of 10 mm diameter and 120 mm luminous length. The irradiance intensity near lamp surface was close to 550 (W/m 2 ). The duct was made of galvanized steel with a 200×200 mm cross section. The detailed information about spatial position could be found in Fig. A1 or literature. Staphylococcus epidermidis (ATCC 12228) was the selected bacteria type, with susceptibility of 0.37 (m 2 /J). The standard k-ɛ model was used to simulate turbulent airflow field, and equation (4-5) were respectively utilized to simulate UV irradiance distributions and aerosol motion/disinfection. Based on literature, three-dimensional geometry and meshing strategy was adopted. All tested bacteria were assumed to be spherical with a 1.0 μm diameter and 1000 kg/m 3 density (Yang et al., 2018) . The inlet velocity magnitudes of ducts were 3.0, 4.5 and 6.0 m/s. For HEFS simulation, the numerical validation case was from previous literature (Feng et al., 2018b) . The length of the ionization stage was 500 mm, and its cross section was 200×200 mm 2 , as shown in figure A2 (b). The ionization stage consisted of three channels, and there were five wires along the centre line in each channel. The discharge wires with 0.05 mm diameter were made of copper. The key parameters of filter medium were: (d f : 10 µm; α: 0.14; Z: 2 mm; Pleat height: 100 mm; Pleat distance: 22.3 mm). The standard k-ɛ model was used to simulate turbulent airflow field, and equation (6-7) in this paper were respectively utilized to simulate electric potential and space charge concentration. The Lagrangian model (equation (2)), particle charging model (equation (8)) and particle filtration model (equation (3)) were simultaneously utilized to simulate particle motion, charging and filtration in porous filter medium. The detailed information about how to integrating Lagrangian model and electrostaic filtration model in ANSYS platform could be found in literature (Feng et al., 2018b) . Figure A2 (a) shows the geometry of validation case of single-stage ESP (Long & Yao, 2010) . Totally, eight corona discharge wires with 0.05 mm diameter were installed in the ESP channel. The simulation strategy of ESP was the same to that of the ionization stage of HEFS system. The energy consumption of various air cleaning devices (UV+Filter, two-stage ESP, HEFS) were quantitatively evaluated in this section. In comparison, the same operation conditions were adopted: inlet velocity was 1 m/s, air flow rate was 1 m 3 /s, and the targeted section area was 1 m 2 . Many units of air cleaning devices should be added together to meet the requirements of targeted cross section with area of 1 m 2 . For the calculation of energy consumption of UV+Filter, the UV generator and fan (mechanical energy loss) was considered, as shown by equation (A1 Where W (W) was the total energy consumption of UV+Filter, W UV (W) and W Fan (W) were respectively energy consumption of UV device and fan, I R (W/m 2 ) and S were respectively irradiance intensity (UV lamp surface) and effective functional surface of UV lamp, P (Pa) and Q (m 3 /s) were respectively pressure loss and airflow rate value of fibrous filter, k was the unit number needed to meet the requirement of cross section with area of 1 m 2 (k=4 for the current study), β was UV conversion coefficient (β=0.433 recommended by manufacturer). In previous study (Yang et al., 2019) , the β value was close to 0.42 based on calculation. For example (I R =340 (V); S=0.0628 (m 2 ); k=4; β=0.433; P=286 (Pa); Q=1 (m 3 /s)), the total energy consumption of UV+Filter was 483 (W). For the calculation of energy consumption of HEFS, the high voltage generator and fan (mechanical energy loss) was considered, as shown by equation (A2 Where W (W) was the total energy consumption of HEFS, W HV (W) and W Fan (W) were respectively energy consumption of high voltage generator and fan, V (V) and I (A) were respectively applied voltage and current value of high voltage generator, P (Pa) and Q (m 3 /s) were respectively pressure loss and airflow rate value of HEFS, k was the unit number needed to meet the requirement of cross section with area of 1 m 2 (k=15 for the current study). For example (V=6500 (V); I=0.0000627 (A); k=15; P=38 (Pa); Q=1 (m 3 /s)), the total energy consumption of HEFS with three discharge wires was 44.1 (W). For pure fibrous filter and two-stage ESP, only the terms of PQ and VIK (equation (A2)) were respectively used in calculation of energy consumption. Predicting fibrous filter"s efficiency by two methods: artificial neural network (ANN) and integration of genetic algorithm and artificial neural network (GAINN) Fundamentals, 11.15, ASHRAE Refrigerating and Air-conditioning Engineers (ASHRAE) STD 52.2: Method of testing general ventilation air-cleaning devices for removal efficiency by particle size Vacuum cleaner as a source of abiotic and biological air pollution in buildings -A review Upper-room ultraviolet air disinfection might help to reduce COVID-19 transmission in buildings: a feasibility study Presence and mobility of the population during the first wave of Covid-19 outbreak and lockdown in Italy A novel CFD analysis to minimize the spread of COVID-19 virus in hospital isolation room Estimation of airborne viral emission: Quanta emission rate of SARS-CoV-2 for infection risk assessment Ventilation control strategy using low-dimensional linear ventilation models and artificial neural network Manufacturing workers and employers, Interim guidance from C DC and OSHA Association of fibrous filters for aerosol filtration in predominant Brownian diffusion conditions Electrostatic precipitator for fine and ultrafine particle removal from indoor air environments Airborne route and bad use of ventilation systems as non-negligible factors in SARS-CoV-2 transmission HVAC systems for environmental control to minimize the COVID-19 infection Filtration characteristics of fibrous filter following an electrostatic precipitator Modeling filtration performance of pleated fibrous filters by Eulerian-Markov method Evaluation of the performance of an electrostatic enhanced air filter (EEAF) by a numerical method Microbial aerosol filtration: growth and release of a bacteria-fungi consortium collected by fibrous filters in different operating conditions Effectiveness of N95 respirator decontamination and reuse against SARS-CoV-2 Virus High efficiency particulate air filter, National standard of the People's Republic of China COVID-19 pandemic and sick building syndrome Susceptibility of SARS-CoV-2 to UV irradiation Sustainable design of courtyard environment: From the perspectives of airborne diseases control and human health Fighting against COVID-19: A novel deep learning model based on YOLO-v2 with ResNet-50 for medical face mask detection Aerodynamic analysis of SARS-CoV-2 in two Wuhan hospitals Evaluation of various particle charging models for simulating particle dynamics in electrostatic precipitators Ultraviolet germicidal irradiation (UVGI) for in-duct airborne bioaerosol disinfection: Review and analysis of design factors Influence of air inlet/outlet arrangement of displacement ventilation on local environment control for unearthed relics within site museum Kinetic modeling of the photocatalytic degradation of methyl ethyl ketone in air for a continuous-flow reactor Modeling of gas-phase heterogeneous photocatalytic oxidation reactor in the presence of mass transfer limitation and axial dispersion Quantification of the fungal fraction released from various preloaded fibrous filters during a simulated ventilation restart New electrostatic precipitator with dielectric coatings to efficiently and safely remove sub-micro particles in the building environment Inactivation of bacterial and fungal spores by UV irradiation and gaseous iodine treatment applied to air handling filters Physical barriers for covid-19 infection prevention and control in commercial settings, nat-ional collaborating centre for environmental he alth Removal of submicron particles using a carbon fiber ionizer-assisted medium air filter in a heating, ventilation, and air-conditioning (HVAC) system Data-driven dynamic clustering framework for mitigating the adverse economic impact of Covid-19 lockdown practices A simple semi-numerical model for designing pleated air filters under dust loading Decontamination of N95 respirators against SARS-CoV-2: a scoping review Carbon-Doped TiO2 film to enhance visible and UV light photocatalytic degradation of indoor environment volatile organic compounds Electrostatically assisted metal foam coarse filter with small pressure drop for efficient removal of fine particles: Effect of filter medium Model-based performance analysis of pleated filters with non-woven layers Modelling aerosol transport and virus exposure with numerical simulations in relation to SARS-CoV-2 transmission by inhalation indoors Evaluation of modeling and measurement techniques of ultraviolet germicidal irradiation effectiveness-towards the design of immune buildings WHO considers "airborne precautions" for medical staff after stu dy shows corona virus can survive in air Vision of China" s future urban construction reform: In the perspective of comprehensive prevention and control for multi disasters The 2019-nCoV epidemic control strategies and future challenges of building healthy smart cities Development and experimental validation of a mathematical model for the irradiance of in-duct ultraviolet germicidal lamps Disinfection efficacy of ultraviolet germicidal irradiation on airborne bacteria in ventilation ducts Use of HEPA filters to reduce the risk of nosocomial spread of SARS-CoV-2 via operating theatre ventilation systems Experimental investigation of thermal comfort and CO2 concentration in mosques: A case study in warm temperate climate of Yalova Air purifiers: A supplementary measure to remove airborne SARS-CoV-2 Comparison of three approaches to model particle penetration coefficient through a single straight crack in a building envelope Inactivation of airborne bacteria by cold plasma in air duct flow Deactivation and ultraviolet C-induced regeneration of photocatalytic oxidation air filters Ultraviolet photocatalytic oxidation for indoor environment applications: Experimental validation of the model Modeling of by-products from photocatalytic oxidation (PCO) indoor air purifiers: A case study of ethanol For fibrous air filter simulation, the numerical validation case was from previous literature (Feng et al., 2018a) . The flat filter medium (glass-fiber material) was used, as shown in figure A1 . The key parameters of filter medium were: (d f : 3 µm; α: 0.035; Z: 500 µm). The standard k-ɛ model, together with equation (1) in this paper, were used to simulate turbulent airflow field in fibrous filter. The Lagrangian model (equation (2)) and particle filtration model (equation (3)) were simultaneously utilized to simulate particle motion and filtration in porous filter medium. The detailed information about how to integrating Lagrangian model and filtration model in ANSYS platform could be found in literature (Feng et al., 2018a) . The inlet air velocity was fixed as 0.4 m/s, which was equal to the filtration air velocity of flat filter medium. The targeted particle sizes ranged from 10 nm to 1000 nm. For UV device simulation, the numerical validation case was from previous literature (Yang et al., 2018) . The in-duct UV lamps were utilized to disinfect airborne