key: cord-0769598-owerpof8 authors: Franco, Alessandro; Leccese, Francesco title: Measurement of CO2 concentration for occupancy estimation in educational buildings with energy efficiency purposes date: 2020-08-07 journal: nan DOI: 10.1016/j.jobe.2020.101714 sha: 7c4eb5c9cb9d415df7d4dcd291f0bac431f72b9b doc_id: 769598 cord_uid: owerpof8 Abstract The measurement of CO2 concentration is a relevant indicator for defining the occupation of indoor spaces. The real-time knowledge of occupation of such spaces is relevant both for maintaining indoor air quality standards and for energy efficiency purposes connected with the operation of heating, ventilation, and air-conditioning (HVAC) systems. The exact knowledge of occupation allows for rapid feedback from and the regulation of an HVAC system and the ventilation rate. Interesting applications include educational buildings and other buildings of the civil sector (e.g., shopping centres and hospitals). This paper provides the results of an experimental analysis in different classrooms of a university campus under real operating conditions, in different periods of the year, and with different kinds of activities. The correlation between the CO2 concentration and occupancy profiles of the spaces is then analysed. Some graphical trends of the CO2 concentrations in these indoor spaces are provided to determine the most important variables affecting such concentrations. The basic elements of the mathematical models for estimating the occupation of classrooms in relation to increases in CO2 concentration are also discussed and analysed. In industrialized countries, civil-residential is often the largest energy consuming sector. Over 40% of the final energy consumption can be connected to this sector. As a consequence, buildings are a relevant source of CO2 emissions. The high energy use of civil buildings is often connected to a non-optimal management strategy [1]. The accurate determination of building occupancy is a relevant factor for energy savings: A reduction in energy consumption of 30-40% to 80% can be expected [2] . Studying the energy demands of civil buildings was relevant importance to the topic of energy sustainability. In this specific field, educational buildings have common peculiarities. University An energy analysis of these particular buildings will help define the possible actions for planning an optimal HVAC control strategy with the purpose of maintaining high standards of indoor environmental quality (IEQ) and increasing energy efficiency. Various papers have highlighted this problem, both in general (e.g. [4] [5] ) and considering some specific case studies (e.g. [6] [7] [8] [9] ). Educational buildings like schools and universities often present higher occupation levels than other public buildings, and the length of the time spent in the classroom is also higher. For example, the number of occupants per unit area is estimated to be four times higher in classrooms than in office buildings, as discussed in [10] . Moreover, in university buildings, due to the different activities that occur, different energy amounts are required, making it challenging to establish benchmark data. In addition, in university buildings, different load profiles can be identified during the year, considering both thermal and electrical uses; thus, it is a relevant problem to define the correct load profiles of plants for climatization and indoor air quality (IAQ) control. During lecture periods, classes are relatively full, and many internal gains in energy input occur due to both the metabolic activity of the people J o u r n a l P r e -p r o o f inside and the operations of various instruments and devices (e.g., laptops and smartphones). Thus, for universities, an optimal operational strategy for the heating and cooling system and ventilation rate should carefully consider all these factors. During examinations, lower occupancy levels are observed in the classrooms. A simple analysis of the monthly reports of energy consumption shows that it is possible to establish a well-defined correlation between occupation and energy consumption. This problem is quite complex because if the electricity consumption connected to the operation of the various devices is directly proportional to the number of students, the energy consumption of the thermal control systems (cooling or heating) is highly influenced by the number of occupants. The presence of people inside the indoor spaces determines the changes in thermal conditions due to sensible and latent heat release. People also release carbon dioxide (CO2), which can be also controlled to maintain adequate air quality conditions. For this reason, accurately monitoring the occupation of crowded spaces is important. Ultimately, the different occupation levels of internal spaces determine the relevant discrepancies between the energy consumption of heating or cooling systems in both design conditions and real operating conditions. The same is true for electricity use. One method for estimating the occupancy of indoor spaces is a time dependent analysis of CO2 concentration [11] [12] [13] . Considering the recent trends in the research on sustainability issues, this paper considers the measurement of CO2 concentrations and their variation to define the real-time occupation of indoor spaces inside public buildings as a method to define the optimal operation of an HVAC. In particular, using demand-controlled ventilation was proposed in various studies [14] [15] [16] [17] . Exact knowledge of the occupational profiles of indoor spaces is fundamental to achieve an operational efficiency increase of the HVAC system and control the environment while maintaining high standards of quality with reduced energy consumption. The central idea involves balancing health, user comfort, and energy efficiency, for which accurately controlling occupation appears to be of fundamental importance. The paper is organized as follows. After a short overview of estimating the occupation of buildings via direct and indirect methods, the results of an accurate experimental analysis of a university campus are presented. The final part of this paper provides a possible correlation between CO2 concentration trends and the occupational levels of indoor spaces with the objective of controlling the operation of the HVAC system and defining accurate demand-controlled ventilation (DCV) strategies based on the direct measurement of CO2 concentrations. J o u r n a l P r e -p r o o f The thermal and electrical energy demand profile at a defined time resolution is the first element for promoting energy efficiency measures and introducing renewable resources. Both are relevant measures for the sustainability of buildings and for pursuing net-Zero Energy Buildings (n-ZEB), a combination of efficiency measures and the use of renewables [18] . An energy analysis of the buildings is important to identify the relevant actions related to energy consumption [19] . Three different strategies are available for defining the energy consumption profile of a building: the analysis of bills, direct measurements, and modelling using commercial computational code. The first strategy is the simplest one and has low accuracy because it permits one to obtain consumption with monthly frequency, and it is not possible to separate the energy consumption of various buildings or areas of buildings. In some special cases, it is possible to disaggregate the energy bills for a single building, which allows for a more accurate analysis. Moreover, no information on this dynamic behaviour is available. The second strategy is based on the direct measurements of specific quantities (natural gas, water, electricity, temperatures, and air flow rate). In this way, it is possible to obtain a characterization of buildings from an energy perspective that is accurate and time dependant; the reference period of observation can range from 15 minutes to 1 hour. However, the application of this method requires the use of a certain number of sensors to provide data with the required sampling frequency. The third strategy, which is frequently employed today, provides a mathematical (dynamic) model of the building, which is usually obtained via multi-purpose commercial software and allows one to obtain a dynamic simulation of the energy loads considering the typical climatic conditions, occupation levels, and energy uses of the various occupants. Defining the dynamic model requires a series of inputs on the users and structural characteristics that must first be collected. Typical inputs include at least three groups of parameters related to the weather, the structure of the building, and the components used inside the building. Many elements have an influence on energy efficiency benchmarking in the civil-residential sector. For example, it is possible to define the characteristics of the building under analysis (old, refurbished, or new) alongside the characteristics of the users and the activities within. However, for a well-defined field of activity, knowing the occupation of the space is important. Energy consumption and the parameters defining the quality of the indoor environment are directly connected to the occupancy profile. Estimating the number of occupants in a room from an analysis of environmental data, such as temperature, humidity, and CO2 concentration, is commonly found in the literature [20] [21] . Predicting the number of persons inside, starting from an evaluation based on indirect experimental measurements, is essential to estimate the energy consumption of each kind of civil or J o u r n a l P r e -p r o o f residential building and to control the operation of the HVAC system for maintaining air quality and environmental comfort standards under reduced energy consumption. Considering the various data that can be acquired for indoor spaces, CO2 concentration has a direct correlation with the number of occupants. The correlation between the occupancy profile and environmental parameters has been investigated for a long period of time [22] . Monitoring CO2 concentrations could be important not only for occupancy estimations but also because medium-to long-term exposure to CO2 causes undesired health and comfort effects. For example, data on CO2 concentrations obtained with specific sensors in conjunction with mathematical models based on the CO2 mass balance have been used to detect occupancy in some past studies [23] [24] [25] . Thus, the continuous measurement of CO2 concentrations using CO2 sensors can accomplish two objectives: furnishing a datum for the estimation of occupancy and assessing air quality to maintain satisfactory levels of comfort. In this work, we analyse the methodology with reference to a particular test case to provide specific results and basic elements that will be useful for increasing knowledge in this interesting field of analysis. For the measurement of CO2 concentrations in indoor spaces, it is important to define some quantitative details. The CO2 concentration limits for indoor and outdoor public buildings are defined by different government health protocols and industrial safety documents. For example, the air levels of CO2 that indicate a "quality level" of indoor air were established directly by the European Standards [26] and indirectly by Persily [27, 28] , who specified the minimum ventilation rates and other measures for new and existing buildings (referring to ASHRAE Standard 62). These measures are intended to provide indoor air quality that is acceptable to human occupants and minimizes adverse health effects. In all the documents, the standards of CO2 concentrations in the air are expressed in ppm (parts per million). A value of CO2 concentration in the range 250-600 ppm is the reference value for outdoor spaces (environment): A higher level indicates a value measured in a crowded town, while a lower level is typical of the countryside. A concentration of 400 ppm is the reference outdoor value In indoor spaces, humans exhale CO2 that remains in the air. Thus, the concentrations of CO2 are generally higher in indoor spaces than the reference outdoor level of 400 ppm. In a simplified case, the IAQ, represented by temperature, and the CO2 concentration and energy consumption maintain the required CO2 concentrations and are strictly correlated via the air ventilation rate. A value of 1000 ppm has become the de facto standard in many applications [27] , whereas a J o u r n a l P r e -p r o o f concentration of 1500 ppm represents the upper acceptable value of IAQ according to European Standards [26] . For the European Standard 13779 [26] , buildings are grouped into four different categories from I to IV. In buildings of Category I, a CO2 concentration of less than 400 ppm is used as the reference value; for Category II, the CO2 concentration is in the range of 400-600 ppm; those of Category III have a value in the range of 600-1000; and buildings of Category IV have values of CO2 concentration greater than 1000. A level of 600-1000 ppm is considered optimal in offices and educational building like schools and universities. This low level is justified because the occupants are young people who are more sensitive to health problems [29, 30] . A concentration over 1000 ppm is considered poor. Higher values can be caused by overcrowding or suboptimal operation of the HVAC systems. However, it is well established that a CO2 concentration over 1500 ppm should be avoided to maintain healthy indoor conditions. For educational buildings, the importance of maintaining a controlled value of CO2 concentration is not only connected to health and safety problems. The air quality and temperature in classrooms are important factors for teaching materials and methods, as well as for improving the learning process [31] . Moreover, it is generally recognized that a level above 2000 ppm is dangerous and reduces human operational efficiency. Exposure is possible only for a short period of time, after which acute or chronic health effects can be observed. To establish a quantitative correlation between the number of persons inside a room and the evolution of the CO2 concentration over time, an accurate value of the CO2 generation rate per occupant is required. A CO2 generation rate ranging from 0.20 l/min to a maximum value of 0.45 l/min per person is provided in the literature [32, 33] . In general, for technical engineering standards, under sedentary activity levels, a level of about 18 l/h, which equals 0.3 l/min per adult person, has been proposed based on medical standards [32] and monitoring campaigns [33] . In general, a direct correlation between CO2 concentration variations and various parameters can be observed. For example, the CO2 variation in a room can also be written as Where C(CO2} represents the indoor concentration, V is the volume of the room, n is the number of occupants, r is the CO2 generation rate per person, m is the air flow rate due to the ventilation rate (mechanical in natural due to infiltration), and Cext is the outdoor CO2 concentration. In the absence of mechanical ventilation, and considering the generation rate, r, as the predominant factor of CO2 concentration, the variation inside the room can be estimated by If the number of occupants is known, the ventilation rate and the consequent outdoor air change rate for maintaining the required standards of CO2 concentration can be defined, but if the number of occupants is not directly available, the ventilation rate can be established by indirectly monitoring the increase of CO2 concentration in the room. Monitoring CO2 concentrations is a well explored field, mainly for specific structures, such as university buildings. The outcomes of previous studies suggest that the data obtained can be correlated with several elements, this correlation is most relevant with the occupancy profile. Further, due to their metabolic processes, people inside a building emit CO2 levels that are proportional to the intensity of the activity. Thus, the CO2 concentrations in confined spaces are higher than those outdoors. Indoor concentrations are strongly correlated with the ventilation rate [34] [35] . The experimental analysis proposed in this paper was developed in the classrooms of educational building at the engineering campus of the University of Pisa. The engineering campus (a view of the area is provided in Fig. 1 ) has a structure that is typical of the historical university campus, with buildings of different origins and characteristics. The objective of this analysis is to measure the air temperature, relative humidity, and CO2 concentrations in some classrooms during normal teaching activities to establish the correlation between CO2 concentration and temperature increases with some quantitative indicators of occupation while referring to surface and volume. Chauvin Arnoux CA 1510 sensors were used for the experimental analysis. Using this particular sensor, direct measurements of physical quantities were possible, such as the CO2 Building B-This building, located in the yellow circle in Fig. 1 , was constructed in 1968-1969. It is a general-purpose building featuring classrooms and computer labs alongside study rooms, restrooms, and a bar. The structure is a light type with inner walls, low capacity materials, and wall insulation. Two large-sized classrooms are located in the building, with a total volume of over 1400 m 3 and 366 seats. There are also eight small-to medium-sized classrooms (from 33 seats to 216 seats) and 6 computer labs. The classrooms in this building, except for the three large-sized classrooms, are characterized by low ceiling levels (less than 3 meters). An HVAC with mechanical ventilation is used to control the indoor air parameters. Two classrooms in the building were selected for the experiments: a large computer lab (CL1) and one of the largest classrooms, which is identified with label 2 in Tab. 1. Building C-This building is located inside the blue circle in Fig. 1 The The experimental analysis was performed during the conventional didactic activities of the semester; for this reason, the occupation of the classrooms was not uniform during the various tests, varying from a minimum of 19% (classroom #4) to a maximum of 100% occupancy (classroom #3). In each classroom, two or four sensors were placed based on the volume. This was done because, as presented in the literature, the measurement of the CO2 concentration can be influenced by the position of the sensors and the mixing value of CO2. Using the above setup, we first analysed all the trends of CO2 concentrations in the various classrooms under several operating conditions. Two condition reflect the specific objectives of this analysis: identifying the characteristics (parameters) of the room that influence CO2 concentration and defining a correlation between this value and the number of students present inside the classroom over time to establish possible feedback on the HVAC system, based not only on controlling the temperature but also on the CO2 concentration. The measurements were done during regular didactic activities and were made without considering whether the conditions were typical or not. The instruments for the measurements were placed on the two sides of the classrooms, as described in Fig. 2 (a) (for two sensors) and Fig. 2 (b) (for the simultaneous use of four sensors). Although it was not possible to ensure that the CO2 was completely mixed in the classrooms, the configuration with four different sensors (one outside of the classroom to also assess the common elements) used in for high volumes enabled us to obtain an average value of the concentration that was representative of each situation. Fig. 3 shows some typical results obtained in a specific room during a lesson lasting three hours, considering the four points of measurement presented in Fig. 2b . The importance of the mechanical ventilation rate is strongly demonstrated by the results in Fig. 4 , which provides the results obtained during a three-hour examination in the computer lab (classroom CL1 in Table 1 ). In the first part of the examination (one hour), the ventilation was active. For this reason, no meaningful increase in CO2 concentration was observed. ppm. In some cases, the measured levels were over 3000 ppm. where VAPS represents the volume available for a single student at the maximum occupation level, and VR is the ventilation rate (in the primary part of the analysed cases due to infiltrations). Even if all the mentioned variables appear to be meaningful, the experimental results show that a type of hierarchical distribution can be identified among the variables, the most relevant of which seems to be the volume available for each student. In the first case, considering a starting level of 500 ppm, the increase would be 6 ppm/min, which means that the ventilation can operate after 80-90 minutes (1000 ppm is considered an acceptable level). However, the relevant increase was 50 ppm/min, which means that after 10 minutes, the action of the ventilation is required. Increases around 0.40 ppm/s are measured when the volume available to student is lower than 10 m 3 . This value is the maximum reference value used for designing buildings for educational purposes. Thus, it is possible to obtain an estimation of the CO2 increase trend over time to express the derivative of the CO2 concentration over time as a function of the volume per student according to the following law: This means that the increase in CO2 concentration over time is correlated with the CO2 generation rate per student, which is a relatively constant value for the specific activities under investigation (examinations or lectures). In this way, we confirm the possibility of using the CO2 monitoring results for estimating the space occupation. However, considering the correlation among the two variables described in Fig. 5 , some discrepancies incompatible with linear behaviour can be observed. J o u r n a l P r e -p r o o f The energy consumption needed to maintain thermal comfort and high indoor air quality in educational buildings is strongly influenced by the occupation of the space, which is not always simple to evaluate in public buildings. Predicting the number of occupants is an essential factor to achieve the optimal management of HVAC systems both to maintain the required levels of temperature, humidity, and pollutant concentrations and to ensure minimum energy consumption. The This study demonstrated the correlation between the measured values of CO2 and the number of occupants through a synthetic variable defined as the volume available per person. The higher values of concentration were obtained when the classrooms were very crowded (occupation rates over 70%), presenting a reduced value of the volume for each student. In particular, the maximum values were observed only when the per-capita volume was lower than 8 m 3 . Values over 0.4 ppm/s were obtained when the per-capita volume was below 10 m 3 . In such cases, mechanical air exchange is clearly required. The linear correlation between the increase in CO2 concentration and the volume available for each occupant can be used for a preliminary estimation of the increase in CO2 concentration, mainly in the phases when the air exchanger is not operational. The experimental analysis also shows that many different factors are relevant for defining the correlation between CO2 concentration and occupation. We observed that some occurrences, such as the opening of doors and windows during a lesson or an examination, can create differences in the measurements. The delay time of the CO2 concentration increase is correlated with the total volume: A perfect-mix model is acceptable for a classroom of a reduced volume/surface ratio, but the same is not appropriate for a classroom of a high volume. For this reason, it is challenging to J o u r n a l P r e -p r o o f define a model for correlating CO2 concentration and occupation, excluding cases of "fully closed" volumes. Monitoring CO2 concentrations and their variation over time in indoor spaces appears to be a valid method for estimating the real number of occupants, thereby activating demand controlled ventilation (DCV) to maintain indoor environmental quality (IEQ) with reduced energy consumption and balancing health, user comfort, and energy efficiency. Interest in the present topic has recently been further exacerbated by the spread of the COVID-19 pandemic. Several countries have started planning their post-lock-down activities, and, in general, all relevant documents agree with the idea of maintaining strict indoor air quality controls to prevent airborne virus transmission in crowded spaces. From this perspective, an indirect estimation of indoor space occupation using increases in CO2 concentration appears to be relevant. Thermal comfort and building energy consumption implications -A review OBSERVE: Occupancy-based system for efficient reduction of HVAC energy Energy-efficient control of under-actuated HVAC zones in commercial buildings Energy audit of public buildings: the energy consumption of a University with modern and historical buildings -Some results Indoor environmental quality of classrooms in Southern European climate Energy Performance analysis of University Buildings: case studies at Sheffield University Experimental and numerical research to assess indoor environment quality and schoolwork performance in university classrooms Control of CO2 in a naturally ventilated classroom Analysis of energy performance of university campus buildings using statistical and energy modelling approaches Energy and comfort assessment in educational building: case study in a French university campus Bayesian estimation of occupancy distribution in a multi-room office building based on CO2 concentrations Probabilistic behavioural modelling in building performance simulation -The Brescia eLUX lab Predicting occupancy counts using physical and statistical CO2-based modeling methodologies Occupancy density and benefits of demand-controlled ventilation in Norwegian primary schools Air flow rates and energy saving potential in schools with demandcontrolled displacement ventilation Demand controlled ventilation (DCV) in school and office buildings: Lessons learnt from case studies Indoor air temperature, CO2 concentration and ventilation rates: long-term measurements in newly built low-energy schools in Sweden Energy demand profile generation with detailed time resolution at an urban district scale: A reference building approach and case study Retrofit strategies towards Net Zero Energy Educational Buildings: A case study at the University of the Basque Country Accurate occupancy detection of an office room from light, temperature, humidity and CO2 measurements using statistical learning models Occupancy determination based on time series of CO2 concentration, temperature and relative humidity Detection of occupancy profile based on carbon dioxide concentration pattern matching Experimental validation of CO2-based occupancy detection for demandcontrolled ventilation. Indoor and Built Environment CO2 based occupancy detection algorithm: experimental analysis and validation for office and residential buildings Investigating the performance of scenario-based model predictive control of space heating in residential buildings EN 13779 -Ventilation for Non-Residential Buildings -Performance for Ventilation And Room Conditioning Systems Evaluating Building IAQ and Ventilation with Indoor Carbon Dioxide Challenges in developing ventilation and indoor air quality standards: the story of ASHRAE Standard 62 Building-Related Illnesses Research report on effects of HVAC on student performance Diffusion of Oxygen and Carbon Dioxide through the Respiratory Membrane Measuring human energy expenditure and metabolic function: Basic principles and methods Indoor occupancy estimation from carbon dioxide concentration Building occupancy estimation and detection: A review Partita IVA 00286820501 VAT No. IT00286820501 Codice fiscale 80003670504 The authors wish to confirm that this manuscript has not been submitted to, nor is under review at, another journal or other publishing venue.The authors have no affiliation with any organization, except the University of Pisa, with a direct or indirect financial interest in the subject matter discussed in the manuscript The authors confirm that the manuscript has been read and approved by both and that there are no other persons who satisfied the criteria for authorship but are not listed.The authors wish to confirm that he has given due consideration to the protection of intellectual property associated with this work and that there are no impediments to publication, including the timing of publication, with respect to intellectual property. In so doing the authors confirm that he has followed the regulations of its institutions concerning intellectual property. By analysing the data, the link between the measured CO2 concentration and occupancy can be studied for each classroom tested. It can be observed that CO2 concentration follows the occupancy profile, where the volume available for each person is the most relevant variable. The authors wish to confirm that there are no known conflicts of interest associated with this publication and there has been no significant financial support for this work that could have influenced its outcome.