key: cord-0752224-n1ysi7qc authors: Nissen, Karolina; Krambrich, Janina; Akaberi, Dario; Hoffman, Tove; Ling, Jiaxin; Lundkvist, Åke; Svensson, Lennart; Salaneck, Erik title: Long-distance airborne dispersal of SARS-CoV-2 in COVID-19 wards date: 2020-11-11 journal: Sci Rep DOI: 10.1038/s41598-020-76442-2 sha: e8fbd891a2613da39a9d525ac3f8b527a42d1110 doc_id: 752224 cord_uid: n1ysi7qc Evidence suggests that SARS-CoV-2, as well as other coronaviruses, can be dispersed and potentially transmitted by aerosols directly or via ventilation systems. We therefore investigated ventilation openings in one COVID-19 ward and central ducts that expel indoor air from three COVID-19 wards at Uppsala University Hospital, Sweden, during April and May 2020. Swab samples were taken from individual ceiling ventilation openings and surfaces in central ducts. Samples were subsequently subjected to rRT-PCR targeting the N and E genes of SARS-CoV-2. Central ventilation HEPA filters, located several stories above the wards, were removed and portions analyzed in the same manner. In two subsequent samplings, SARS-CoV-2 N and E genes were detected in seven and four out of 19 room vents, respectively. Central ventilation HEPA exhaust filters from the ward were found positive for both genes in three samples. Corresponding filters from two other, adjacent COVID-19 wards were also found positive. Infective ability of the samples was assessed by inoculation of susceptible cell cultures but could not be determined in these experiments. Detection of SARS-CoV-2 in central ventilation systems, distant from patient areas, indicate that virus can be transported long distances and that droplet transmission alone cannot reasonably explain this, especially considering the relatively low air change rates in these wards. Airborne transmission of SARS-CoV-2 must be taken into consideration for preventive measures. Sampling strategy. Sampling was performed on separate occasions during April and May 2020. In the first two occasions, 17 and 28 April, surfaces of exit vent openings in all 19 patient rooms in ward 1 (Fig. 1a) were swabbed as described below. When repeated on April 28, the internal surfaces of the central ventilation ducts, on the top floor were also swabbed and filter sections removed, as described further below. Due to the detection of SARS-CoV-2 RNA in the ventilation system (see "Results"), a further sample collection was performed using fluid traps, both at the terminal end of the ducts prior to the exhaust filters (at the same area where swabs were taken on April 28) as well as under the ceiling vent openings in the ward rooms (ward 1, see Fig. 1b ), in an attempt to determine the infective ability of any collected virus. Swab samples. Surfaces were swabbed using sterile nylon flocked swabs (Copan eSwab, Copan Italia SpA, Italy) moistened in sterile viral transport medium (VTM), containing Hank's balanced salt solution (Gibco, UK) supplemented with 2% fetal bovine serum (Gibco, USA), 100 µg/ml Gentamicin, and 0.5 µg/ml Amphotericin B 27 . Round ceiling vent openings were swabbed around the inside of the entire opening (circumference ca 25 cm). Swabs were placed in tubes containing 750 µl viral transport medium and stored at 4 °C until analysis within 24-72 h. Sampling was performed on April 17 and 28, 2020. Indoor relative air humidity and temperature were 30-31% and 20-21 °C, respectively. Filter samples. Exit ventilations from each of the eight stories in the investigated hospital building, (Fig. 1b) , lead to separate HEPA filter systems, located on the eighth (top) floor. Consequently, we could identify ducts and exhaust filters collecting air from individual floors not merging airflows. We chose to examine exhaust filters from three floors in the building that had been specifically designated for COVID-19 patients; two COVID-19 wards and a COVID-19 out-patient clinic. In addition, we examined exhaust filters from one story with per- www.nature.com/scientificreports/ sonnel areas and a cafeteria, as a negative control. The distance between the COVID-19 wards and the exhaust filters and inspection hatches was 49, 53 and 56 m respectively for each COVID-19 ward ( Table 1 ). The four stories located between the COVID-19 wards and the central ventilation in the top of the building (Fig. 1b) only sporadically harbored COVID-19 patients and were therefore not investigated. Adjacent inspection hatches upstream from (prior to) the HEPA filters were opened, and internal 30 × 30 cm surfaces swabbed as described above. Furthermore, one (out of six) 60 × 60 cm laminate F7 HEPA filter sections was removed from each system (filtering air from one ward or floor) and three filter samples (3 × 3 cm) were randomly cut out of the filters using sterilized scissors, placed in vials containing 2.5 ml of viral transport medium (described above), and stored at 4 °C until analysis within 72 h. The removed filters had been routinely replaced one month prior to collection. Fluid samples. Fluid sample collection was performed near air entrances (ward rooms) and exits (directly prior to exhaust filters) in the ventilation system by placing open, 10 cm diameter petri dishes with 10 ml of DMEM (Dulbecco's Modified Eagle's medium (cell medium); Gibco) diluted 1 to 5 with autoclaved water, suspended 15 cm below ceiling vent openings (in ward rooms) for 24 h, or placed within central vent ducts via inspection hatches for 3 h. DMEM was diluted to ensure appropriate salt balance for the cells and no osmotic effect on the virus after evaporation of water during the collection process. We used DMEM instead of water only to be able to add the whole volume of sample onto cells without a dilution effect of the cell medium. These points were chosen in an attempt to determine if virus found entering and/or exiting the ventilation ducts retained infective ability, in response to the PCR results from vent opening and exhaust filters. The suspended petri dishes in the ward rooms were placed within what we expected to be the normal air flow to ventilation ducts, as well as placing the dishes as far from the patients as possible, in order to avoid contamination by coughing induced droplets or other patient or personnel activity in the rooms. An open petri dish containing cell medium was exposed to air in the biosafety level (BSL)-2 area of the laboratory for 24 h and used as a negative control, along with non-exposed DMEM and viral transport medium. DMEM and VTM spiked with synthetic oligonucleotides (gBlocks, IDT, Belgium) based on N and E gene sequences with introduced 5 base pair deletions were used as positive controls (Suppl. Table 1 ). DMEM exposed to air in 19 ward rooms were combined to three pools. Pooling was performed when we could establish that a large number of rooms were occupied by non-contagious patients (seven rooms), patients with suspected COVID-19 but not confirmed (five rooms) and only six rooms were occupied by contagious COVID-19 patients (May 13, 2020) (Suppl. Table 1 ). Due to evaporation during collection, the final concentration of DMEM in the petri dishes after collection was equivalent to undiluted cell medium. The entire pooled volume ranging from 5 to 10 ml was subsequently applied to Vero E6 cells in T25 flasks and incubated up to 13 days. Samples were subsequently collected and subject to rRT-PCR. Petri dishes with 10 ml DMEM exposed to air outside of patient areas for 24 h were used as negative control. www.nature.com/scientificreports/ Ward conditions. All exit vent openings in the ward rooms are situated in the ceiling and are approximately 3 to 5 m from the head end of the beds (fresh air input openings are at 0 to 50 cm above floor level). Seven of the 19 openings are situated in adjacent washing rooms (see Fig. 1a ) and are up to approximately 5 to 6 m from beds. Total air changes per hour (ACH) for each patient room varied between 1.5 and 2.6 in ward 1, and 2.1 to 2.7 in ward 2, between 2.8 and 3.2 in the outpatient clinic, (measured December 2017). Air flow in the central ventilation shafts, from each story, ranged between 2.27 and 3.48 m 3 /s (Table 1 ). Pressure differences in rooms in ward 1 varied, − 6 to − 8.1 Pa between corridor and anterooms and + 5.5 to + 18 Pa between anterooms and patient rooms (measured March 2020). Hence, the anterooms were under negative pressure compared to the adjacent ward corridor as well as patient rooms. RNA extraction and rRT-PCR. RNA was extracted using 280 μl of samples and QIAamp viral RNA kit (Qiagen, Hilden, Germany), according to manufacturer's protocol. Portions of the SARS-CoV-2 nucleocapsid (N) and envelope small membrane protein (E) genes were amplified by rRT-PCR, using primers (Thermo Fisher Scientific, Waltham, MA, USA) previously described [28] [29] [30] As positive controls, double stranded DNA fragments (gBlocks, IDT, Belgium) with a five-nucleotide deletion in the targeted part of the E (10 2 copies/µl) and N (10 3 copies/µl) gene were used. Positive control Ct vales were 31.67 ± 0.68 and 28.07 ± 2.66 respectively. All PCR products with a Ct value < 45 were confirmed by Sanger sequencing (Macrogen, the Netherlands). Negative controls (swabs) were performed on non-exposed VTM (Suppl. Table 1 ). grown in DMEM (Gibco, 41966) supplemented with 10% FBS (Gibco, USA) and 1 × Penicillin-Streptomycin (Sigma-Aldrich, PA333). The flasks were incubated (37 °C, 5% CO2) until cells confluency reached approximately 90%, after which the cell media was substituted with 9 ml of pooled samples supplemented with 2% FBS and 1 × Penicillin-Streptomycin. Potential cytopathic effect (CPE) was observed daily. Increase in viral load was determined by rRT-PCR, using 100 μl of supernatant from each T-25 flask at 0 (base line for comparison), 24 and 120 h post infection (hpi). rRT-PCR was also performed on DMEM exposed to air in a BSL-2 laboratory for 24 h (see section "Fluid samples"), non-exposed DMEM and DMEM spiked with SARS-CoV-2 synthetic oligonucleotide control sequence as negative and positive controls, respectively (Suppl. Table 1 ). Eleven days post inoculation, supernatants from the pooled samples (1 ml) were passed once into new flasks seeded with Vero E6 cells and containing 4 ml of cell media. Two days after the passage, samples were taken as described above for quantification by rRT-PCR. All procedures involving live virus were performed in a BSL-3 laboratory. Authority DNR 2020-01787. As this retrospective data collection was considered completely anonymized by the Ethics committee, the need for patient consent was waived by the Swedish Ethical Review Authority. The study was conducted according to good clinical and scientific practices and following the ethical principles of the Declaration of Helsinki. Samples extracted from the main exhaust filters, located on the eighth (top) floor of the investigated hospital building (Fig. 1b) , from each separate ventilation system for the three investigated COVID-19 wards were positive for both genes in eight (88.9%) out of nine samples ( to baseline values (see "Results" above for Ct values) after 24 or 120 hpi on Vero E6 cells from samples retrieved from ward vent openings or central ventilation ducts or filters. Several aspects during the COVID-19 pandemic support the risk of aerosol transmission of SARS-CoV-2. First, mounting evidence for pre-and asymptomatic transmission, where the spread of droplets through coughing and sneezing cannot be a major factor, must raise questions about aerosol transmission 31 . Second, aerosols generated by speech could theoretically contain enough SARS-CoV-2 virus particles to support transmission, and these aerosols can remain airborne for up to ten minutes 20 . In addition, coronaviruses can be emitted in aerosols through normal breathing 32 . Third, field studies in hospital wards have detected SARS-CoV-2 RNA both in vent openings and in the air [14] [15] [16] [17] . These findings are not unexpected seeing as similar observations have been made for both SARS and Middle East Respiratory Syndrome (MERS) 8, 33, 34 . In this study, we found SARS-CoV-2 RNA in vent openings in ward rooms harboring COVID-19 patients. Viral RNA was also detected in fluid placed in open dishes suspended below vent openings. Similar levels of viral RNA were detected in exhaust filters and open petri dishes with cell medium at least 44 to 56 m from the three investigated COVID-19 wards. Only a small fraction of each filter was analyzed implying that a large number of particles emanating from COVID-19 wards can disperse to greater distances than can be explained by droplet transmission routes. In previous studies, the effect of ventilation has not shown any obvious impact on the risk for spread of droplet-transmitted diseases, probably since droplets are more governed by gravity 35 . Furthermore, the ventilation system in the investigated hospital building has a relatively low air flow; between 1.7 and 3 total air changes per hour (ACH) for each room, depending on room volumes. The recommendation for airborne infection isolation rooms is 12 ACH in most guidelines 35 . Notably, the relative air humidity in the investigated environment was low, between 30 and 31%. Low air humidity has recently been suggested to increase the risk of airborne SARS-CoV-2 dispersal 36,37 . We initiated this study by performing rRT-PCR on numerous surface and filter samples. Detection of SARS-CoV-2 as well as other coronavirus RNA in ventilation openings has been reported before 10, 15, 38 . However, the detection of viral RNA in the exhaust filters over 50 m from patient care areas was unexpected. In response to these findings, we found it vital to rapidly address the question of infective ability in order to determine the immediate risk of infection for uninfected patients, personnel working in the investigated wards and service personnel that might be exposed while working with the ventilation systems. We therefore employed the ad hoc methods described above in an attempt to determine the infective ability of the samples. We are aware that there are several potential limitations to the employed sampling methods in fluid traps; the likelihood of viral particles being deposited in fluids by gravity, the length of time the viral particles retain infective ability, concentration and increased osmolarity of the cell medium by evaporation as well as pH increase due to oxygen exposure during sampling. We have not determined whether the detected RNA could be from viral particles that have been inactivated by antibodies, seeing as a majority of the patients admitted to at least one of the wards were in later phases of COVID-19 disease at both collection dates (Table 2) , and may have likely developed an immune response. Even though we could not determine infective capability of virus collected in cell medium, we repeatedly detected Table 2 . Overview of results from the 19 investigated COVID-19 ward rooms (ward 1), including patient details regarding duration of symptoms, date when clinical sample was collected for PCR-diagnosis, PCR-result from clinical sample and ongoing oxygen therapies when ventilation samples were collected. Rooms marked with an * can accommodate two patients, and thus patient data is supplied for two patients for each sample occasion. Sample set 1: April 17, 2020. Sample set 2: April 28, 2020. Samples not exhibiting fluorescence above threshold level after 45 PCR cycles are labeled "negative". No www.nature.com/scientificreports/ SARS-CoV-2 RNA using this method. The placement of the petri dishes, either just below the ceiling in ward rooms or at distances around at least 50 m from patients in central vent ducts indicates that dispersal by means other than larger droplets must occur, since larger droplets are considered to precipitate by gravity within one or two meters from a source 5 . Although RNA could be detected in samples from ward rooms and central ventilation ducts, no infectivity was seen after inoculating samples on susceptible cells. This collection method was adopted in order to rapidly address the question as to what threat the RNA findings may infer in a clinical setting. Several explanations for these results may be identified. First, the Ct values are close to the detection limit, indicating that there were few viral copies in theses samples. Also, many of the admitted patients at this time point (later than other samplings in this study) were in late phases of COVID-19 or cleared of infection. We chose to report this as we could detect SARS-CoV-2 RNA in these samples, and that droplets do not appear to be a plausible explanation for these findings as droplets could unlikely follow a ballistic pathway from patient into the petri dished at 2.5 m height, and in all three pools. It is important to continue to develop effective sampling methods in order to determine infective ability of SARS-CoV-2 as well as differentiating between patients in early and late phases of disease. Since we are aware of these technical limitations, we have recommended service personnel to take adequate protective measures while working with the ventilation systems as we cannot definitively repudiate the risk of infection from contaminated air. Ongoing oxygenation therapies, such as High Flow Nasal Cannula (HFNC) oxygenation, in each room did not apparently correlate to detection, or Ct values, of SARS-CoV-2 RNA in vent openings ( Table 2) . This raises the question if the risk for airborne transmission should be considered in more situations than during potentially aerosol generating procedures such as HFNC 6 . This is further corroborated by the studies on aerosols generated when speaking and breathing 20, 32 . Results differed in ward rooms between the two samplings of vent openings, which could be due to varying disease progression for the occupying patients. Some vent openings were positive for both N and E genes despite the rooms having been evacuated and routinely cleaned ( Table 2 ). This suggests that detection also could result from viral shedding by previous patients and calls for further studies on how long SARS-CoV-2 RNA can be detected in the environment, with the accompanying risk for transmission via fomites. Alternatively, detection of viral RNA in the ventilation systems could arise from such activities as handling bed linens or cleaning which may disturb viral particles from textiles or surfaces and displace them into the air, and that these virions have dried and been rendered inactive. On the other hand, RNA deterioration after inactivation could limit the extent of this source of RNA found in HVAC systems. In this study we could not demonstrate infectious capability of the virus, when inoculated on Vero E6 cells, from samples in either vent openings, exhaust filters or by collection directly in cell medium. This is likely due to the pathogens rapidly drying in the vents or inadequate amounts of virus collected near vent openings or in front of exhaust filters. Also, collection directly in cell medium does not appear to have been performed previously and these results should be interpreted cautiously. Furthermore, admitted patients in the ward were between day 5 and 23 after symptom onset ( Table 2 ). There is accumulating evidence that COVID-19 contagiousness peaks shortly prior to symptom onset 2, 31, 39 . This implies that the patients in this study may be in a less contagious phase of COVID-19 disease, which is consistent with the findings that SARS-CoV-2 infectivity appears to be low eight days after symptom onset 39, 40 . Nevertheless, during dispersal from a patient to ventilation, and over considerable distances, the virus may still retain infective capability. RNA was also detected in containers placed at ceiling level, demonstrating that viral particles were airborne during these specific periods, at not only deposited on fomites over longer, uncertain duration. We speculate that the risk of infection by exposure to ventilation system air is presumably very low, due to dilution of viral load and drying. Nevertheless, the apparent capability of the virus to be transported in air, as we present here, should raise concerns for the risk of infection in smaller, confined spaces in close proximity to contagious patients, i.e. all air in patients rooms, intensive care units, etc. during care for COVID-19 patients 41 . This may be even more important concerning patients in earlier phases of disease, in which contagiousness may be high. This includes both symptomatic and asymptomatic SARS-CoV-2 infected persons in any confined space, such as homes, public transportation, restaurants, etc. The presented findings indicate airborne dissemination of SARS-CoV-2, especially considering the distance SARS-CoV-2 RNA was dispersed. However, further investigations, preferably discriminating between patients in early and later phases of SARS-CoV-2 disease as well as direct sampling of expiratory air from COVID-19 patients will be needed to resolve this question. Detection of coronavirus RNA, including SARS-CoV-2, in hospital and other ventilation systems has been reported, as well as nosocomial and HVAC associated outbreaks [8] [9] [10] [11] [12] [13] . In particular, MERS coronavirus, closely related to SARS-CoV-2, has caused major hospital associated outbreaks [9] [10] [11] [12] . Also, growing concern about aerosol transmission of SARS-CoV-2 has recently been ventilated 42 . Here we present further evidence for SARS-CoV-2 ability to disperse from patients to ward vent openings as well as detection of viral RNA in ventilation exhaust filters located at least 50 m from patient room vent openings. Although we could not conclude that the viral samples in this collection retained infective ability, the distance at which we detected RNA suggests that there may be a risk for airborne dissemination and transmission, especially at much closer distances to contagious persons in confined spaces, both in and outside hospital environments. We therefore find it reasonable to take precautionary measures against airborne transmission and that further investigations are necessary. World Health Organization. Modes of transmission of virus causing COVID-19: Implications for IPC precaution recommendations: Scientific brief Temporal dynamics in viral shedding and transmissibility of COVID-19 The role of particle size in aerosolised pathogen transmission: A review Airborne or droplet precautions for health workers treating COVID-19? Guideline for isolation precautions: Preventing transmission of infectious agents in health care settings Airborne transmission of severe acute respiratory syndrome coronavirus-2 to healthcare workers: A narrative review Particle sizes of infectious aerosols: Implications for infection control Extensive viable middle east respiratory syndrome (MERS) coronavirus contamination in air and surrounding environment in MERS isolation wards Middle East respiratory syndrome coronavirus (MERS-CoV) outbreak in South Korea, 2015: Epidemiology, characteristics and public health implications Environmental contamination and viral shedding in MERS patients during MERS-CoV outbreak in South Korea Nosocomial amplification of MERS-coronavirus in South Korea MERS-CoV outbreak following a single patient exposure in an emergency room in South Korea: An epidemiological outbreak study COVID-19 Outbreak associated with air conditioning in restaurant Aerosol and surface distribution of severe acute respiratory syndrome coronavirus 2 in hospital wards Air, surface environmental, and personal protective equipment contamination by severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2) from a symptomatic patient Detection of air and surface contamination by SARS-CoV-2 in hospital rooms of infected patients Aerodynamic analysis of SARS-CoV-2 in two Wuhan hospitals Aerosol and surface contamination of SARS-CoV-2 observed in quarantine and isolation care Aerosol and surface stability of SARS-CoV-2 as compared with SARS-CoV-1 The airborne lifetime of small speech droplets and their potential importance in SARS-CoV-2 transmission Aerosol transmission of SARS-CoV-2? Evidence, prevention and control Household secondary attack rate of COVID-19 and associated determinants in Guangzhou, China: A retrospective cohort study Identifying and interrupting superspreading events-implications for control of severe acute respiratory syndrome coronavirus 2. Emerg COVID-19 outbreak on the diamond princess cruise ship: Estimating the epidemic potential and effectiveness of public health countermeasures Characteristics of household transmission of COVID-19 Clinical characteristics of 138 hospitalized patients with 2019 novel coronavirus-infected pneumonia in Wuhan, China Centers for Disease Control and Prevention. Preparation of Viral Transport Medium Detection of 2019 novel coronavirus (2019-nCoV) by real-time RT-PCR Unique epidemiological and clinical features of the emerging 2019 novel coronavirus pneumonia (COVID-19) implicate special control measures Centers for Disease Control and Prevention, Respiratory Viruses Branch, Division of Viral Diseases. 2019-Novel Coronavirus (2019-nCoV) Real-Time rRT-PCR Panel Primers and Probes Evidence supporting transmission of severe acute respiratory syndrome coronavirus 2 while presymptomatic or asymptomatic Respiratory virus shedding in exhaled breath and efficacy of face masks Airborne transmission of SARS-CoV-2: The world should face the reality Evidence of airborne transmission of the severe acute respiratory syndrome virus Ventilation control for airborne transmission of human exhaled bio-aerosols in buildings Indoor temperature and relative humidity in hospitals: Workplace considerations during the novel coronavirus pandemic Weather impact on airborne coronavirus survival Airborne route and bad use of ventilation systems as non-negligible factors in SARS-CoV-2 transmission Virological assessment of hospitalized patients with COVID-2019 Predicting infectious SARS-CoV-2 from diagnostic samples Small droplet aerosols in poorly ventilated spaces and SARS-CoV-2 transmission It is time to address airborne transmission of COVID-19 We thank Thomas Collin and the service technicians at Uppsala University Hospital for their kind cooperation and assistance in accessing blueprint data and ventilation ducts, and Dr. Kåre Bondeson at Uppsala University Hospital for supplying patient PCR data. Study design, sampling, main authorship, by K.N. and E.S. PCR by T.H., J.K., cell culture experiments by D.A., J.L. and Å.L. Study design and interpretation by L.S. Manuscript preparation by all. Open Access funding provided by Uppsala University. The authors declare no competing interests. Supplementary information is available for this paper at https ://doi.org/10.1038/s4159 8-020-76442 -2.Correspondence and requests for materials should be addressed to E.S. Publisher's note Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations. License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creat iveco mmons .org/licen ses/by/4.0/.