key: cord-0747171-cr7xng4p authors: Risbeck, M. J.; Bazant, M. Z.; Jiang, Z.; Lee, Y. M.; Drees, K. H.; Douglas, J. D. title: Modeling and Multiobjective Optimization of Indoor Airborne Disease Transmission Risk and Associated Energy Consumption for Building HVAC Systems date: 2021-08-11 journal: nan DOI: 10.1101/2021.08.10.21261866 sha: 4592f804f3ba6b96c0ee6d967ab781774cef7421 doc_id: 747171 cord_uid: cr7xng4p The COVID-19 pandemic has renewed interest in assessing how the operation of HVAC systems influences the risk of airborne disease transmission in buildings. Various processes, such as ventilation and filtration, have been shown to reduce the probability of disease spread by removing or deactivating exhaled aerosols that potentially contain infectious material. However, such qualitative recommendations fail to specify how much of these or other disinfection techniques are needed to achieve acceptable risk levels in a particular space. An additional complication is that application of these techniques inevitably increases energy costs, the magnitude of which can vary significantly based on local weather. Moreover, the operational flexibility available to the HVAC system may be inherently limited by equipment capacities and occupant comfort requirements. Given this knowledge gap, we propose a set of dynamical models that can be used to estimate airborne transmission risk and energy consumption for building HVAC systems, based on comfort preferences and weather conditions. By combining physics-based material balances with phenomenological models of the HVAC control system, it is possible to predict time-varying airflows and other HVAC variables, which are then used to calculate the key metrics. Through a variety of examples involving real and simulated commercial buildings, we show that our models can be used for monitoring purposes by applying them directly to transient building data as operated, or they may be embedded within a multi-objective optimization framework to evaluate the tradeoff between infection risk and energy consumption. By combining these applications, building managers can determine which spaces are in need of infection risk reduction and how to provide that reduction at the lowest energy cost. The key finding is that both the baseline infection risk and the most energy-efficient disinfection source can vary significantly from space to space and depend sensitively on the weather, thus underscoring the importance of the quantitative predictions provided by the models. With the recognition that airborne exchange of respiratory aerosols may be the primary means of transmission 28 for COVID-19 and other diseases [1] [2] [3] [4] , it is crucial to understand how HVAC systems can affect this infection In this section, we present various dynamic models that can be used to estimate and predict infection risk and 254 HVAC energy consumption within an indoor zone. All models are defined in the standard continuous-time state-space for states x, inputs u, outputs y, and static parameters θ. (Note the distinction between u and θ is that values of 257 u vary throughout the simulation period, whereas values of θ are held constant.) Models are simulated using the 258 standard 4th order explicit Runge-Kutta method assuming a piecewise-constant hold on u and calculating y as the 259 average value over the integration interval, which for our purposes is ∆ = 15 min. 260 Performance metrics are all calculated for each timestep as functions θ (y, u) that are then integrated as appro-261 priate over the simulation interval. In various contexts, they are used as optimization objectives or constraints. With this general approach, the main dynamic model for the airborne infectious quanta concentration C is as 272 follows: From these variables, we then calculate the primary metrics via where N T is the expected number of transmission events that occur and E aux the energy consumption associated 275 with UV and auxiliary disinfection, both over the time period t ∈ [0, τ ]. Descriptions and units of all variables are 276 given in Table 1 . We discuss key model features and parameters in the following sections. 277 8 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08. 10 .21261866 doi: medRxiv preprint Table 1 : Variables in the infectious particle concentration model. Description Unit µ I attenuation factor for infector generation rate (e.g., due to masks) − µ S attenuation factor for susceptible dose rate (e.g., due to masks) − τ evaluation time for metrics s βq hazard rate for transmissions q −1 w UV power consumption of in-duct UV at maximum activation kW w aux,j power consumption of in-zone disinfection device j at maximum activation kW 9 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08. 10.21261866 doi: medRxiv preprint To model the time variation in infection quanta concentrations, we note that infectious particles are released into 279 the air by the infectious individual and then removed by a variety of mechanisms. To standardize modeling of these 280 effects, we define the concept of "clean-air delivery" to the space as follows: for a piece of equipment or physical 281 process j that deactivates or captures infectious particles at a total rate r j (measured in units of q/s) from an air 282 stream with concentration C (measured in units of q/m 3 ), the corresponding clean-air delivery rate is defined as 283 f clean,j = r j C which thus has units m 3 /s corresponding to a hypothetical volumetric flow (and can be converted to air-change 284 rates by dividing by the space volume). We use this definition because for most disinfection processes, r j is directly 285 proportional to C, and thus f clean,j can be expressed as a simple fraction of airflow through the device. In addition, 286 this formulation provides a common basis for comparison of different disinfection devices: multiple devices providing 287 the same clean-air delivery rate thus become fungible from an infection-risk perspective and can be assessed in terms 288 of energy consumption or other considerations to choose the best among them. One complication of this clean-air framework is that for devices and processes that operate at the particulate 290 level (i.e., deposition and filtration), the removal rate r j depends on the size distribution of the particles contain-291 ing the infectious material [4] . When the inlet size distribution is known, accounting for size-dependent effects is 292 straightforward for a single device. However, because their action leads to changes in the airborne size distribution, 293 it is not longer possible to fully and exactly describe the clean-air characteristics of a device without knowing (and 294 accounting for the inherent recirculation effects on) the size distribution of airborne particles. For simplicity, our 295 current approach is to assume a representative particle diameter (e.g., 1 to 3 µm), close to the effective aerosol size 296 defined by Bazant and Bush [4] for typical respiratory activities and room conditions. With this value, we calculate 297 all clean-air delivery rates assuming a narrow unimodal distribution of particles at that size. However, see discussion 298 in the next section for how this effect could be modeled more accurately without significant changes to the existing 299 framework. Aside from size-dependent effects, the calculation of the clean-air delivery rate for most processes and devices is 301 straightforward. For example, airborne particles naturally deposit on the ground at a given velocity ν deposition due 302 to gravity. Thus, in a room with volume V and height h, the removal rate of such particles by deposition is given by Similarly, due to natural decay of the viruses (assumed to occur with a first-order rate constant k decay ), the removal 304 rate due to natural decay is thus given by 305 r decay = k decay V C In practice, this decay rate may vary with temperature and humidity within the space [4], but for simplicity here 306 we assume it is truly constant. As modeled above, we combine these two effects as "natural" disinfection sources in Note that they scale with the total volume of the space and occur independently of any HVAC operational decisions. 309 10 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint flow f filter through the filter, which captures a fraction η filter of the particles the total removal rate is given by 311 r filter = η filter f filter C and so the clean-air delivery is simply 312 f clean,filter = η filter f filter Effective filtration efficiencies for various filter grades are known [43] , modulo uncertainty in size dependence. Simi-313 larly, for UV devices that kill a given fraction η UV of the microbes passing through them, the clean air production 314 is 315 f clean,UV = η UV f filter If properly designed, UV disinfection tunnels can achieve very high disinfection rates η uv ≈ 1 [59], but the performance 316 of smaller standalone devices may vary. For devices operating in parallel, their total clean-air delivery is a simple sum of their individual values. Since 318 all auxiliary in-zone devices are effectively in parallel, we thus include the summation term in Eq. (1), noting that 319 the maximum clean-air capacity f max aux,j of a given auxiliary device needs to be scaled by the extent a aux,j to which 320 it is currently active. Note that for some devices a aux,j may vary continuously, while for others, it may take only a 321 binary value indicating whether the device is on or off. For devices operating directly in series, however, the total clean-air delivery must account for the fact that the 323 clean-air delivery for each device must be calculated in terms of the original inlet concentration rather than that 324 device's particular inlet concentration. The canonical example of this configuration is in the AHU: when air is 325 returned to the AHU, a given fraction x a is vented to the ambient (and replaced with a corresponding volume of 326 outdoor air), after which it passes through a filter with disinfection efficiency η filter and possibly also through a UV 327 kill tunnel that kills a fraction a uv η UV of microbes in the airstream. Taken individually, the clean-air rates of each 328 device would be given as However, because these devices operate in series, we must account for the fact that each device processes the outlet 330 of the previous device. Thus, the inlet concentration to the filter is only 1 − x a times its initial value, and thus the 331 filter provides only (1 − x a )η filter fractional disinfection. The overall clean-air delivery for the AHU is thus given by (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. with P s giving that individual's infection probability in terms of the individual's infectious dose rate q s , which is 345 itself given by We note that at steady-state conditions (i.e., dC/dt = 0), the model in Eq. (1) gives C = q I /f clean . Substituting 347 these values (and converting the time-varying integral to a simple multiplication) gives we are interested in the HVAC operation of the zones, it is more practical to adopt a zone-based approach in which 361 infection risk is associated with spaces rather than individuals. To address these limitations, we take an approach similar to Bazant and Bush [4] and make a linear approximation 363 as follows: 12 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint N T presented in Eq. (1). The main benefit of this formulation is that we can now split the whole-building R on a 366 zone-by-zone basis. Thus, separate actions can be taken in each zone based on that zone's contribution to overall 367 infection risk. In arriving at this formulation, we have made use of the fact that 1 − exp(−x) ≈ x for small values of x, which 369 allows us to remove the nonlinearity and shift the summation inside the integral. We note also that the linear 370 approximation is conservative, i.e., uniformly over-estimating N T , due to concativity of the exponential function. f breathe,S of infectors and susceptibles, the mask effectivenesses µ I and µ S , and finally the infector exhaled quanta 380 concentration N I . We discuss these parameters in more detail as follows. but this value should be adjusted for specific spaces with different activity levels (e.g., gyms) and possibly also for 386 different age distributions (e.g., in an elementary school). Note that because we generally do not know which specific 387 individuals in the space are infectious, we will almost always assume f breathe,I ≈ f breathe,S . However, the values can 388 be considered separately in edge cases where distinct separate values are known. For the mask effectiveness parameters µ I and µ S , unfortunately there is very large uncertainty relating to both 390 mask material and fit. For example, an N95 mask may have a theoretical filtration efficiency above 99%, but if worn 391 incorrectly (so that a significant amount of air can escape around the edges of the mask), then its effective efficiency 392 may be significantly lower. Given this variability, we use a default value of roughly 70% filtration efficiency. As with 393 the breathing-rate parameters, we generally do not know which specific individuals are infectious, and so there may 394 not seem to be clear motivation to use different values for µ I and µ S . However, when aerosols are exhaled by humans, 395 they generally contain a large amount of water that will evaporate as the particles come to equilibrium with the 396 humidity in the space. As this evaporation occurs, the particles shrink in diameter by roughly a factor of 2 at 50% 397 relative humidity [4]. Thus, we generally expect that µ I > µ S since the particles are bigger when exhaled through 398 the infector's mask than when they are inhaled through the susceptibles' masks. Although this effect is challenging 399 to quantify, we retain separate µ I and µ S in case accurate experimental values are obtained in the future. 400 Finally, for the infector's exhaled quanta concentration C I , we note that this value is commonly characterized 401 in conjunction with the breathing rate f breathe,I as a single parameter q (denoted q I in our equations above) giving 402 13 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint a quanta generation rate in quanta per time [36, 39] . However, given that COVID-19 is transmitted primarily in 403 respiratory aerosols, it is suggested by Bazant and Bush [4] that the value be disaggregated as separate C I and 404 f breathe,I as we have modeled it, with C I ranging from 10 q/m 3 for quiet breathing, to q/m 3 while speaking, and as 405 high as 1000 q/m 3 while singing. This choice of parameterization makes it clear that the dependence of infection 406 risk (as determined by the total received quanta dose) is roughly quadratic in the average breathing rate. Of course, 407 the true generation rate of infectious quanta is complicated by additional factors (e.g., intermittant coughing and 408 variation in viral load due to natural disease progression), but this parameterization at least captures the fundamental 409 trends with respect to activity level and vocalization. For the infectors N I , one option is to choose the value based on the incidence of disease in the general population. Such statistics are generally available from the CDC and other organizations and can be multiplied by the design 416 occupancy of a zone. Unfortunately, these values can vary significantly with time and location, which makes them 417 difficult to incorporate into quantitative analysis. Thus, we instead opt for a conditional approach as follows: rather 418 than trying to estimate the actual number of infectors N I in the space, we instead assume that N I = 1 and thus 419 calculate infection risk conditioned on the fact that that one infectious individual has made it into the space. With 420 this assumption, the infection rate N T from Eq. (2) thus scales linearly in the number of infectors (i.e., 2 infectors 421 in the space will on average cause 2N T infections over the course of a day, 3 will cause 3N T , etc.). We know from 422 the mathematics that this approach will overestimate the number of new infections when the number of infectors is 423 larger (since the susceptible population is correspondingly reduced), but if the situation is already that dire, HVAC 424 measures alone will not be sufficient, and the prudent choice is to simply close the building. The main point is that To model the evolution of temperature and humidity within the zones, we use straightforward (thermal) energy 446 and (water vapor) mass balances respectively. Although there are some pressure fluctuations in the space, they are 447 small enough to allow a constant-density assumption for air within the zones. The volume within a zone is assumed 448 to be well-mixed and thus have uniform temperature and humidity. Note that throughout this discussion, we use 449 "humidity" to mean the "absolute humidity ratio" (commonly denoted ω) unless otherwise specified. ODE equations for the mass and energy balances are as follows: The AHU outlet conditions and loads are calculated from simple heating and cooling coil models with the following 452 functional form (and described in more detail in Section 2.2.2): The electricity consumption of the fan is given by a cubic polynomial (see Section 2.2.3 for more details): Finally, from all of these outputs we the main metrics associated with energy consumption and thermal comfort in 455 the space: Descriptions and units of all variables in these equations can be found in Table 2 . We discuss these equations in 457 more detail in the following sections. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint in which ω sat (T ) gives the saturation humidity at temperature T . This term is responsible for modeling the dehu-499 midification provided by the coil, which is often a significant fraction of energy consumption in humid climates. Note 500 that the first equation assumes linear mixing for the recombination of coil and bypass streams. We calculate the 501 outlet humidity as 502 ω out = x bypass ω in + (1 − x bypass )ω coil which will always be less than or equal to the inlet humidity ω in . Summarizing the heating and cooling models, we thus have the following relationships: From these conditions, we can thus calculate the thermal loads on the coils as follows: in which H(T, ω) is the specific enthalpy of wet air at temperature as before, and H w (T ) is the specific enthalpy of 506 liquid water. Note that this expression is written so that it gives the heat gained by the air stream, with a positive 507 value indicating the stream was heated and a negative value indicating the stream was cooled. We can thus split 508 into individual heating and cooling components as The calculated T out , ω out , ∆h h coil , and ∆h c coil then become the AHU conditions T AHU , ω AHU , ∆h h AHU , and ∆h c AHU 510 indicated in Eq. (4). As above, we do not consider humidification equipment, but where present, it could be accounted 511 for by increasing ω AHU up to a given setpoint. Physically, the energy consumed by the fan is given by where η fan is the mechanical efficiency of the fan, and ∆P fan is the pressure rise across the fan. The cubic dependence 516 on f comes from the fact that the pressure rise of the fan is equal to the pressure drop through the ductwork, which 517 is commonly modeled as proportional to the square of flow. These considerations suggest that w fan ∝ f 3 . In practice, 518 18 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint the mechanical efficiency of the fan will vary over its operating range, and thus the cubic term alone is not sufficient 519 to match the actual performance of the fan. By adding the additional linear and quadratic terms, this variation can 520 be captured. Note that some sources will suggest adding an additional constant term to better match experimental 521 behavior. However, we require for our application that w fan is zero when f is zero (e.g., during unoccupied hours 522 when the HVAC system is shut off), and so we do not include this term to avoid artificial inflation of predicted 523 electricity consumption. The most accurate way to determine the coefficients c i in the fan model is to obtain a dataset of (f, w fan ) pairs 525 from the actual fan and use standard regression. Unfortunately, it is uncommon to directly measure w fan is real 526 buildings, and so this approach is not practical. Instead, we define one set of coefficientsc i to match a representative 527 AHU fan with efficiencyη fan and pressure rise ∆P fan . We then rescale thec i linearly based on the design values for 528 η fan and ∆P fan (which are generally readily available) for the each AHU we model. This approach gives reasonable 529 accuracy for a variety of zones and buildings. A key requirement for the fan model is that it be able to account for the different electricity consumption 531 associated with different filter types. In general, higher-efficiency filters require higher pressures to deliver the same 532 airflow. This additional pressure must be overcome by the fan, which in turn increases electricity consumption. To explicitly defined control laws, those laws often consist of complicated rule-based logic that operates on much faster 546 timescales than desired simulation timestep. Thus, rather than try to replicate the control laws directly, we instead 547 choose a phenomenological approach in which we attempt to model the outcomes of the controllers' actions. For 548 example, rather than trying to model the (heavily modified) PI control law within the VAV controllers to specify 549 airflow as a function of setpoint tracking error, we instead assume that the controller is well-designed and thus 550 maintains temperature setpoints within the space whenever possible. This overall approach simplifies our modeling 551 effort, as it allows us to use information about internal system states and disturbances that would not be directly 552 available to the controllers. 553 19 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. These calculations use the following intermediate variables: Note that the clip function is defined as clip(x, a, b) = min(max(x, a), b) for a ≤ b. Variables used in this model are 556 described in Table 3 . Specific equations are discussed in the following sections. Overall, the main functionality of the controller model is that it allows prediction of the internal quantities that 558 ultimately determine infection risk and energy consumption in the space. We can thus adjust the static controller 559 parameters θ and predict how the HVAC control system will respond, which allows us to optimize for energy 560 consumption or infection risk depending on our current priorities. In an ideal system, we would be able to manipulate 561 (and thus optimize) the airflow f AHU and outdoor-air fraction x a directly, but in existing HVAC systems, these 562 quantities reflect the response of the regulatory control system and thus can be adjusted only indirectly. Using this 563 simple controller model, we thus bridge the gap between the controller settings we can manipulate and the HVAC 564 variables required for infection-risk and energy modeling. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint current T z , the chosen f AHU or Q h , and the values of the remaining model inputs. Thus, we can solve those equations 574 for thef AHU andQ h that drive T z to T max z and T min z respectively, i.e., solving 575f AHU satisfies T max in which the "..." represent the remaining model inputs (which would not all be known in a real system but are 576 known to the model). Note that for physical reasons, both variables must be nonnegative, but since that restriction 577 is enforced by clipping after the fact, we place no sign restrictions onf AHU andQ h . From the model structure, we 578 know that a suitable valueQ h always exists and a suitablef AHU exists under standard operating conditions (i.e., T AHU < T z ). In the event that the denominator is zero, we setf AHU to ±∞ depending on the calculated sign ofQ c . In cases where 588 T AHU and T z are constant during the integration interval, this calculation is exact, and the accuracy deteriorates as 589 T AHU and/or T z vary within the interval. By assumption, T AHU will be equal to its setpoint T sp AHU , and so there is simply the minimum fraction of f AHU that will deliver the required minimum outdoor-air ventilation rate f min vent (which 614 cycles between zero and the pre-configured boundf vent based on the occupancy flag σ). As discussed in the previous 615 section, we always have that f AHU ≥ f min vent , and so we know that x min a = f min vent /f AHU will always be between 0 and 1. For x max a , the bound is calculated as the maximum fraction of f AHU that will keep the temperature of the resulting 617 mixture below the supply temperature setpoint T sp AHU (so as to avoid an unnecessary heating load). Assuming linear 618 mixing, this condition is exactly satisfied when which gives a valid 0 ≤ x max a ≤ 1 whenever T a < T sp AHU < T z . However, because those constraints are not always 620 satisfied (in particular due to seasonal variation in T a ), we modify the calculation to clip both temperature differences Note that the models here assume that a simple (but standard) outdoor-air economizer is responsible for outdoor- the goal of the optimization is to identify the most efficient clean-air sources, which can vary from day to day based 709 on ambient conditions. In addition, it may be the case that some spaces already provide adequate disinfection under 710 standard operation, and thus there is no motivation to further increase clean-air delivery. In order to address these needs, we formulate a multiobjective optimization problem using the dynamic models 712 to predict the necessary decision metrics. Mathematically, the overall structure of the optimization problem is as 713 follows: That is, we perform multiobjective optimization over a set of model parameters θ ∈ Θ with each scalar objective 715 function and constraint z k , calculated from the inputs u t and outputs y t of the simulation model. Note that in this 716 context, the models f ( · ), h( · ), and k ( · ) represent the coupled models, i.e., the combination of infections quanta, 717 thermal, and controller models as mentioned in the previous paragraph. Owing to the multiple objectives, the goal is not to find just a single optional point θ * but rather the set of be installed or replaced. The key distinction is that operational variables can be reasonably be adjusted on a daily or 728 faster basis, whereas changes to design variables would generally be changed only monthly or less frequently. Thus, 729 26 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint that approximates the full space and then identify the Pareto setθ * from just that finite set by simulating the 766 performance metrics for each point within that set. This choice is appropriate for the following reasons: • The number of independent decision variables is generally between 3 and 5, which means a simple grid over 768 the continuous variables will not give a prohibitive number of points. • Some decision variables (e.g., filter type or on/off choice for equipment) are implicitly discrete, and thus 770 continuous optimization methods cannot be applied in a straightforward manner. two values forā UV corresponding to "on" and "off" respectively. Thus, to optimize over this set, we need perform 783 11 × 11 × 2 = 242 simulations. Once the setΘ has been chosen, the Pareto optimization algorithm is straightforward: • For each θ i ∈Θ: • Simulate the model using parameters θ i to determine each z k (θ i ). • If all bounds z min • For each θ i ∈Θ * : • ReturnΘ * , the Pareto-optimal subset ofΘ. Thus, we require one model simulation for each element ofΘ and K 1 comparisons for each pair of elements inΘ. Note that more efficient algorithms are known [66], but this naive implementation is sufficient for the problem sizes 795 we consider. 796 28 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint to implement within the system. This selection could be made via thresholds on the variables, e.g., choosing the 798 solution with the lowest energy consumption E such that the number of transmissions N T ≤ 1 if any such points 799 exist, or otherwise choosing the solution with the lowest N T . The exact selection criteria will depend on a building 800 manager's current priorities, but by providing the full Pareto set, the fundamental tradeoff can be fully evaluated. the COVID-19 pandemic). Data was collected at a 1-minute frequency and then re-sampled to 15-minute intervals 818 for our purposes. As discussed in Section 2.1, calculation of infection risk requires values of key parameters relating to occupant 820 activity. For the Office zone, we assume a breathing rate of 0.7 m 3 /h, while in the Gym zone, we use a higher 821 breathing rate of 1.6 m 3 /h. These values correspond to "low" and "moderate" activity respectively for a typical 822 adult occupant [61] . For the exhaled quanta concentrations in the zones, it reasonable to suspect that Gym occupants 823 have a higher overall exhaled particle concentration, as they are more likely to be breathing deeply and through their 824 mouth compared to Office occupants. However, it is also plausible that actively infectious individuals would be less 825 likely to exercise if they are feeling symptomatic, and thus we would expect Gym infectors to have below-average 826 viral load (and thus also exhaled quanta concentration). Given this uncertainty and the absence of definitive data, we 827 use the same mean exhaled quanta concentration of 20 q/m 3 in both spaces, corresponding to light vocalization [4] 828 Finally, the models require a time-varying occupancy profile, which is unfortunately not provided by the dataset. taken from floorplan diagrams, and we assume MERV8 filters with no occupants wearing masks, as is consistent with 832 pre-pandemic operation. 33 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. value) before increasing the supply temperature setpoint once again to achieve maximum clean-air delivery. Overall, 926 we see that even with just these two decision variables being considered, the range of achievable infection rates (and 927 34 All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. EnergyPlus simulated data is not as realistic as the real data in the previous section (in particular it is much less 932 noisy and is subject to much more regular disturbance profiles), the key benefit is that we can directly compare 933 the effects of different control actions. Specifically, for a given day's weather, we can simulate all candidate sets 934 operational variables rather than just the default operating policy. We will use this feature to more thoroughly 935 assess the available control space and the accuracy of our models. For this purpose, we consider the first floor of the "Large Office" reference building provided by EnergyPlus, Similarly, we assume MERV8 in-duct filters and that occupants are not wearing masks. For optimization variables, 941 we allow the minimum ventilation rate to be varied from its default level (chosen by EnergyPlus in accordance with 942 ASHRAE standards) to double that value, while we allow the supply temperature setpoint to be adjusted from its 943 default of 55°F up to 65°F. full year of the building operating with those variables using EnergyPlus to obtain the required BMS data. We then 948 use that BMS data with the proposed models to calculate daily values for energy cost and infection rate. We perform 949 this process for both a cold climate (TMY data from Chicago, IL) and a hot climate (TMY data from Houston, 950 TX). The results of these simulations are shown in Fig. 5 . For the purposes of energy accounting, we assume cooling 951 is provided via electricity at a COP of 3, while heating is provided by gas at 90% efficiency. We use an electricity 952 price of 0.12 $/kW h and a gas price of 0.80 $/therm. For brevity, we do not show thermal discomfort, although all 953 temperature comfort violations are below 4°F · h/day, and humidity comfort violations are generally confined to the 954 winter with indoor conditions being too dry. From these results, we see similar behavior as in the previous real-data examples, but with new trends emerging 956 from the new optimization variable. First, we note once again that infection rate is generally higher in the winter 957 months and lower in the summer months, simply due to variation in the average airflow provided by the HVAC 958 system. We note that this effect is much more pronounced in the Cold climate compared to Hot due to the weather-959 dependent cooling loads (and resulting airflow differences). Second, we see that for reducing infection risk, increasing 960 the supply temperature setpoint is less effective than increasing the ventilation rate in the heating season but more 961 effective in the cooling season. This observation is consistent with the fact that the HVAC systems often operate near 962 minimum-flow constraints during the heating season due to the small cooling load, and thus adjusting the supply 963 temperature setpoint has little to no effect on total airflow in these conditions. By contrast, adjusting the supply supply temperature is always more effective in this case.) Third, we see that increased ventilation almost always 967 requires additional energy consumption, and the magnitude is much higher in particularly hot or cold weather. The 968 explanation for this effect is that because the building is equipped with an economizer using an aggressive suitability 969 threshold, the system will automatically increase ventilation above its minimum value when energetically favorable. Thus, any additional ventilation that results from increasing the minimum ventilation setpoint necessarily requires an 971 energy penalty. By contrast, increasing the supply temperature setpoint can potentially reduce energy consumption, 972 and so it tends to be much less costly. Finally, we note that the HVAC system by itself has a somewhat narrow range to reduce the infection rate. Comparing the maximum and minimum infection rates on each day, we see less than a factor of two reduction. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. the mapped optimization sets (and thus the Pareto-optimal points within those sets) vary significantly based on the 985 weather, and thus optimal operation changes as well. Before moving on, we highlight some of the key features of these mappings. First, for the cases that come to 987 a sharp point in the upper left corner, it is evident that the value of the minimum ventilation rate becomes nearly 988 degenerate at high values of the supply temperature setpoint. The explanation for this behavior is that the higher 989 supply temperatures result in increased total supply airflow, and so the economizer will naturally increase outdoor-air 990 flow (to maintain roughly a constant outdoor-air fraction). Thus, increasing the minimum ventilation rate essentially 991 has no effect because the economizer is already providing more than that amount of ventilation. Second, we note that 992 increasing the ventilation rate uniformly leads to an increase in energy use. As observed in the previous examples, this 993 behavior is due to the aggressive economizer on this building: any time extra ventilation is energetically favorable, 994 it will be supplied automatically by the economizer; thus, any increased ventilation that results from changing the 995 minimum setpoint is necessarily at an energy penalty. We note that the use of energy-recovery ventilation systems 996 could significantly reduce this cost [44], but installation of such devices would be costly and perhaps not worthwhile 997 solely for reducing infection risk. Third, we see that increasing the supply temperature setpoint can decrease energy 998 cost at first but then eventually begins to increase it. This is generally due to the tradeoff between latent cooling load 999 (which decreases at higher supply temperatures) and fan power (which increases at higher flows caused by higher flow rate (since it is still at minimum) but requires additional energy consumption to heat the air to that temperature. re-scale the model's predictions to match the actual data using one single scale factor for the entire week. This the infection risk in buildings as operated. Furthermore, by adding additional models for space temperature and All rights reserved. No reuse allowed without permission. (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in perpetuity. The copyright holder for this preprint this version posted August 11, 2021. ; https://doi.org/10.1101/2021.08.10.21261866 doi: medRxiv preprint It is time to address airborne transmission of COVID-19 Aerosol emission and 1087 superemission during human speech increase with voice loudness Quantitative assessment of the risk of airborne transmission of 1090 -2 infection: Prospective and retrospective applications A guideline to limit indoor airborne transmission of COVID-19 A paradigm shift to combat indoor respiratory infection Speech can produce jet-like transport relevant to 1098 asymptomatic spreading of virus Air-borne infection The size and the duration of air-carriage of respiratory droplets and droplet-nuclei Effect of voicing and 1107 articulation manner on aerosol particle emission during human speech Size distribution and sites of origin of droplets expelled from the human respiratory tract during 1111 expiratory activities Modality of human expired aerosol size distributions Infection of air: Bacteriologic and epidemiologic factors Violent expiratory events: on coughing and sneez-1118 ing Fluid dynamics of covid-19 airborne infection 1120 suggests urgent data for a scientific design of social distancing Effects of ventilation on the indoor spread of 1122 COVID-19 The fluid mechanics of natural ventilation Estimating covid-19 exposure in a classroom setting: A comparison between mathe-1126 matical and numerical models Toward understanding the risk of secondary airborne infection: 1128 emission of respirable pathogens Dynamics of infectious disease transmission by inhalable respiratory 1130 droplets Covid-19 rarely spreads through surfaces. so why are we still deep cleaning Using a mathematical model to evaluate the efficacy of TB control measures Mathematical models for assessing the role of airflow on the risk of airborne 1138 infection in hospital wards Humidity-dependent decay of viruses, but not bacteria, in aerosols and droplets follows 1140 disinfection kinetics Back to normal: An old physics route to reduce SARS-CoV-2 transmission in indoor spaces Ultraviolet irradiation doses for coronavirus inactivation-1145 review and analysis of coronavirus photoinactivation studies Response to letters to the editor 1147 on aerosol filtration efficiency of common fabrics used in respiratory cloth masks: Revised and expanded results Puff trains in speaking produce long-range turbulent 1150 jet-like transport potentially relevant to asymptomatic spreading of viruses Towards improved social distancing 1153 guidelines: Space and time dependence of virus transmission from speech-driven aerosol transport between two 1154 individuals Asymptomatic transmission, the achilles heel of current strategies 1156 to control covid-19 Effectiveness of three versus six feet of physical distancing for controlling spread of covid-19 among primary 1159 and secondary students and staff: A retrospective, state-wide cohort study Mask use and ventilation improvements to 1163 reduce covid-19 incidence in elementary schoolsgeorgia Airborne spread of measles in a suburban elementary school The transmission of tuberculosis in confined spaces: 1168 an analytical review of alternative epidemiological models HVAC filtration for controlling infectious airborne disease transmission in indoor 1171 environments: predicting risk reductions and operational costs Risk of indoor airborne infection transmission estimated from carbon dioxide 1174 concentration Association of the infection probability of COVID-19 with ventilation rates in confined 1176 spaces A systematic approach to estimating the effec-1178 tiveness of multi-scale IAQ strategies for reducing the risk of airborne infection of SARS-CoV-2 The efficacy of social distance and ventilation effectiveness in preventing COVID-19 1181 transmission Exhaled co2 as covid-19 infection risk proxy for different indoor environments and 1183 activities Investigation of potential aerosol transmission and infectivity of SARS-CoV-2 through central 1186 ventilation systems Building readiness Economic, environmental and 1190 health implications of enhanced ventilation in office buildings Method for measuring performance of protable household electric room air cleaners Core recommendations for reducing airborne infectious aerosol exposure Development and testing of the characteristic curve fan model The relationship between filter pressure drop, indoor air quality, and 1201 energy consumption in rooftop HVAC units Estimates of the energy impact of ventilation and associated financial expenditures Energy vs. ventilation rate in buildings: A comprehensive scenario-based assess-1205 ment in the European context Why enthalpy economizers don't work Energy standard for buildings except low-rise residential buildings A simplified dynamic model for chilled-water cooling and dehumidifying coilspart 1: 1212 Development A simplified dynamic model for chilled-water cooling and dehumidifying coils-part 2: Experimental 1214 validation Dynamic modeling and self-optimizing operation of chilled water systems 1216 using extremum seeking control Development and evaluation of optimization-based air economizer strategies Ultraviolet germicidal irradiation handbook: UVGI for air and surface disinfection Optimizing the design of room air filters for the removal of submicrometer particles Exposure Factors Handbook Indoor occupancy estimation from carbon dioxide concentration Predicting occupancy 1228 counts using physical and statistical CO2-based modeling methodologies Bayesian filtering for building occupancy estimation 1231 from carbon dioxide concentration Scaling and related techniques for geometry problems Monitoring carbon dioxide to 1237 quantify the risk of indoor airborne transmission of COVID-19