key: cord-0745417-ckk67iom authors: Liu, Yang; Pan, Wuxuan; Long, Zhengwei title: Optimization of air supply parameters for stratum ventilation based on proper orthogonal decomposition date: 2021-08-21 journal: Sustain Cities Soc DOI: 10.1016/j.scs.2021.103291 sha: 4141ec3c0ee5bec5e71d9fc7778312f69145258d doc_id: 745417 cord_uid: ckk67iom Under the current COVID-19 epidemic conditions, stratum ventilation can provide treated fresh air directly into the human breathing zone, improving the air quality for inhalation. However, in the design of air supply parameters for stratum ventilation, the traditional trial-and-error and experimental methods are inefficient and time consuming, and they cannot be used to identify the optimal air supply parameters from a large number of parameters. Therefore, in this paper, the inverse design method based on proper orthogonal decomposition (POD) was applied to the design of ventilation parameters for a room with stratum ventilation. Predicted mean vote (PMV), predicted percentage dissatisfied (PPD) and droplet nuclei concentration in the human breathing zone were selected as design objectives to optimize air supply parameters. The transmission of COVID-19 was controlled by reducing the concentration of droplet nuclei in the respiratory area. The results show that, compared with the trial-and-error method, the inverse design method based on POD is more than 90% faster. POD method can greatly expand the sample size. Considering the dispersion of exhaled droplet nuclei in the room, the appropriate stratum ventilation parameters can reduce the concentration of fine droplet nuclei by more than 20% compared with the traditional design parameters. Nowadays, COVID-19 is a big problem for humanity's health and economy according to the negative impact of the virus on people's quality of life, leading to acute respiratory diseases, death, and financial crises worldwide (Rahmani & Mirmahaleh, 2021) . There are many modes of COVID-19 transmission, of which droplet transmission is considered the most important (Novel coronavirus pneumonia diagnosis and treatment plan (trial version 7), 2020). Morawska and Cao (2020) have found that aerosol propagation of COVID-19 is possible. The particle size of viruses is between 0.01 and 0.5 μm, and the particle size of the COVID-19 virus is between 0.08 and 0.16 μm (Li, Wu, Niu, & Gao, 2020) . Lindsley et al. (2010) found that the virus content of small particles was greater than that of large particles. Meanwhile, Jan, Euan, Mary-Louise, and D (2011) summarized the size of droplets produced by the human body under normal respiration. The results showed that the droplet size produced under normal breathing conditions was less than 5 μm. The small particle droplet nuclei produced in respiration cannot be ignored in the course of disease transmission. Air cleaning is an effective and reliable method in indoor airborne COVID-19 control . For most infectious diseases, ventilation can effectively reduce the probability of infection (Qian, Zheng & Zhang, 2012) . Therefore, it is of great importance to study ventilation parameters and droplet nuclei propagation for small particles. To cope with this pandemic, professionals in architecture, urban planning sectors, and design agencies have already switched their focus to visualize the post-pandemic era (Megahed & Ghoneim, 2020) . The choice of ventilation method has become very important. In the stratum ventilation method, fresh air is sent directly to the breathing zone of the human body, and the indoor air is fresher. Tian, Lin, Wang, and Liu (2009) and Lin, Wang, Yao, and Chow (2012) studied the diffusion of indoor particulate matter under stratum ventilation and displacement ventilation by numerical simulation. According to their results, the particle concentrations in the room overall and in the breathing zone under stratum ventilation were lower than those under displacement ventilation; as a result, the risk of particulate matter inhalation, and thus of pathogen inhalation, is lower under stratum ventilation. Tian et al. (2019) studied the ventilation characteristics of stratum ventilation, displacement ventilation and mixed ventilation. They found that stratum ventilation can ensure good air quality for indoor occupants, with better contamination exclusion than that provided by mixed ventilation or displacement ventilation. This effective contamination exclusion gives stratum ventilation a clear advantage during an epidemic, particularly in multi-row classrooms where students gather after returning to school. Therefore, this paper will optimize the air supply parameters of stratum ventilation from the perspective of controlling airborne diseases and thermal comfort. Considering the effective contamination exclusion and energy saving characteristics of stratum ventilation, this work will be of great importance for sustainable development of the post-pandemic era. Many people have studied the optimization of the supply air parameters of the stratum ventilation. Table 1 shows a summary of the studies on optimization of air supply parameters of stratum ventilation. The usual methods are experimental or numerical simulation. However, the experimental method is time-consuming, expensive and the study sample size is relatively small. The sample size of the numerical simulation method is larger than that of the experimental method, but it still takes a long time to obtain a large number of data. Therefore, the inverse design method based on proper orthogonal decomposition (POD) was applied to the design of ventilation parameters for a room with stratum ventilation. Summary of previous work on optimization of air supply parameters of stratum ventilation (air change per hour (ACH), supply air temperature (T), supply air velocity (V), air quality (AQI)). In recent years, inverse design methods have been widely used in the design of indoor air supply parameters. These methods, which include the computational fluid dynamics (CFD)-based adjoint method, CFD-based genetic algorithm method, and the proper orthogonal decomposition (POD) method, show promise in the inverse design of airflow and heat transfer in an enclosed environment . POD is an effective method for reducing CFD simulation effort (Feng, Yu & Cao, 2018) . In the continuous development and evolution of inverse design methods, Wei et al. (2019) integrated the POD method with other inverse design methods that can provide the optimal design for each design objective. In the design process, they demonstrated the efficiency of the POD method. Therefore, the POD method is adopted in this paper to optimize the supply air parameters of the stratum ventilation. To date, there is no relevant literature that applies the inverse design method based on POD to the design of air supply parameters for a room with stratum ventilation. The thermal comfort and air quality under stratum ventilation could be further improved with optimized air supply parameters. Since the traditional trial-and-error method and experimental methods are inefficient and time-consuming, they are not suitable for the analysis and optimization of the flow field under a large number of air supply parameters. Therefore, this study combined the use of the POD inverse design method to optimize the design of ventilation parameters in a stratum-ventilated room, and the goals of environmental thermal comfort and a reduction in the indoor droplet nuclei concentration. City University of Hong Kong has built an environmental chamber room for investigation of various ventilation methods. Numerous experiments and studies on stratum ventilation have been carried out in this chamber (Lin, 2011; Yao & Lin, 2014a) . It provides a useful reference value for the numerical simulation of stratum ventilation, as well as a large amount of experimental data to verify the accuracy of a numerical model. As described in this paper, we have optimized the air supply parameters of the environmental chamber and verified the numerical model with the experimental data provided in (Yao & Lin, 2014b) . The chamber is laid out as a classroom, and the layout and geometric model are shown in Fig. 1 and Fig. 2 In this study, STAR-CCM+ software was used for simulation calculations. Xu and Chen (2000) used the K-epsilon two-layer turbulence model to predict mixed convection by displacement ventilation in an office. The computed results agreed well with the corresponding airflow pattern and the distributions of air temperature, air velocity, air velocity fluctuation, and tracer-gas concentration. Therefore, the K-epsilon two-layer turbulence model was selected in this study. This model can be applied accurately to either low-Reynolds number type meshes of y + close to 1 or wall-function type meshes of y + greater than 30 (Rodi, 1991) . Because of the indoor heat source, we turned on the radiation model. For the simulation of droplet nuclei diffusion, Ai, Mak, Gao, and Niu (2020) demonstrated that a tracer gas is a suitable substitute for studying the air propagation of droplet nuclei in a building environment. It is found that under some indoor scenarios, the coronaviruses present in the respiratory droplets become active due to size reduction that occurs both in sessile and airborne droplet nuclei causing an increase in the spread (VR & Haghighat, 2020 ) . An extensive literature searches in Ai, Mak, Gao, and Niu (2020) indicated that tracer gas simulation is sufficiently accurate for study of the particle size of particles not larger than 3-5 μm. This size range represents the dominant portion of human expiratory droplet nuclei in terms of quantity. The passive scalar method is typically used to simulate the tracer gas and was therefore used to simulate the droplet nuclei from human expiratory in this study. To generate the mesh for this model, we used a trimmed cell mesher. Because the classroom model was more regular after simplification, it was appropriate to use a hexahedral mesh. The mesh at the inlet and at the source of droplet nuclei, i.e., the oral cavity of the human body, was encrypted. The simulated velocities of the validation case (in Section 3.1) at 20 positions uniformly distributed in two lines, i.e., Line 1 (X = 3.0 m, Y =2.875 m) and Line 2 (X = 6.6 m, Y = 2.875 m), were monitored and compared for three types of grid number, as shown in Fig. 3 . The velocities between 530,000 grids and 1,004,000 grids were close to each other, whereas large discrepancies existed at several positions between 219,000 grids and the other two types of gird number. Therefore, 530,000 grids were adopted with consideration of both accuracy and time cost. Inverse design concept uses the desired enclosed environment as the design objective and inversely determines the systems required to achieve the objective . POD method shows the promise in the inverse design of airflow and heat transfer in an enclosed environment. POD technology provides a linear approximation of a set of functions, which makes it easier to describe complex raw input data as the sum of weighted basis functions. This method is also called principal component analysis, and it can be used to extract the main feature components of data; it is often used to reduce the dimension of high-dimensional data. For the flow field, the coherent structure of the data can be extracted through analysis, and several linearly independent orthogonal bases are constructed. Thus, the physical field under any design parameters can be expressed as a linear combination of the orthogonal basis functions and its corresponding coefficients, so as to realize the dimensionality reduction and fast acquisition of the physical field. The mathematical process of POD is described in reference Chen, Reuss, and Sick (2012) . This paper only briefly introduces the necessary components. The data selected in this paper are the predicted mean vote (PMV) and predicted percentage dissatisfied (PPD) value near the human body and the average concentration of droplet nuclei in the human breathing zone, calculated by CFD simulation cases. The POD method is used to decompose the scalar field ( ) = ( ) ( ) ( ) (called snapshots; i is the index of the grid points in the scalar quantity distributions, and k is the snapshot index) into a linear combination of M spatial basis functions (POD modes, ) and the corresponding coefficients ( ) . The index of the grid points is arbitrary (e.g., they needn't correspond to the nodes of a mesh), but they must be the same order for all K snapshots. The scalar field composed of PMV, PPD and concentration data was reordered into a row in the same order. The average value of the data in the scalar field is removed. Then rearranged the data into the matrix (1) according to the sequence of snapshot. (1) Here, 'I' is the number of grid points of the selected scalar field, and 'K' is the number of snapshots. The spatial correlation matrix of the scalar field is defined as The scalar field can be reconstructed by the following formula: The first few orthogonal basis functions with large energy contributions can be selected to reduce the dimension of the original data field. The energy contained in the orthogonal basis function plays a key role in the number of orthogonal basis functions used in scalar field reconstruction. In general, if the cumulative energy of the selected by interpolation. Compared with CFD simulation, the POD method is very simple and efficient. In this study, multi-parameter and multi-objective optimization of the stratum-ventilated classroom was carried out, and the optimization strategy is shown in Fig. 4 . The whole process is divided into two parts. First, the data set is obtained through numerical simulation, and then the POD is used to expand it. Finally, the target parameters are obtained by filtering the data obtained through POD interpolation. The parameters to be optimized in this study are air supply temperature and air supply velocity. The optimization objectives were selected in accordance with the design requirements, and three POD optimization objectives were identified: |PMV| , PPD and the average concentration of droplet nuclei in the breathing zone of the human body. During the normalized phase of COVID-19, droplets or aerosol particles produced by infected personnel are considered as the potential source of infection with uncertain exposure risk (Ren et al., 2021) . In this study, the occupant of seat 3 was the potential source of infection. The dimensionless concentration (C d ) of droplet nuclei at the mouth opening of the occupant (seat 3) was set as 1, and the human respiratory volume was set as 6.6 L/min (Liu et al., 2014) . The cooling loads of the occupants, lighting and workstation were 17 × 70 W, 1176 W and 300 W, respectively . This study optimized the supply air temperature and velocity, and the optimal range of the supply air temperature was 17-26 ℃ (Shao, Wang, Li, & Lin, 2018) . In the study of , it is pointed out that when the air change per hour exceeds 15, it will cause greater draft risk, so the selection of maximum air change per hour should be less than 15.Therefore, the range of air supply velocity selected in this paper was 1.6-3.2 m/s (7.2-14.4 ACH) (Zhang, Cheng, Fang, Huan, & Lin, 2017) . In the calculation of PMV and PPD, we assumed that the classroom occupants were sedentary and wearing summertime clothing; thus, the clothing thermal resistance was 0.57 clo, and the human metabolic rate was 1.0 met (Shao, Wang, Li, & Lin, 2018) . The relative humidity in the room was set at 50%. Table 2 In the POD interpolation process, the step size for velocity interpolation was 0.05 m/s, and the step size for temperature interpolation was 0.25 ℃. Information for a total of 1221 flow fields was obtained by interpolation. In the process of POD orthogonal basis extraction, more than 95% of the "energy" was extracted in the flow field reconstruction. For validation of the environmental model shown in Fig. 1 Because the experimental data of the environmental model shown in Fig. 1 was not found, the experimental data of a classic office model of Yuan, Chen, Leon, Hu, and Yang (1999) was chosen for the passive scalar method verification. The geometric model of the experiment is shown in Fig. 6 . The simulation results for SF 6 concentration obtained by CFD simulation under the same boundary conditions on three lines in the figure were compared with the experimental data of Yuan et al. to verify the correctness of model selection and parameter settings in the passive scalar method. Geometric model of the office. The comparison between the experimental and simulation results is shown in Fig. 7 , which indicates that the concentration distribution was essentially consistent with the experimentally measured results. Generally speaking, the simulation results for the chamber were in good agreement with the experimental data. Passive scalar method can be used to simulate indoor concentration field. The interpolation results for the PMV and PPD field are shown in Fig. 8 . The optimal air supply parameters for |PMV| and PPD as the optimization objective were an air supply temperature of 19 ℃ and an air supply speed of 2.45 m/s. The PMV and PPD results obtained through POD interpolation were relatively smooth with the variation of each parameter. In this study, the influence of temperature on thermal comfort was greater than that of air supply velocity. The variation trend of PPD results was similar to PMV results. The temperature field and velocity field at the height of the inlet under the optimal air supply parameters calculated by CFD are shown in Fig. 9 , and the temperature on the air supply path was lower than in other areas. The air velocity was higher and the temperature was lower near the front row of the classroom than near the back row under stratum ventilation. The flow field and temperature field at this height were not uniform. Therefore, the thermal comfort of occupants in different After the concentration data under 1221 sets of air supply parameters were obtained by the POD interpolation method, the average scalar value of the droplet nuclei in the 17 occupants' breathing zones in each case was calculated. The average relative concentration ( / ) results are shown in Fig. 11 . On the whole, the average relative concentration of droplet nuclei in the human breathing zone decreased with the increase in air supply volume. The optimal air supply parameters under the optimization target were 26 ℃ and 3.15 m/s. The / with different temperature is compared for different zones in Fig. 14, where the sixteen seats have been divided into four zones (i.e., zones 1-4) of four seats each as shown in Fig. 1 . At different air supply temperatures, the concentration ratio of each region is roughly the same. It can be seen from Fig. 14 that temperature has little influence on the concentration distribution in each region. The results for the three optimization objectives were sorted, the comprehensive score was calculated to evaluate the optimization results under each air supply parameter, and then the appropriate air supply parameters were obtained. The proportions of different optimization objectives can be adjusted in accordance with the actual scenario. In the current epidemic situation, the proportion of thermal comfort can be reduced, and more attention can be paid to the freshness of indoor air and the effects of contamination exclusion. The health of occupants in confined spaces should be of utmost priority (Agarwal et al., 2021) . As an example, we set the weight of the concentration field optimization goal to 70% and the total weight of the PMV and PPD optimization goal to 30%. Scoring function can then be defined as The results are shown in Fig. 15 In general, POD interpolation must ensure that the selected basis function contains more than 90% of the total "energy", which in turn will ensure good interpolation and reconstruction of the flow field information under other parameters. "Energy" can be understood as the amount of information extracted. The energy ratios of the orthogonal basis functions extracted by the POD method are shown in Fig. 16 . Cumulative contribution of orthogonal basis function to total energy is shown in Fig. 17 . It can be seen that in the extraction of orthogonal basis functions, the energy proportion of mode 1 is above 60%, and the accumulated energy proportion of the first two modes is above 95%. When the PMV, PPD and concentration field results are extracted and reconstructed by orthogonal basis functions, two orthogonal basis functions can be used to reconstruct more than 95% of the cumulative energy. The PMV and PPD calculated by CFD for the other 20 cases was compared with the interpolation result from the POD method, and the error percentage is R and R : Here |PMV| and PPD represents the result of CFD calculation, and |PMV| and PPD represents the result of POD interpolation. The errors in the PMV and PPD results obtained by POD interpolation are shown in Table 3 and Table 4 , and the total average error was only 2.58% and 1.12%. Similarly, the percentage error for POD interpolation of concentration is R : Here represents the result of CFD calculation, while represents the result of POD interpolation. The errors in the POD interpolation results are shown in Table 5 , and the total average error was 3.89%. In this study, through numerical simulation, the inverse design method based on POD was applied for the first time to the design of ventilation parameters for a stratum-ventilated room. The numerical model was verified, and the accuracy and feasibility of the method were confirmed by comparison with experimental data. Taking PMV, PPD and the concentration of droplet nuclei in breathing zone as the optimization objective, the optimized air supply parameters were obtained. The transmission of COVID-19 was controlled by reducing the concentration of droplet nuclei in the respiratory area. The main conclusions are summarized as follows. (1) Compared with the traditional trial-and-error method, the inverse design method based on POD can reduce the calculation time by more than 90%. POD method can greatly expand the study sample size. In this study, through the flow field and concentration field data of 20 CFD cases, 1221 sets of data were obtained by interpolation after POD analysis. (2) In the current COVID-19 epidemic situation, where the indoor transmission of small droplet nuclei is a significant problem, the IF value can be reduced by more than 20% under the appropriate stratum ventilation parameters compared with the traditional design parameters. (3) The proportions of different optimization objectives can be adjusted in accordance with the actual scenario. In this work, the scoring function is set according to the optimization target of thermal comfort accounting for 30% and the optimization target of concentration accounting for 70%. Indoor air quality improvement in COVID-19 pandemic Tracer gas is a suitable surrogate of exhaled droplet nuclei for studying airborne transmission in the built environment On the use and interpretation of proper orthogonal decomposition of in-cylinder engine flows Effects of temperature and supply airflow rate on thermal comfort in a stratum-ventilated room Influence of air supply Angle on heating effect of stratum ventilation arranged on the same side of the return tuyeres in winter Technical feasibility of a stratum-ventilated room for multiple rows of occupants Removal of SARS-CoV-2 using UV+Filter in built environment Fast prediction for indoor environment: Models assessment Measurements of Airborne Influenza Virus in Aerosol Particles from Human Coughs A study of adult respiratory volume in State-of-the-art methods for inverse design of an enclosed environment Experimental study on air distribution characteristics in stratum ventilation chamber. Refrigeration & Air Conditioning Effect of Stratum Ventilation on Thermal Comfort and Energy Utilization Efficiency of Numerical Simulation Antivirus-built environment: Lessons learned from Covid-19 pandemic Airborne transmission of SARS-CoV-2: The world should face the reality Novel coronavirus pneumonia diagnosis and treatment plan (trial version 7) Prediction model of infection probability of air borne respiratory infectious diseases Coronavirus disease (COVID-19) prevention and treatment methods and effective parameters: A systematic literature review Mitigating COVID-19 infection disease transmission in indoor environment using physical barriers Experience With Two-Layer Models Combining the k-e Model With A One-Equation Model Near the Wall Potential of stratum ventilation to satisfy differentiated comfort requirements in multi-occupied zones The impact of temperature on mean local air age and thermal comfort in a stratum ventilated office Numerical Investigation of Indoor Aerosol Particle Dispersion under Stratum Ventilation and under Displacement Ventilation. Indoor and built environment Experimental study of local thermal comfort and ventilation performance for mixing, displacement and stratum ventilation in an office The contribution of dry indoor built environment on the spread of Coronavirus: Data from various Indian states Inverse design of aircraft cabin ventilation by integrating three methods Simulation of mixed convection flow in a room with a two-layer turbulence model An experimental and numerical study on the effect of air terminal layout on the performance of stratum ventilation An experimental and numerical study on the effect of air terminal types on the performance of stratum ventilation Measurements and computations of room airflow with displacement ventilation Optimization of room air temperature in stratum-ventilated rooms for both thermal comfort and energy saving Multi-criteria performance optimization for operation of stratum ventilation under heating mode Numerical Simulation of Indoor Thermal Environment Effected by Air Supply Temperature and Grille Angle on Stratum Ventilation in a Typical Office Influence of temperature difference of supply air on indoor thermal comfort under stratum ventilation This study was supported by National Science Foundation of China (Grant No.51878442). The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper.