key: cord-0733477-4j1et2od authors: Cadnum, Jennifer L.; Jencson, Annette L.; Alhmidi, Heba; Zabarsky, Trina F.; Donskey, Curtis J. title: Airflow patterns in double occupancy patient rooms may contribute to roommate-to-roommate transmission of severe acute respiratory syndrome coronavirus 2 date: 2022-04-27 journal: Clin Infect Dis DOI: 10.1093/cid/ciac334 sha: f45385c1d58e104740db6e5896964d292bd2e79b doc_id: 733477 cord_uid: 4j1et2od BACKGROUND: Hospitalized patients are at risk to acquire severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2) from roommates with unrecognized coronavirus disease 2019 (COVID-19). We hypothesized that airflow patterns might contribute to SARS-CoV-2 transmission in double occupancy patient rooms. METHODS: A device emitting condensed moisture was used to identify airflow patterns in double occupancy patient rooms. Simulations were conducted to assess transfer of fluorescent microspheres, 5% sodium chloride aerosol, and aerosolized bacteriophage MS2 between patient beds 3 meters apart and to assess the effectiveness of privacy curtains and portable air cleaners in reducing transfer. RESULTS: Air flowed from inlet vents in the center of the room to an outlet vent near the door, resulting in air currents flowing toward the bed adjacent to the outlet vent. Fluorescent microspheres (212-250 µm diameter), 5% sodium chloride aerosol, and aerosolized bacteriophage MS2 released from the inner bed were carried on air currents toward the bed adjacent to the outlet vent. Closing curtains between the patient beds reduced transfer of each of the particles. Operation of a portable air cleaner reduced aerosol transfer to the bed adjacent to the outlet vent but did not offer a benefit over closing the curtains alone, and in some situations resulted in an increase in aerosol exposure. CONCLUSION: Airflow patterns in double occupancy patient rooms may contribute to risk for transmission of SARS-CoV-2 between roommates. Keeping curtains closed between beds may be beneficial in reducing risk. Healthcare personnel and patients are at risk to acquire severe acute respiratory syndrome 2 coronavirus 2 (SARS-CoV-2) in hospitals [1] . Infection control measures including universal 3 masking, use of personal protective equipment, and pre-admission and pre-procedure screening 4 are commonly used to minimize the risk for transmission [1] . These measures are effective in 5 reducing, but not eliminating, the risk for acquisition of SARS-CoV-2 [2] [3] [4] [5] . In several studies, 6 viral sequencing has confirmed transmission of SARS-CoV-2 in healthcare settings, particularly 7 between co-workers and from patients with unrecognized coronavirus disease 2019 (COVID-19) 8 to personnel not wearing appropriate protective equipment 2,6-10]. Transmission from infected 9 personnel to hospitalized patients has also been demonstrated, but infrequently [2,11-12]. 10 In 3 recent reports, acquisition of SARS-CoV-2 by hospitalized patients has been linked 11 to roommates with unrecognized COVID-19 in double occupancy rooms [3,11-12]. The source 12 patients often tested negative for SARS-CoV-2 on admission with subsequent onset of symptoms 13 during their hospital stay. In these cases, the secondary attack rate has been surprisingly high, 14 ranging from 19% to 89% [3, [11] [12] . High viral burden and aerosol-generating procedures were 15 associated with increased risk for transmission to roommates [3, [11] [12] . 16 The mechanism of transmission of SARS-CoV-2 to hospital roommates is uncertain. 17 However, patients in shared rooms typically do not have close contact and are spaced more than 18 2 meters apart with closed curtains between beds. Thus, airborne transmission seems likely, 19 particularly given the association with aerosol-generating procedures [3, 11] . However, in 20 contrast to many indoor community settings, hospital rooms have ventilation requirements that 21 should reduce the risk for airborne transmission (ie, more than 6 air changes per hour versus 1 to 22 2 in many community buildings) [13] [14] . In recent studies, it has been proposed that patterns of airflow might have contributed to long-distance transmission of large and small droplets 1 containing SARS-CoV-2 in restaurants and in a patient transport van [15] [16] [17] [18] . Here, we 2 performed simulations to test the hypothesis that similar directional airflow patterns might 3 contribute to SARS-CoV-2 transmission in double occupancy patient rooms. We also evaluated 4 the effectiveness of privacy curtains and a portable air cleaner in reducing exposure to aerosol. Carbon dioxide monitoring to assess ventilation in double occupancy patient rooms 7 Carbon dioxide monitoring was conducted as part of a quality improvement assessment approved 8 by the Infection Control Committee of the Louis Stokes Cleveland VA Medical Center. Six 9 positive pressure double occupancy patient rooms with 8 to 11 air changes per hour were studied. Carbon dioxide levels were continuously monitored every 1 minute between 7 AM and 1 PM 11 using an IAQ-MAX CO2 Monitor and Data Logger (CO2Meter, Inc) [19] . The time of the 12 readings was selected because personnel commonly enter the rooms at that time for work rounds. All readings were collected in rooms occupied by 2 patients. Carbon dioxide levels were graphed 14 along with the number of people present in the rooms. 15 The Centers for Disease Control and Prevention (CDC) has recommended that carbon 16 dioxide readings above 800 ppm in buildings may be considered an indicator of suboptimal Efficacy of privacy curtains in reducing exposure to aerosolized bacteriophage MS2 17 We conducted simulations to assess the effectiveness of privacy curtains in reducing exposure to Carbon dioxide monitoring to assess ventilation in double occupancy patient rooms 12 During the 8-hour monitoring periods in 6 patient rooms, carbon dioxide levels remained below 13 800 ppm, ranging between 420 to 650 ppm. In addition to the 2 patients, each room was 14 intermittently occupied by 1 to 5 healthcare personnel conducting routine care activities over 15 periods of 2 to 20 minutes. Carbon dioxide levels consistently increased when personnel entered 16 the rooms for 10 minutes or more; the peak carbon dioxide level of 650 ppm occurred when 5 17 staff members were in a room for 10 minutes. As shown in Figure 1 .B, when the curtains were closed between the 2 beds fog flowed 6 above and to a lesser extent around the curtain before exiting through the outgoing air vent. The Figure 2 shows the particle counts detected at bed 1 (nearest to door) over 660 seconds after 3 release of 5% sodium chloride aerosol from bed 2 (farthest from door) with normal ventilation 4 versus with the incoming air vents covered. With normal ventilation, particle counts peaked 90 5 seconds after release at 58,045 particles detected and then rapidly declined to baseline. With the 6 vents closed, particle counts peaked at a much lower level 480 seconds after release but persisted 7 at above 6,000 particles detected through the 660 seconds of monitoring. 8 Figure 3 shows the impact of privacy curtains with or without a portable air cleaner on 9 the average peak number of aerosol particles detected at bed 1 (after release from bed 2) and bed 10 2 (after release from bed 1) for the 3 experiments. With the curtain open, peak particle counts 11 were much higher at bed 1 versus bed 2. Closing the curtain substantially reduced the average 12 peak particle counts detected at bed 1 (44,064 to 2,218) and bed 2 (5,470 to 1,162). With the curtain open, operation of the portable air cleaner in either position substantially 14 reduced peak particle counts detected at bed 1. However, operation of the air cleaner in either 15 location did not substantially decrease the average particle counts detected at bed 2; release of 16 fog in the room demonstrated that the air cleaners created turbulent airflow in proximity to the 17 device that altered the normal airflow such that some outgoing air was pulled toward bed 2. Operation of the air cleaner at either location in combination with closing the curtains resulted in 19 higher average peak particle counts at bed 1 and bed 2 than closed curtains alone. In both cases, 20 release of fog demonstrated that the air cleaners created turbulent airflow that pulled fog toward 21 the beds where particle counts increased. Our results provide support for the hypothesis that airflow patterns in double occupancy patient 17 rooms may contribute to risk for transmission of SARS-CoV-2 between roommates and suggest 18 that keeping curtains closed between beds may be beneficial in reducing risk. Our findings are consistent with recent reports that have implicated patterns of airflow in 20 transmission of SARS-CoV-2 in restaurants and motor vehicles [15] [16] [17] [18] . Jones et al. [15] Transmission of SARS-CoV-2 on a patient 3 transport van droplet transmission of SARS-CoV-2 by direct air flow in a restaurant in Korea COVID-19 outbreak associated with air conditioning in restaurant Probable airborne transmission of SARS-CoV-2 in a poorly 11 ventilated restaurant Use of carbon dioxide measurements to assess ventilation in an acute care hospital Airborne transmission of respiratory viruses A vibrating mesh 19 nebulizer as an alternative to the collison three-jet nebulizer for infectious disease 20 aerobiology 13 filter box fan air cleaner in reducing aerosolized bacteriophage MS2 Control Hosp Do plexiglass barriers reduce the risk for 3 transmission of severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2)? Efficacy of portable air cleaners and masking for 6 reducing indoor exposure to simulated exhaled SARS-CoV-2 aerosols -United States Efficacy of ventilation, HEPA air cleaners, 9 universal masking, and physical distancing for reducing exposure to simulated exhaled 10 aerosols in a meeting room Testing mobile air purifiers in a school classroom: 12 reducing the airborne transmission risk for SARS-CoV-2 Performance analysis of 15 portable HEPA filters and temporary plastic anterooms on the spread of surrogate 16 coronavirus Laboratory study of physical barrier 18 efficiency for worker protection against SARSCoV-2 while standing or sitting