key: cord-0732735-j8ts1ung authors: Lu, Yiran; Li, Yifan; Zhou, Hao; Lin, Jinlan; Zheng, Zhuozhao; Xu, Huji; Lin, Borong; Lin, Minggui; Liu, Li title: Affordable measures to monitor and alarm nosocomial SARS‐CoV‐2 infection due to poor ventilation date: 2021-06-28 journal: Indoor Air DOI: 10.1111/ina.12899 sha: a005253ba35d97cbabc3497af2887b0f17de31d7 doc_id: 732735 cord_uid: j8ts1ung Since the coronavirus disease 2019 (COVID‐19) outbreak, the nosocomial infection rate worldwide has been reported high. It is urgent to figure out an affordable way to monitor and alarm nosocomial infection. Carbon dioxide (CO(2)) concentration can reflect the ventilation performance and crowdedness, so CO(2) sensors were placed in Beijing Tsinghua Changgung Hospital's fever clinic and emergency department where the nosocomial infection risk was high. Patients’ medical records were extracted to figure out their timelines and whereabouts. Based on these, site‐specific CO(2) concentration thresholds were calculated by the dilution equation and sites’ risk ratios were determined to evaluate ventilation performance. CO(2) concentration successfully revealed that the expiratory tracer was poorly diluted in the mechanically ventilated inner spaces, compared to naturally ventilated outer spaces, among all of the monitoring sites that COVID‐19 patients visited. Sufficient ventilation, personal protection, and disinfection measures led to no nosocomial infection in this hospital. The actual outdoor airflow rate per person (Q (c)) during the COVID‐19 patients’ presence was estimated for reference using equilibrium analysis. During the stay of single COVID‐19 patient wearing a mask, the minimum Q (c) value was 15–18 L/(s·person). When the patient was given throat swab sampling, the minimum Q (c) value was 21 L/(s·person). The Q (c) value reached 36–42 L/(s·person) thanks to window‐inducted natural ventilation, when two COVID‐19 patients wearing masks shared the same space with other patients or healthcare workers. The CO(2) concentration monitoring system proved to be effective in assessing nosocomial infection risk by reflecting real‐time dilution of patients’ exhalation. April 28, 2020, excluding HCW infections, the proportion of patient nosocomial infections with SARS-CoV-2 was 12.5% in 10 UK hospitals and 1 Italian hospital. 13 General patients attending hospitals are vulnerable to infection by the virus. 14 In brief, the scale of hospitalacquired SARS-CoV-2 infection cannot be neglected. In pandemics, the fast-spreading diseases on top of other diseases, especially those requiring regular treatment and those that are seasonal, can cause overcrowding in hospitals and shortages of equipment needed to care for patients and HCWs. [15] [16] [17] A maximum capacity based on social distancing may be incorporated in hospital designs, 18, 19 but is often not implemented in practice. Crowds lead not only to the violation of the minimum social distance to avoid short-range transmission of respiratory droplets, 20 but also to inadequate dilution of fine droplets and droplet nuclei by the building ventilation system. 21 Recent studies have revealed that the release strength of SARS-CoV-2 from a patient can reach millions of copies per hour. 22, 23 Hand hygiene and wearing masks can likely eliminate the transmission of most expiratory viruses. [24] [25] [26] [27] [28] Whether the remaining viruses, if any in the air, can cause infection depends on the critical infection dose, the intake and immune system of the susceptible person. 29, 30 Poor indoor ventilation can lead to a high intake of the virus and potential infection. [31] [32] [33] [34] [35] The dose, intake, and immune response are unknown and potentially case-dependent, which makes it challenging to identify the absolute infection risk caused by insufficient ventilation. Confirmation of SARS-CoV-2 infection requires strong evidence incorporating computed tomography (CT) imaging features, epidemiology history, clinical manifestation, and pathogen serum examination. It is time-consuming and fails to reflect the increasing nosocomial risk to HCWs and patients. 36 In this study, carbon dioxide (CO 2 ) concentration was taken as an indicator of human exhalation and indoor ventilation performance, so sensors were placed in Beijing Tsinghua Changgung Hospital (Abbreviated as Changgung Hospital) at the end of January 2020. We also estimated the actual outdoor airflow rate per person during the presence of COVID-19 patients. The experience and evidence may help hospitals and authorities to determine a strategy to minimize nosocomial SARS-CoV-2 infection. At present, reverse transcription-polymerase chain reaction (PCR), droplet digital PCR, and isothermal amplification, among other methods, are applicable for quantitatively analyzing the environmental contamination of SARS-CoV-2 to demonstrate possible risks in less than 1 h. [37] [38] [39] [40] [41] [42] [43] A fluorescence spectrometer can measure viable microorganisms, 44 but the quantity is not correlated with the quantity of pathogens. Real-time environmental surveillance technology of SARS-CoV-2 and many other pathogens is yet to come. Unlike the abovementioned methods for direct detection, the CO 2 concentration distribution can trace human exhalation in almost real time, and the difference between indoor and outdoor concentrations can reveal the dilution performance of ventilation for a known number of indoor occupants' exhalation if there are no other significant sources of CO 2 , such as combustion. 45 Thus, the CO 2 concentration is an adequate index of the potential infection risk posed by poor ventilation in comparison with other methods, as shown in Table 1 . If ventilation is supplied by a mechanical system and the flow rate is constant, the CO 2 concentration indicates the crowdedness; if the number of occupants is known, it indicates the performance of ventilation. A surveillance campaign was conducted at the Changgung Hospital from the beginning of the outbreak in January 2020. In accordance with symptoms of patients diagnosed with COVID-19 and the patients' whereabouts, we deployed 32 iBEEM sensors in areas with a high incidence of COVID-19 patients ( Figure 1 ). The sensors, whose measurement interval is 5 min, were placed approximately 0.8-1.2 m above ground and far from CO 2 emission sources to collect real-time ambient CO 2 concentration. The measurement area covered the fever clinic (FC) and the emergency department which was in the outpatient building. The former adopts natural ventilation, the latter adopts mechanical ventilation. Changgung Hospital implemented masks, physical distancing, and other preventive measures to control nosocomial infection (Appendix S1A). With the infection control measures in place, neither HCWs nor patients were infected within Changgung Hospital throughout the COVID-19 pandemic. • The present study explores an effective method to monitor and alarm nosocomial infection by reflecting realtime dilution of patients' exhalation. • In this study, aided with personal protection and disinfection measures, outdoor airflow rate per person of 15-18 L/(s·person) was sufficient to prevent nosocomial infection when there was only one COVID-19 patient, and 21 L/(s·person) was sufficient during throat swab sampling. • This study provides evidence on affordably controlling nosocomial infection during the COVID-19 pandemic using a real-time CO 2 concentration monitoring system. Five COVID-19 patients went to Changgung Hospital in February 2020 and they were numbered as C1-C5 according to the order of their registration time. Based on their medical records, they went to the pediatric hall, emergency hall, FC, and CT room ( Figure 1 ). HCWs with adequate personal protective equipment (PPE) were in close contact with infectors in the CT room and FC nursing station for less than 5 min and in the FC consulting room and emergency internal medicine (EIM) consulting room for at least 5 min. Unconscious close contact of more than 5 min between infectors and susceptible people occurred in the pediatric hall, emergency hall, and FC waiting area. Prolonged or close contact indicates a higher infection risk. The ventilation performance of those areas is critical for diluting exhalation from the infectors. Therefore, this study focused on the ventilation performance of areas visited by COVID-19 patients. This study was approved by the ethics commissions of Changgung Hospital and the sampling procedure did not obstruct routine medical care procedures at the hospital. Adequate ventilation can dilute the exhalation of confirmed patients in the hospital, reduce the residence time of the exhaled substances, and the possibility of other patients being exposed to the coronavirus. CO 2 concentration has been used as an indicator to estimate ventilation rates and characterize ventilation for decades. If sufficiently ventilated and the occupancy is stable, the CO 2 exhaled by people will be quickly diluted to a steady state. Based on the dilution equation, the theoretical upper limit of the CO 2 concentration (C u ) can be represented by Equation (1), as follows: where C u is the theoretical upper limit of the CO 2 concentration (ppm); C o is the outdoor CO 2 concentration (ppm); G m is the indoor personnel total CO 2 generation rate when the number of people in the room reaches the maximum (m 3 /h) (Appendix S1B); and Q is the outdoor airflow rate (m 3 /h). Each site's C u varied (Table 2) , so the CO 2 dilution index (I d ) and the risk ratio (R r ) were used to briefly compare and evaluate all of the sites' outdoor air ventilation performance. The I d compares the ventilation effectiveness between the natural ventilation implemented in the FC and the mechanical ventilation applied in the outpatient building and is expressed as follows (Equation (2)): where C is the measured real-time CO 2 concentration (ppm). I d > 1 indicates that the air ventilation is poorer than the designed/required condition, and thus the risk of nosocomial infection rises. (1) C u = C o + 10 6 G m Q (2) The R r is the time proportion of I d > 1, so it quantitatively describes how often the site had a poor CO 2 dilution condition. If one site's long-term R r exceeded 50%, namely, the CO 2 concentration at one site exceeded the threshold over half of a long period, its outdoor air supply was deemed insufficient to dilute the occupants' exhalation during normal operation. where g is the CO 2 generation rate per person [m 3 /(h·person)], which was estimated by directly measured statistics 46 (Appendix S1B) for the lack of occupants' body mass data; and C e is the equilibrium CO 2 concentration measured in the presence of COVID-19 patients (ppm). The implement of the Equation (3) should also meet the requirements below: (a) the target zone is free from air exchange with other indoor zones which has different CO 2 concentration; (b) the average CO 2 generation rate per person is constant and known; (c) the CO 2 concentration in the target is at equilibrium. During our measurements at Changgung Hospital, only five COVID-19 patients arrived for treatment. Nonetheless, during their presence and in the first hour of absence, we collected 510 CO 2 concentration data points ( Figure 1D ). Furthermore, throughout according to the order of their registration time. According to medical records, the diagnosis process for confirmed patients is outpatient clinic, CT room, and isolation ward. Patient C1 went to the pediatrics department, emergency hall, CT room, and isolation ward. Patient C2-C4 went to the fever clinic, emergency hall, CT room, and isolation ward. Patient C5 went to the emergency hall, emergency internal medicine, CT room, and isolation ward. d The sensors were placed approximately 0.8-1.2 m above ground and far from CO 2 emission sources. The measurement range of the sensor is calibrated between 400 and 1000 ppm, its accuracy is ±50 ppm and its measurement interval is 5 min pattern. CT room: before a CT scan, a doctor will be in the CT room to prepare the patient for the scan, and then the doctor will leave. The preparation and scan both take approximately 2 min, so the upper limit of the occupant number was set as 1.5 rather than 1.0. EIM consulting room: usually one patient with one relative and one doctor. FC nursing station and consulting room: usually 2 healthcare workers and one patient with one relative. b The required minimum outdoor air change rate was taken from the G m /Q, where C o is the outdoor air CO 2 concentration, which was assumed to be 419 ppm (1 ppm = 10 −6 mol/mol) for the outpatient building and 400 ppm for the FC. Sites in the outpatient building were mechanically ventilated, and their designed outdoor airflow rate (Q) as well as designed outdoor air change rate (n d ) was listed. Because sites in the FC were naturally ventilated, their Q value was estimated by the required minimum outdoor air change rate (n r ). Q = n r Ah, where h is the height of a room, which was 3 m in this study. d The monitored real-time CO 2 concentration in the emergency hall, EIM waiting room, and consulting room were significantly correlated with one another according to the Pearson correlation analysis [r = 0.596−0.841; p < 0.01 (2-tailed)], which indicated that the indoor air was well-mixed. The emergency hall, EIM waiting room, and consulting room were combined, so the total generation rate of CO 2 was calculated separately and then added. The designed flow rate was also added to calculate the theoretical upper limit of the CO 2 concentration. Generally, I d and R r were higher in mechanically ventilated inner spaces, and I d,p was usually higher than the mean value of the corresponding I d,f . In other words, natural ventilation dilutes airborne contaminants better than mechanical ventilation in Beijing in winter. aims to compare all of the sites' ventilation conditions by nondimensionalizing the CO 2 concentration, where C is the measured real-time CO 2 concentration, which was measured at eight sites (ppm); C o is the outdoor air CO 2 concentration, which was 419 ppm for sites equipped with mechanical ventilation in the outpatient building and 400 ppm for sites relying on natural ventilation in the fever clinic (FC); C u is the theoretical upper limit of the CO 2 concentration, which was 505, 963, and 793 ppm for the CT room, pediatric hall, and the remaining three sites in outpatient building, and 867, 902, and 864 ppm for the waiting area, consulting room, and nursing station in the FC, respectively. I d > 1 indicates that the ventilation condition is relatively poor compared with the designed/required condition, and thus the risk of hospitalacquired infection increases. I d should be between 0 and 1 so that R r is defined as the proportion of I d > 1. Real-time concentrations that were below the set outdoor air concentration were excluded when calculating I d . d The top arrow shows that the sites were placed in order of closeness to the outdoors. The CT room, EIM consulting room, and waiting room had no outer windows/doors. However, the latter two rooms were directly connected to the emergency hall, which had an outer door, through an open inner door. The emergency hall, pediatric hall, and FC waiting area all had outer doors that were frequently opened. The FC consulting room had one open outer window, whereas the nursing station had two. e The green rectangle represents the safe zone. The zone indicates that the ventilation condition is good and droplets was supposed to be higher. Under the protection of This is the first study to quantitatively provide a recommended outdoor airflow rate per person to prevent SARS-CoV-2 nosocomial infection based on a CO 2 monitoring system set in an undesignated hospital where COVID-19 patients were treated during the pandemic. However, our study still has some limitations. First, due to the need to maintain patients' personal privacy, we had no access to surveillance video. Therefore, much background information was unknown, such as the actual occupancy inside each monitoring site, the type of masks and the way the patients wore them, the actual social distance that the patients kept, and the virus shedding pattern of COVID-19 patients, including coughing and sneezing frequency. According to an official survey, approximately 98% of Beijing citizens wore face masks when they went to the hospital during the COVID-19 pandemic, and 98% of those wore disposable face masks, medical surgical masks, and N95 or KN95 masks. 47 Therefore, we assumed that all of the patients and their relatives in Changgung Hospital wore masks. Second, the outdoor CO 2 concentration was estimated using data collected indoor when the target sites were unoccupied (Appendix S1B) rather than real-time outdoor measurement. Considering that the outdoor CO 2 concentration fluctuates with time, taking a specific value may result in overestimating of the Q c value on some days while underestimating on other days. Third, the monitoring sites were not isolated from other sites with different CO 2 concentration, which is required to use equilibrium CO 2 analysis but was impossible during the hospital's daily operations. Furthermore, the airflow pattern between adjacent spaces during daily operation, the CO 2 concentration in adjacent spaces, and the CO 2 distribution inside most of the target sites were not determined. These would add uncertainty to the estimated outdoor airflow rates. Two sensors were set in the emergency hall due to its large area, and over 99% of the real-time CO 2 concentrations measured in February by these two sensors were within 10% of the mean value difference. Therefore, we assumed that the indoor air was also well-mixed in other sites with a smaller area. We also ensured that each CO 2 concentration period fluctuated within 10% (15%) of the mean value difference when calculating the outdoor airflow rate per person using equilibrium analysis in mechanically (naturally) ventilated sites. Fourth, the occupants' CO 2 generation rate was estimated by directly measuring the CO 2 generation of healthy people, 46 to American Society for Testing and Materials international standard D6245-18. Q c = 10 6 g/[3.6(C e -C o )], where g is the carbon dioxide (CO 2 ) generation rate per person [m 3 /(h·person)], which was estimated by directly measured statistics 46 (Appendix S1B) for the lack of occupants' body mass data; C e is the equilibrium CO 2 concentration measured in the presence of COVID-19 patients (ppm); and C o is the outdoor CO 2 concentration, which was 419 ppm for the outpatient building and 400 ppm for the fever clinic. b Changgung hospital requires patients to wear masks. Patients who come to the hospital for treatment wear disposable masks, medical surgical masks, and N95 or KN95 masks. The throat swab was sampled immediately after a patient had been diagnosed as a COVID-19 suspected case. The consulting process was supposed to last for more than 5 min, so the swab sampling process was sorted into the same categorize, but listed separately. Furthermore, clinic spaces in which patients with aerosol infectious diseases are likely to be present should be located in the outer spaces of outpatient buildings to introduce natural ventilation quickly and easily at the beginning of a pandemic. It is affordable and effective to deploy CO 2 sensors to reveal nosoco- (1) Ventilation conditions can be easily evaluated using the realtime CO 2 concentration as an indicator. We recommend that hospitals install a CO 2 concentration monitoring system to provide a warning of the risk of nosocomial infection due to poor ventilation. (2) According to this case study conducted in Changgung The authors would like to thank Yizhou Bai, Zhe Zhao, Kaili Chen, Hospital, for their thorough support in sensor deployment, equipment maintenance, and data sharing. No conflict of interest was declared. The peer review history for this article is available at https://publo ns.com/publo n/10.1111/ina.12899. Li Liu https://orcid.org/0000-0001-8512-8676 WHO coronavirus disease (COVID-9 Rapid implementation of SARS-CoV-2 sequencing to investigate cases of health-care associated COVID-19: a prospective genomic surveillance study Does nosocomial COVID-19 result in increased 30-day mortality? A multi-centre observational study to identify risk factors for worse outcomes in patients with COVID-19 Risk of COVID-19 among front-line health-care workers and the general community: a prospective cohort study Hospital-acquired SARS-CoV-2 infection: lessons for public health SARS-CoV-2 infection among healthcare workers in a hospital in Madrid, Spain Transmission of COVID-19 to health care personnel during exposures to a hospitalized patient Epidemiology of Covid-19 in a long-term care facility in king county. Washington Presymptomatic SARS-CoV-2 infections and transmission in a skilled nursing facility Death from Covid-19 of 23 health care workers in china Healthcare worker infections and deaths due to COVID-19: a survey from 37 nations and a call for WHO to post national data on their website Clinical characteristics of 138 hospitalized patients with 2019 novel coronavirus-infected pneumonia in Wuhan Nosocomial COVID-19 infection: examining the risk of mortality. The COPE-nosocomial study (COVID in Older People) Clinical characteristics of 140 patients infected with SARS-CoV-2 in Wuhan Critical supply shortages-the need for ventilators and personal protective equipment during the Covid-19 pandemic Effective strategies to prevent coronavirus disease-2019 (COVID-19) outbreak in hospital what other countries can learn from Italy during the COVID-19 pandemic Small droplet aerosols in poorly ventilated spaces and SARS-CoV-2 transmission Short-range airborne transmission of expiratory droplets between two people Short-range airborne route dominates exposure of respiratory infection during close contact How can airborne transmission of COVID-19 indoors be minimised? COVID-19 patients in earlier stages exhaled millions of SARS-CoV-2 per hour Emergence of a highly fit SARS-CoV-2 variant Physical distancing, face masks, and eye protection to prevent person-to-person transmission of SARS-CoV-2 and COVID-19: a systematic review and meta-analysis Respiratory virus shedding in exhaled breath and efficacy of face masks Hand hygiene and the novel coronavirus pandemic: the role of healthcare workers Effectiveness of face masks in preventing airborne transmission of SARS-CoV-2. mSphere Face mask use in the general population and optimal resource allocation during the COVID-19 pandemic Supporting the health care workforce during the COVID-19 global epidemic Aerodynamic analysis of SARS-CoV-2 in two Wuhan hospitals COVID-19 outbreak associated with air conditioning in restaurant Aerosol and surface stability of SARS-CoV-2 as compared with SARS-CoV-1 Aerosl and surface distribution of severe acute respiratory syndrome coronavirus 2 in hospital Wards Factors involved in the aerosol transmission of infection and control of ventilation in healthcare premises Indoor transmission of SARS-CoV-2. Indoor Air Reducing nosocomial transmission of COVID-19: implementation of a COVID-19 triage system Recognizing and controlling airborne transmission of SARS-CoV-2 in indoor environments Effects of ventilation on the indoor spread of COVID-19 Overcoming the bottleneck to widespread testing: a rapid review of nucleic acid testing approaches for COVID-19 detection Investigating SARS-CoV-2 surface and air contamination in an acute healthcare setting during the peak of the COVID-19 pandemic in London Environmental contamination in the isolation rooms of COVID-19 patients with severe pneumonia requiring mechanical ventilation or high-flow oxygen therapy Detection of air and surface contamination by SARS-CoV-2 in hospital rooms of infected patients Surface environmental, and personal protective equipment contamination by severe acute respiratory syndrome coronavirus 2 (SARS-CoV-2) from a symptomatic patient Review of bioaerosols in indoor environment with special reference to sampling, analysis and control mechanisms Risk of indoor airborne infection transmission estimated from carbon dioxide concentration Carbon dioxide generation rates of different age and gender under various activity levels Public awareness and mask usage during the COVID-19 epidemic: a survey by China CDC new media Contamination inside CT gantry in the SARS-CoV-2 era Environmental contamination of SARS-CoV-2 in healthcare premises Rapid response to an outbreak in Qingdao, China Air purifiers: a supplementary measure to remove airborne SARS-CoV-2