key: cord-0702899-jrgeasqy authors: Di Gilio, Alessia; Palmisani, Jolanda; Pulimeno, Manuela; Cerino, Fabio; Cacace, Mirko; Miani, Alessandro; de Gennaro, Gianluigi title: CO(2) concentration monitoring inside educational buildings as a strategic tool to reduce the risk of Sars-CoV-2 airborne transmission date: 2021-07-03 journal: Environ Res DOI: 10.1016/j.envres.2021.111560 sha: e4d48f25c5ba4c7eb7f240ca6455cc3cc8bb620b doc_id: 702899 cord_uid: jrgeasqy In order to avoid SARS-CoV-2 transmission inside educational buildings and promote the safe reopening of schools, the Italian Government, in line with the other European countries and in accordance with the WHO recommendations, adopted a contingency plan including actions able to guarantee adequate air ventilation in classrooms. Therefore, in this pilot study, a surveillance activity based on the real-time monitoring of CO(2) levels as a proxy of SARS-CoV-2 transmission risk, was conducted inside 9 schools (11 classrooms) located in Apulia Region (South of Italy) during the reopening of schools after the lockdown due to COVID-19 pandemic. More specifically, monitoring activities and data treatment were conducted to evaluate the initial scenario inside the classrooms (first stage of evaluation) and the potential improvements obtained by applying a detailed operating protocol of air ventilation based on specific actions and the simultaneous real time visualization of CO(2) levels by non-dispersive infrared (NDIR) sensors (second stage of evaluation). Although, during the first evaluation stage, air ventilation through the opening of windows and doors was guaranteed, 6 (54%) classrooms showed mean values of CO(2) higher than 1000 ppm and all classrooms exceeded the recommended CO(2) concentration limit value of 700 ppm. The development and implementation of tailored ventilation protocol including the real time visualization of CO(2) levels allowed to depict better scenariosAn overall improvement of CO(2) levels was indeed registered for all classrooms where teachers were compliant and helpful in the management of the air ventilation strategy. Therefore, this study reports the first evidence-based measures demonstrating that, with the exception of few environments affected by structural limits, the real-time visualization and monitoring of CO2 concentrations allowes effective air exchanges to be implemented and contributes to prevent SARS-CoV-2 transmission. Moreover, on the basis of the monitoring outcomes and in order to ensure adequate air ventilation in educational buildings, a 4 level-risk classification including specific corrective actions for each level was provided. The Severe Acute Respiratory Syndrome Coronavirus-2 (SARS-CoV-2) is the responsible agent of taking into account that both students and teachers share the same space for at least 5 hours a day. 85 Moreover, due to the need for maintaining thermal comfort during the winter season and for 86 limiting the external noises, classrooms are often isolated and it's reasonable to assume that, 87 especially in absence of a mechanical ventilation system, the air cannot be adequately renewed. 88 This represents a critical issue in the COVID-19 pandemic era. Inside unvented or insufficiently 89 vented classrooms, indeed, an infected asymptomatic teacher or student could spread a virus- Ventilation and Air Conditioning systems (HVAC) and thus, venting is usually done by opening the 107 windows during the breaks. In the same way, air cleaner systems such as electronic ones (e.g. specifically, in addition to social distancing and mask wearing, the indoor CO 2 monitoring is 127 suggested as practical proxy of the transmission risk of respiratory infectious disease. Indeed, in 128 indoor environments an excess of CO 2 is usually due to human exhalation and an increase of CO 2 129 levels over outdoor levels could be related to the increased probability to inhale breath exhaled by 130 other people and thus, to infection risk (Rudnick and Milton, 2003; Peng and Himenez, 2021) . None of the selected educational buildings is equipped with a mechanical ventilation system able to (Table 1S) . At this regard, the 286 J o u r n a l P r e -p r o o f percentage relative standard deviation determined for each single sensor revealed to be below 7% 287 (Table 2S) . When compared to the AQ Guard analyzer, the eleven NoseC sensors generally have 288 overestimated the CO 2 concentrations over the explored concentration range (400-900 ppm). 289 However, the percentage relative standard deviation determined for each NoseC sensor with respect 290 to the AQ Guard analyzer is not significant reaching in only one case the maximum value of 14% 291 (Table 2S) classrooms) exposed to indoor CO 2 concentrations higher than 1000 ppm highlighted the outbreak 308 of higher risk for dry cough and rhinitis. Moreover, CO 2 levels higher than 1000 ppm were 309 associated with decreasing of cognitive scores (productivity and learning ability) (Allen et al., Table 2 ). This evidence supports the hypothesis that the number of persons is not the only 349 factor that explains the CO 2 level behaviour. that only looking at the real time data, it is possible to promote effective air exchanges able to lower 394 CO 2 levels to background values. In fact, for example in Figure 5 are shown the evolutions of CO 2 395 levels along school hours in the same classroom and during two days: when the teacher looks (21 th 396 January) and not looks (19 th January) at real time CO 2 data. It is remarkable to underline that a 397 tailored modulation of actions for air ventilation allowed for classroom 3A to maintain the CO 2 398 concentration at low levels preserving at the same time the thermal comfort of the students despite 399 the cold temperatures registered during the monitoring period. Indeed, the mean indoor temperature the CO 2 concentrations constantly remained above the 700 ppm reaching peak values in some cases 413 higher than 1000 ppm (as a mere example 26 th January is reported in Figure 6 ). This evidence can European countries in accordance with the WHO, educational buildings often fail in contagion 485 containment due to the presence of a high number of students inside enclosed environments for 486 several hours a day. In these conditions, indeed, the probability that a subject re-inhales the air 487 exhaled by another potentially infected bystander and thus, the SARS-CoV-2 transmission 488 probability result relatively high. Therefore, in order to safely promote the school re-opening, 489 adequate ventilation plans able to guarantee more effective fresh air exchanges should be adopted. In this pilot study, a surveillance activity based on real time monitoring of CO 2 levels, was 491 conducted inside 9 schools (11 classrooms) located in Apulia Region (South of Italy) in order to 492 evaluate the effectiveness of their ventilation protocols and suggest tailored corrective actions able 493 to limit SARS-CoV-2 transmission risk. The development of tailored operating protocols of air ventilation and their prompt implementation in relation to the real time visualization of CO 2 levels, 495 allowed to promote more effective air exchanges while guaranteeing the thermal comfort of 496 students. Anyway, even if real-time monitoring of CO 2 levels and the implementation of proper 497 protocols were provided, for some classrooms the only natural ventilation resulted to be not 498 effective to guarantee adequate air exchanges due to building structural limits. Therefore, in these 499 cases, further strategies based on the installation of heating, ventilation and air conditioning 500 systems and air cleaner devices are needed to ensure adequate indoor ventilation and guarantee a 501 safe school life during the pandemic. Molecular detection of SARS-CoV-2 from indoor air samples in environmental monitoring needs 540 adequate temporal coverage and infectivity assessment Beyond Six Feet: A Guideline to Limit Indoor Airborne 543 Transmission of COVID-19 The transmission of tuberculosis 545 in confined spaces: an analytical review of alternative epidemiological models. The International 546 Is there an airborne component to the transmission of COVID-19?: A 548 quantitative analysis study Impact of indoor air pollution in nursery and primary schools on childhood asthma Quantitative assessment of the risk of airborne 553 transmission of SARS-CoV-2 infection: Prospective and retrospective applications Estimation of airborne viral emission: Quanta 556 emission rate of SARS-CoV-2 for infection risk assessment Effect of indoor air 560 quality of day care centers in children with different predisposition for asthma Portable air purification: 563 Review of impacts on indoor air quality and health Testing mobile air purifiers in a school classroom: 565 Reducing the airborne transmission risk for SARS-CoV-2 Indoor air quality in schools Indoor and outdoor 571 monitoring of volatile organic compounds in school buildings: indicators based on health risk 572 assessment to single out critical issues Temporal variation of VOC emission from solvent and wood water based wood stains Evolution of 578 spray and aerosol from respiratory releases: theoretical estimates for insight on viral transmission Indoor/outdoor air 581 quality assessment at school near the steel plant in Taranto (Italy) What aerosol physics tells us about airborne pathogen 584 transmission EPA's Guide to Air Cleaners in the Home Measurement of CO2 concentration for occupancy estimation in 588 educational buildings with energy efficiency purposes Using a mathematical model to evaluate the efficacy of TB 591 control measures The role of particle size in 593 aerosolised pathogen transmission: A review Transmission of COVID-19 595 virus by droplets and aerosols: A critical review on the unresolved dichotomy COVID-19 Aerosol Transmission Estimator Room ventilation and the risk of 600 airborne infection transmission in 3 health care settings within a large teaching hospital Model calculations of aerosol transmission and infection risk of COVID-603 19 in indoor environments A probabilistic transmission dynamic model to assess 606 indoor airborne infection risks Environmental perceptions and health before and after relocation to a green building FAQs on Protecting Yourself from Aerosol Transmission Transmission of SARS-CoV-2 by inhalation of 616 respiratory aerosol in the Skagit Valley Chorale superspreading event Interaction of aerosol particles 619 composed of protein and salts with water vapor: Hygroscopic growth and microstructural 620 rearrangement Guide for ventilation towards healthy classrooms How can airborne transmission of COVID-19 indoors be minimised? Environment International 630 142, 105832 Toward understanding the risk of secondary 632 airborne infection: emission of respirable pathogens Modelling the transmission of airborne infections 635 in enclosed spaces Exhaled CO2 as COVID-19 infection risk proxy for different indoor 638 environments and activities Covid-19 guidance document Simulation of SARS-CoV-2 Aerosol Emissions in the Infected 643 Population and Resulting Airborne Exposures in Different Indoor Scenarios Airborne spread of measles in a suburban elementary 646 school Risk of indoor airborne infection transmission estimated from carbon 649 dioxide concentration Airborne Transmission Route of COVID-19 Meters/6 Feet of Inter-Personal Distance Could Not Be Enough School air quality related to dry cough, rhinitis and nasal patency in 656 children Data driven indoor air quality 658 prediction in educational facilities based on IoT network Assessment of 661 CO2 and aerosol (PM2.5, PM10, UFP) concentrations during the reopening of schools in the 662 COVID-19 pandemic: The case of a metropolitan area in Central-Southern Spain Modelling aerosol transport 666 and virus exposure with numerical simulations in relation to SARS-CoV-2 transmission by 667 inhalation indoors Ventilation and laboratory 671 confirmed acute respiratory infection (ari) rates in college residence halls r n a l P r e -p r o o f -Indoor CO 2 monitoring reveals to be a practical proxy to Sars-CoV-2 transmission risk -A surveillance activity was conducted inside 11 classrooms during school reopening -All classrooms showed inadequate ventilation conditions (CO 2 higher than 700 ppm) -Better scenarios were depict when real time visualization of CO 2 levels was allowed -A 4 level