key: cord-0700126-qooqshfx authors: Jensen, Paul Arthur title: Critical Design Parameters in Design and Efficacy of Upper‐Room UVC(254) Luminaire Systems: Part I: Overview of Major Parameters and Relationships date: 2021-04-25 journal: Photochem Photobiol DOI: 10.1111/php.13425 sha: 6da1a68a6a4c7cde476fdb1cf95e9b9920ebd0a1 doc_id: 700126 cord_uid: qooqshfx During the current SARS‐CoV‐2 and tuberculosis global pandemics, public health and infection prevention and control professionals wrestle with cost‐effective means to control airborne transmission. One technology recommended by Centers for Disease Control and Prevention and the World Health Organization for lowering indoor concentration of these and other microorganisms and viruses is upper‐room ultraviolet 254 nm (UVC(254)) systems. Applying both a material balance as well as some nondimensional parameters developed by Rudnick and First, the impact of several critical parameters and their effect on the fraction of microorganisms surviving UVC(254) exposure was evaluated. Vertical airspeed showed a large impact at velocities <0.05 m s(−1) but a lesser effect at velocities >0.05 m s(−1). In addition, the efficacy of any upper‐room UVC system is influenced greatly by the mean room fluence rate as opposed to a simple volume‐ or area‐based dosing criteria. An alternative UVC(254) dosing strategy was developed based on the fluence rate as a function of the UVC(254) luminaire output (W) and the square root of the product of the room volume and the ceiling height. During the current SARS-CoV-2 and tuberculosis pandemics, public health and infection prevention and control professionals wrestle with means to control the airborne transmission. This requires the implementation of airborne precautions (1) (2) (3) (4) (5) : Administrative controls: The first and potentially most effective level of airborne control is the use of administrative measures (policies and practices) to reduce the risk for exposure to persons who might have COVID-19, TB disease, measles, or some other airborne-transmitted disease. One often overlooked area includes the operation and maintenance of environmental controls as well as proper use of personal protective equipment. Environmental controls: The second level of the hierarchy is the use of environmental controls to prevent the spread and reduce the concentration of small infectious droplets in ambient air. Personal Protective Equipment (PPE): Respirators to protect the wearer and masks to protect the environment are the primary PPE measures when dealing with airborne transmission. One technology that has been used globally for surface and air disinfection for over 100 years is Ultraviolet C Region (UVC). UVC, also known as germicidal ultraviolet (GUV) light and ultraviolet germicidal irradiation (UVGI), refers to shortwavelength ultraviolet "light" (radiant energy) that has been shown to inactivate bacteria, fungi and viruses (6) . UVC wavelengths of 200-280 nanometers (nm) have been shown to be effective for disinfection; however, there is a dose dependency based on wavelength as well as the composition of materials surrounding the microdroplet. Two primary applications of UVGI air disinfection include upper-room UVC luminaires and in-duct UVC luminaires. This paper will not address in-duct UVC applications. Upper-room UVC may complement ventilation to effectively reduce the concentration of infectious microdroplets in the air. The most common form of artificially generated UVC is by low-pressure mercury (Hg) discharge lamps at a predominant wavelength of 254 nm (UVC 254 , subscript "254" denotes the wavelength in nm). While this technology is commonly used for water disinfection, it had been used as far back as the 1940s for air disinfection. A quick search on the Internet showed the rapid advancement of UVC LED technologies. UVC chips range in UVC output of 0.003-0.05 W and cost <$30! While not quite powerful enough nor economical for current use, they will be soon (7, 8) . UVC LEDs are available in 260-270 nm and 270-280 nm ranges. In the last quarter of the 20 th century, UVC 254 became less and less popular in the United States due to the lower incidence of tuberculosis. With the SARS-CoV-1 pandemic in 2003 as well as increasing incidence of multidrug-resistant tuberculosis globally, there was a resurgence of UVC 254 usage in the United States. Now that we are fighting the SARS-CoV-2 pandemic, UVC 254 has made a strong comeback for both air and surface disinfection. Another wavelength that has been at the forefront of research in recent years is UVC 222 . Other papers in this special issue of the Journal of Photochemistry and Photobiology address UVC 222 as well as other UVC-producing technologies. This manuscript only pertains to upper-room UVC 254 applications. Currently, there are no national (US) or international consensus standards on design of luminaires nor design of luminaire application/layout. Consensus standards exist for occupational exposure to UVC but not to nonoccupational persons (9) . Underwriter's Laboratories published an ANSI/UL Standard 1598-Standard for Luminaires in 2018 (10) with the subsequent addition of Annex L-Additional Requirements For Germicidal Equipment, outside of the ANSI process (11) . ANSI/UL 1598 addresses electrical safety of luminaires and Annex L attempts to classify germicidal equipment (luminaires) as "safe." Over the years, there have been "rules of thumb" and empirical recommendations. I will briefly summarize in Table 1 . In 1999, First et al. (12) stated that the use of germicidal irradiation for the disinfection of air is an old technology that, strangely, is not yet mature. Since that time, it has matured a bit. Except for the paper by Mphalele et al., none of the recommendations helped designers with simple, generalizable dosing criteria that could be used as a starting point in the design cycle without the assistance of a CAD UVC lighting program (13, 14) . ASHRAE GPC 37 committee is working on publishing a document that details the commissioning cycle. Mphalele et al. (13) recommended starting with a volumetric dosing criterion of 0.017 W UVC254 m −3 based on a study performed at the Airborne Infection Research Facility in eMalahleni (previously known as Witbank), South Africa. Patients with infectious tuberculosis were housed in one of three patient rooms. All the air from these three patient rooms was sent to one of two animal rooms which housed guinea pigs as air samplers. Each patient room had an operational ceiling fan to assist in air mixing. Upper-room UVC 254 luminaires were operated on alternating days. The air from the patient rooms was sent to alternate animal rooms, coinciding with the alternate use of the UVC 254 luminaires. The study was repeated with about 30% less UVC 254 output and showed a strikingly similar effect (unpublished). Environmental factors such as temperature, humidity (absolute and relative) and solar radiation are not within the scope of this manuscript. The following parameters are deemed critical in providing effective disinfection of air: ). An inverse relationship between the effectiveness index (I) and fraction surviving (C UVC-ON /C UVC-OFF ) was derived. The data were fit to an exponential function. Below are the four major equations. The vertical Mixing Number (N m ) is a dimensionless number to indicate airflow rate passing through the UVC 254 -irradiated zone in the upper room is high relative to the mechanical air exchange rate (λ M ) and the ceiling height (H ROOM ). When N m is large, a significant portion of the room air will be irradiated while if N M is small, a small portion of the room air will be irradiated. AER UVC254 is the observed or expected air exchange rate (AER) based on the reduction in airborne microorganisms and viruses due to upper-room UVC 254 systems. This is often called "equivalent AER," meaning that if a mechanical ventilation system had been used in lieu of an upper-room UVC 254 system, one would observe equivalent or similar AER. Following is equation 7 from Rudnick (15): where S is the mean vertical speed (m s −1 ), H ROOM is the ceiling height (m) and λ m is the air exchange rate due to mechanical ventilation (s −1 ). The Irradiance Number (N I ) is related to UVC 254 irradiation or mean fluence rate (E). When N I is large, the more effective air disinfection should become. Note that the product of z and E is AER UVC254 . Following are equations (4) and (16) from Rudnick (15) : where z is the microbe susceptibility to UVC 254 (m 2 J −1 ), E is the mean fluence rate in the room (W m −2 ), d i is the mean UVC 254 ray length (m), W i is the UVC 254 output of the luminaire, V ROOM is the room volume and λ M is the air exchange rate (s −1 ). Dimensionless numbers N I and N M were combined into another dimensionless parameter, the Effectiveness Index (I), equation 17 from Rudnick (15) . I is an Index of UVC 254 effectiveness. When I is large, the larger the benefit from the upper-room UVC 254 system. Note that the denominator of I is the sum of the inverse of the N I and N M ; thus, one should understand the interrelations of all the parameters that went into this relative approximation of risk of disease transmission. where N I is the irradiance number (dimensionless) and N M is the mixing number (dimensionless). Rudnick developed an empirical relationship of their data to estimate the fraction of microbes surviving the UVC 254 treatment (C UVC-ON /C UVC-OFF ) in their equation 18 (15) . Miller and Xu also used a similar approach to present their results in terms of fraction of microbes surviving the UVC 254 treatment (16) (17) (18) . To initially identify sensitivity of selected parameters, one input variable was changed at a time and its impact on other variables was evaluated. The final step in this analysis paralleled much of the Rudnick modeling (15) . Because much of Wells (19) , Riley (20) , Miller (16) and Rudnick (15) is based on a material balance, a closer look at the basis of these equations is necessary. General dilution ventilation is the term-ofart for the fundamental material balance (21): Where V ROOM is the volume of the room (m 3 ), G is the rate of generation of microbes (microbes s −1 ), Q 0 is the effective volumetric airflow rate (m 3 s −1 ), C i is the concentration at time t i (microbes m −3 ) and t is time (s). At equilibrium or steady state, dC i = 0; the dilution ventilation material balance becomes: To solve this equation, one would integrate from t 1 to t 2 as follows: where G is the rate of generation of microbes (microbes s −1 ), Q 0 is the effective volumetric airflow rate (m 3 s −1 ), C i is the concentration at time t i (microbes m −3 ) and dt is delta time (s). Note that the effective volumetric airflow rate is made up of three components (16, 18, 22) : where Q 0 is the effective total volumetric airflow rate (m 3 s −1 ), Q M is the volumetric airflow rate (i.e. clean air) of mechanical ventilation system, assuming C entering room is 0 (m 3 s −1 ), Q UVC254 is the equivalent Q required to provide the same volumetric airflow rate as that observed by inactivation of airborne microbes due to UVC 254 (m 3 s −1 ) and Q N is the equivalent Q required to provide the same volumetric airflow rate as that observed by natural decay of airborne microbes by various means (m 3 s −1 ). If the room is at equilibrium (i.e. C i and G are constant), this material balance may be simplified and rearranged as follows: The air exchange rate (AER, λ) may be calculated as follows (21): If we substitute AER for Q, we get the following: To demonstrate this, we will use the following data from Mphalele (13, 14) : Entering these criteria into the Eq. 11, and assuming both G & C i = constant, the following relationships are established: Next, we will double the ceiling height (H ROOM ), keep the same luminaire power (W) and keep the same Q M . As a result, volume of the room (V ROOM2 = 2 V ROOM1 ) will be doubled, the AER M for Room 1 will be halved to 3 h −1 , the mean fluence rate in the room will be halved and the AER UVC254 will be halved. Entering these criteria, we get the following: Hence, the doubling of the room volume (V ROOM1 ) resulted in the SAME equilibrium concentration of microbes in the room. Mathematically, this makes sense; however, it does not make sense logically as we are dealing with a biological response to mean fluence rate (E), From Wells (23), Riley (20) , Miller (16) and Rudnick (15), we further understand that: where: AER UVC254 is the air exchange rate (AER) due to UVC 254 (s −1 ), z is the microbe susceptibility to UVC 254 (m 2 J −1 ) and E is the mean Fluence Rate in Room (W m −2 ). The main premise of the Rudnick equations is that the room is at equilibrium, the generation rate (G, microbes s −1 ) equals the removal and inactivation rates (15) . When the generation rate equals 0 microbes s −1 , the material balance may be rearranged as follows (15): There have been many evaluations of this material balance in the industrial environment for vapors, gases and particulates; however, there have been limited studies with bioaerosols. From the standpoint of AER N and AER M , there should be no difference in modeled results because bioaerosols are simply particles. From the standpoint of AER UVC (254 nm or other wavelengths), the data are far more limited, partly because of the cost of conducting such experiments and because we are dealing with a biological response to UVC. This biological response is related to the sensitivity of the microbe(s) to UVC and other environmental factors (temperature, relative humidity, solar radiation, etc.), the composition of the liquid coating surrounding the microbe (absorbing of UVC and/or shielding microbe from UVC), dose of UVC, etc. To evaluate the significance of vertical airspeed (S), estimated fraction surviving (C UVC-ON /C UVC-OFF ) is plotted against vertical airspeed (S) in Fig. 1 . In this case, the room dimensions, luminaire output (W) and mean fluence rate in room (E, W m −2 ) were held constant. Three lines were developed for AERs of 2, 6 and 12 h −1 . See Fig. 1 . This family of lines appears to approach that of an inverse power function. With an AER of 2 h −1 , increasing the vertical airspeed (S) beyond 0.05 m s −1 results in a very small decrease in estimated fraction surviving (C UVC-ON / C UVC-OFF ). As the AER increases, the vertical airspeed (S) beyond which a benefit is noted also increases. For example, with an AER of 6 h −1 , vertical airspeed (S) more than 0.10 m s −1 yields small benefit while with an AER of 12 h −1 , vertical airspeed (S) more than 0.015 m s −1 yields similarly small improvements. Another If one keeps the same luminaires (i.e. holding luminaire output as a constant and increases the room volume) the mean fluence rate would decrease as the room volume increases. The converse is true as well. If one wants to keep the same mean fluence rate in the room, one must proportionally increase the luminaire output (E) as the room volume (V ROOM ) increases. Note that the constant mean fluence rate (E) in the room shows an increase in surviving fraction (C UVC-ON /C UVC-OFF ) for all three air exchange rates (λ M ) as the ceiling height (H ROOM ) increases. However, when the mean fluence rate (E) was kept constant, the increase in surviving fraction was less dramatic. This might seem counterintuitive. The increase in surviving fraction may be due to the decrease in benefit provided by the upper-room UVC 254 luminaire systems or may be that the model developed by Rudnick is not generalizable (15) . Note the linear relationship between the luminaire output (W) and the mean fluence rate (E) when the room volume (V ROOM ) increases due to an increase in ceiling height (H ROOM ). At the three air exchange rates (λ M ,) of 2, 6 and 12 h −1 , the three lines are relatively flat. In Fig. 7 , the luminaire output (W) increased 0.71 to 1.0 W and the mean fluence rate (E) remained constant (0.050 W m −2 ). At the three air exchange rates (2, 6 and 12 h −1 ), the lines have a slightly shallower slope. Because the mean fluence rate (E) is a function of the ray length (d) and the ray length (d) is a function of the square root of the room area (A ROOM ), there is a nonlinear relationship between luminaire output (W) and mean fluence rate (E). Based on Miller (16) & Rudnick (15) laboratory studies and the evaluation above, the mean room fluence rate (E) may be a better predictor than a simple volumetric-based or area-based UVC 254 dosing criterion. As shown in Examples 1 and 2, there is a limit to the validity of applying a simple material balance to solve the UVC 254 dosing conundrum, and specifically, a volumetric-based UVC 254 dosing criterion. Because the mean fluence rate (E) in the room is proportional to the square root of the room area (A ROOM ) and inversely proportional to the volume of the room (V ROOM ), we must consider the following derivation of mean fluence rate as well as ray length. Rudnick estimated ray length as follows (15) where d is the mean UVC 254 ray length (m) and A ROOM is the area of the room (m 2 ). As Rudnick stated that this simplified method of calculation of ray length is based on a length-to-width ratio of 3 or less (15) . These equations only deal with the "plume" of UVC 254 in a horizontal plane. Based on measurements taken in the field, there is also a vertical component that is not accounted for by Rudnick (15) . Some luminaires have more vertical spread of UVC 254 than others due to increased spacing between baffles as well as the removal of some or all the baffles. As the ceiling height (H ROOM ) increases, the vertical dimensions of the plume increase. Beggs and Sleigh (24) performed some modeling of upper-room UVC 254 and concluded that if the size of the irradiated zone is doubled, the length of time the microdroplet is exposed to UVC 254 doubles, hence, the fluence rate could also be reduced by 50%. They hypothesize that the microdroplet will still receive the same dose. Hence, an alternative to the 2D plume should be investigated. Now, let us take a closer look at ray length (d). As shown in Fig. 2 , the mean fluence rate (E) is a function of ray length (d) (15) : Ray length (d) is a function of the square root of area (A ROOM ) and the inverse of room volume (V ROOM ). We can substitute the product of room area (A ROOM ) and ceiling height (H ROOM ) for room volume (V ROOM ), and we develop the following the relationship with mean fluence rate (E) being proportional to room area (A ROOM ) and ceiling height (H ROOM ) through the following series of substitutions: Assuming a mean fluence rate (E) of 0.05 W m −2 (5 μW cm −2 ), we can estimate the constant and solve Eq. 15 to some up with the following: where W is the required UVC 254 output of the luminaire (W), E is the desired mean fluence rate (W m −2 ), V ROOM is the volume of the room (m 3 ), H ROOM is the ceiling height (m) and β is the proposed dosing criterion (dimensionless). Applying this relationship to data from Mphalele (13, 14) , the following new dosing criterion was developed: A volume-based UVC 254 dosing criterion would provide mean fluence rate (E) equal to or greater than the result of equation 17 while the area-based UVC 254 criterion would provide mean fluence rate (E) equal to or less than the result of equation 17. Equation 17 assures mean fluence rate (E) in a room like that found in Mphalele (13, 14) . Equation 17 , with all the previous assumptions noted, may be used as the starting point for luminaire selection in the design cycle to implement an upper-room UVC 254 system. Assumptions of steady-state conditions and perfect mixing are not realistic assumptions for real-world applications. People may not be generating infectious aerosols at the same rate at all times nor do many facilities have perfect air mixing. Near perfect air mixing can be achieved using auxiliary room fans and/or ventilation supply diffusers. In addition, poor implementation room mixing fans and poor diffuser designs may adversely affect the containment or protective attributes of a room. In addition, room mixing fans may adversely impact infection prevention and control practices in traditional and nontraditional healthcare settings. These parameters will be discussed in a companion paper. Figures 1-4 demonstrate that there is a limit beyond which additional vertical airspeed (S) provides minimal additional benefit. "Fast" fan speeds may cause discomfort due to drafts. Both the volumetric dosing criterion (W/V ROOM ) and the area dosing criterion (W/A ROOM ) may be adequate starting points to enumerate the make, model and number of UVC 254 luminaires for a room. However, a more accurate method would be to select a desired mean fluence rate (E) and allow a CAD program to iteratively quantitate the number and location of UVC 254 luminaires. Additionally, the mean fluence rate is not the simple relationship of luminaire output (W) and room volume (V ROOM ) or room area (A ROOM ); rather, it is a function of the luminaire output (W) divided by the product of the square root of the room area (A ROOM ) and the ceiling height (H ROOM ) or the luminaire output (W) divided by the square root of the product of the room volume (V ROOM ) and ceiling height (H ROOM ). Again, the dosing criterion is not simply based on one-dimensional criterion of a room; rather, it is the fluence rate (E). In summary, average fluence rate (E) and the mean vertical airspeed (S) are critical design parameters when dosing a room with UVC 254 . Use of a UVC CAD program is necessary to finetune the design and final performance testing is necessary to ensure a safe environment for the room occupants and sufficient UVC 254 in the upper room to inactivate microorganisms and viruses at the desired rate. Further evaluation of the effectiveness index (E) is needed, particularly in other rooms with other geometries and sizes. A simple and affordable method to assess the vertical airspeed (S) must be identified and evaluated. The accuracy of volume-based and area-based UVC 254 dosing criteria needs to also be evaluated in other rooms with other geometries, dimensions, volumetric airflow rates (λ M ) and mixing conditions. Some engineers have raised the issue of alternative dosing criteria for "high" ceilings. None of the proposed dosing criteria consider other factors within the room that might positively or negatively affect the actual mean fluence rate. For example, what is the actual reflectance of various surfaces? How will various objects (TVs, room furnishings, illumination fixtures, etc.) influence the actual mean fluence rate? These questions are critical as the next step in the design cycle is to evaluate the preliminary make, model and quantity of luminaires using a UVC 254 CAD program. As with any CAD or non-CAD modeling, the "proof" is in the details and assumptions. Part 2 of this series will include more detail on ceiling height, ray length, air mixing and CAD programming. Centers for Disease Control and Prevention, National Center for Immunization and Respiratory Diseases (NCIRD) (2020) Infection Control Guidance for Healthcare Professionals about Coronavirus (COVID-19). Available at Guidelines for preventing the transmission of Mycobacterium tuberculosis in health-care settings Chiarello and the Healthcare Infection Control Practices Advisory Committee (HICPAC) (2007) Guideline for Isolation Precautions: Preventing Transmission of Infectious Agents in Healthcare Settings Available at: https:// www.who.int/publications/i/item/infection-prevention-and-control-ofepidemic-and-pandemic-prone-acute-respiratory-infections-in-healthcare Geneva: World Health Organization. License: CC BY-NC-SA 3.0 IGO The history of ultraviolet germicidal irradiation for air disinfection Understand the facts about UV-C LEDs and germicidal applications UV disinfection products American Conference of Governmental Industrial Hygienists (2021) TLVs ® and BEIs ® : Threshold Limit Values for Chemical Substances and Physical Agents and Biological Exposure Indices. ACGIH Worldwide ANSI/UL Standard 1598, UL Standard for Luminaires Annex (new) L, Additional Requirements For Germicidal Equipment (Part of UL Standard 1598 but not part of ANSI/UL Standard 1598). Issued 29 Guidelines for the application of upper-room ultraviolet germicidal irradiation for preventing transmission of airborne contagion-part I: Basic principles Nardell (2015) Institutional Tuberculosis Transmission. Controlled trial of upper room ultraviolet air disinfection: A basis for new dosing guidelines Online supplement: Institutional tuberculosis transmission: A controlled trial of upper room ultraviolet air disinfection -Technical specifications and dosing guideline application Fundamental factors affecting upper-room ultraviolet germicidal irradiation-Part II. Predicting effectiveness Efficacy of ultraviolet irradiation in controlling the spread of tuberculosis Efficacy of ultraviolet germicidal irradiation of upper-room air in inactivating airborne bacterial spores and mycobacteria in full-scale studies Impact of environmental factors on efficacy of upper-room air ultraviolet germicidal irradiation for inactivating airborne mycobacteria The use of germicidal lamps to control tuberculosis in healthcare facilities Airborne spread of measles in a suburban elementary school Chapter 4: General industrial ventilation. Industrial Ventilation -A Manual of Recommended Practice Factors influencing effectiveness of ultraviolet germicidal irradiation for inactivating airborne bacteria: Air mixing and ventilation efficiency Airborne Contagion and Air Hygiene A quantitative method for evaluating the germicidal effect of upper room UV fields Ultraviolet air disinfection for control of respiratory contagion Clearing the air: The theory and application of ultraviolet air disinfection Presentation: What UVGI Upper Room Performance is Possible? -What is Adequate? International UVGI Guidelines Conference. CRC, Construction Research Communications Ltd Environmental Control for Tuberculosis: Basic Upper-room Ultraviolet Germicidal Irradiation Guidelines for Healthcare Settings Acknowledgements-Author would like to thank Nancy Jensen for her critical review and commentary. Additional supporting information may be found online in the Supporting Information section at the end of the article:Appendix S1. Nomenclature.