key: cord-0697234-dy23a2bl authors: Bhattacharya, Arup; Ghahramani, Ali; Mousavi, Ehsan title: The effect of door opening on air-mixing in a positively pressurized room: implications for operating room air management during the COVID outbreak date: 2021-06-19 journal: nan DOI: 10.1016/j.jobe.2021.102900 sha: fddb9c116501f5d9ff5e0ee8be27e31b38bd849c doc_id: 697234 cord_uid: dy23a2bl The effect of the built environment on the predominant indoor airflow patterns is significant. To protect the healthcare workers at the front line from the outbreak of COVID − 19, it is necessary to understand the transmission dynamics of the virus, which has been shown to depend on indoor airflow patterns. In hospital operating rooms (ORs), design requirements pose a unique challenge as the positive pressure in the OR can facilitate virus spread into adjacent spaces, shall a COVID-positive patient require a surgical procedure. Moreover, the turbulent vortexes from door motions could independently increase the probability of virus escape from the OR to the adjacent corridors. Therefore, to obtain critical knowledge about the alteration of flow fields due to door movement in a positively pressurized room and quantify the air mixing across the door, a series of experiments were conducted in a controlled chamber. The results demonstrate significant impacts of the door opening on the airflow patterns. Increased alterations near the door and vortexes penetrating far into the chamber with multiple doors openings warrant further study of the indoor airflow dynamic under door motion. This experimental study proposes an algorithm to quantify the air exchange due to a standard door opening and quantifies this exfiltration of contaminated air up to 2 air changes per hour, that is 10% of the OR supply airflow rate. The algorithm to quantify the dissipated air quantity and the analyses of interaction between initial conditions and door openings contribute to the originality of this paper. The fast and somewhat uncontrollable spread of SARS-CoV-2 has put forward an unparralleled challenge to the healthcare workers who are at the frontline of this battle. The providers of healthcare services are at a disproportionately high risk of contracting the infection, as they are infected in 29% of the cases [Bai et al., 2020] . Initially close contact infection through respiratory droplets were thought to be the principal route of COVID-19 transmission. But, Morawska and Cao (2020) has shown the airborne transmission to be a main reason behind the spread by summarizing a wide array of studies [Morawska and Cao, 2020] . Substantive evidence of the virus being airborne has already been established [Mittal et al., 2020] . The on-field studies inside Wuhan Hospitals in China demonstrated the virus's capability to diffuse indoors and travel up to 10m airborne [Setti et al., 2020] , which projects additional challenges when patients infected with the novel Coronavirus (SARS-CoV-2) had to undergo a non-deferable surgical intervention [Peng et al., 2020] . The operating room is a very sophisticated, well-ventilated space, susceptible to contamination spread [Mousavi et al., 2019] . These spaces are positively pressurized with respect to adjacent spaces to ensure directional airflow driving the contamination away from the patient to prevent surgical site infection [Hathway et al., 2015 , Hu et al., 1996 , Setti et al., 2020 . However, the isolation condition is of utmost importance when a contagious source is inside the operating room, as the breakdown in isolation condition results in unwanted spread of the infectious agents [Mousavi and Grosskopf, 2016a] . Hence, it is important to understand the reasons for the unwanted spread in order to maintain the adequate protection and safety for patients and healthcare professionals. It has been shown in a number of studies that external interventions such as occupant movement and door opening can impact the flow field [Khalil, 2009 , Mousavi and Grosskopf, 2016b , Schaffner, 1982 , Josephson and Gombert, 1988 , Edlin et al., 1992 , Li et al., 2007 , Beggs et al., 2008 , Eames et al., 2009 , Bhattacharya et al., 2020 . Literature suggests the are particularly crucial since it disrupts the isolation condition and has the potential to even reverse the differential pressure [Mousavi and Grosskopf, 2016a , Bhattacharya et al., 2020 , Gustavsson, 2010 . Gustavsson (2010) explored the generation of vortices resulting from door opening [Gustavsson, 2010] . Existing studies have concluded that door openings are mass transfer mechanisms through volumetric exchange of air [Ahmed et al., 1993 , Hitchings, 1994 , Kiel and Wilson, 1989 , Smith et al., 2013 , Balocco et al., 2012 . Mousavi et al. (2016) suggested that 5% of the air from a negatively pressurized isolation room can be transported to the cleaner environment, resulting from opening and closing the isolation chamber door [Mousavi and Grosskopf, 2016a] . Having established that the door movement has extensive impacts on the existing airflow across two spaces separated with a differential pressure, it is crucial to understand how different human and structural factors impact the the air movements. The impacts are different depending on the type of door, opening speed and frequency [Mousavi et al., 2018] . For example, it is not clear whether a swing or sliding door results in lower contaminant transport. Lee et al. (2016) used computational fluid dynamics (CFD) simulation and conducted experiments to measure inter-zonal volume exchange due to door opening and concluded that under the isothermal condition, there was not much difference between a swinging and a sliding door [Lee et al., 2016] . On the contrary, Kalliomäki et al. (2016) showed that a sliding door could reduce the alterations on the airflow [Kalliomäki et al., 2016] . Mousavi and Grosskopf (2016) demonstrated that the speed of door operation is inversely proportional to exchange volume across the opening through numerical simulation study [Mousavi and Grosskopf, 2016a] . Frequent door openings have been associated with increased contamination transfer between spaces [Mousavi and Grosskopf, 2016b] . In an experimental study by Hathway et al. (2015) , it was found that the swept volume due to the swing motion of the door was almost equal to the exchange volume [Hathway et al., 2015] . Apart from air exchange, door motion is also responsible for altering the indoor flow field in a ventilated space. In an experimental study inside an operating room, Zhou et al. (2018) demonstrated a difference in flow patterns for the two door movements, as the air flow across the door during the closing period was different than that during opening the door [Zhou et al., 2018] . The generation of vortices at the door tip and propagation of those vortices through the flow field in the room was indicated by Eames et al. (2009) in their experiment involving measurements of dye concentrations in a mock-up room [Eames et al., 4 J o u r n a l P r e -p r o o f 2009]. Results showed a significant airflow structure moving along the wall, implying the existence of a separate, near-wall flow field. Mazumder et al. (2010) demonstrated higher contaminant concentrations near moving bodies in their simulation of an inpatient ward [Mazumdar et al., 2010] . This result was further substantiated as both Villafruela et al. (2016) and Bhattacharya et al. (2020) also demonstrated higher contaminant concentrations associated to traffic movement following a door opening [Bhattacharya et al., 2020 , Villafruela et al., 2016 . The thermal boundary condition of indoor space is affected by the opening of doors aiding in the generation of lateral airflow movement, specifically found for displacement ventilation . Papakonstantis and colleagues (2018) measured the change in flow vectors during door opening and closing using 3-dimensioanl velocity measurements in the proximity of the door [Papakonstantis et al., 2018] . They explained the advection of flow vortex along the wall during opening. In a two-dimensional numerical simulation study of door opening, Bhattacharya and Mousavi (2020) , showed that the opening and closing movement of the door has profound impacts on the velocity profiles and the direction of streamlines [Bhattacharya and Mousavi, 2020] . As demonstrated through that study the flow field recorded higher speed during the closing motion compared to the opening. This could be attributed to velocity residuals due to the opening phase. In summary, the focus of existing literature has been on understanding the impact of door opening in the volumetric exchange and air mixing. There has been a dearth of pertinent research on characterizing the air mixing with respect to pressure differential and different types of door opening exercise from actual field data. In this study, experiments were carried out in a controlled environment with capabilities to obtain positive pressure levels sufficient to emulate/exceed operating room conditions. The volumetric air exchange has been characterized and quantified under three different pressure differentials across a swinging in door for both a single and two-consequent door openings. Several previous studies have investigated the volumetric exchange between spaces separated by a door, ensuring differential pressures at the two compartments from numerical simulation approach Grosskopf, 2016a, Lee et al., 2016] and experimental approach [Gustavsson, 2010 , Kalliomäki et al., 2016 . The novelty of this paper lies in the way it analyzed and quantified potential contaminant migration outside the operating room from door opening, considering the room is positively pressurized. Although some existing studies have looked in to the changes in the velocity field due to door opening [Eames et al., 2009 , Zhou et al., 2018 J o u r n a l P r e -p r o o f et al., , Papakonstantis et al., 2018 , changes in the existing flow field due to perturbation induced through door opening and closing motions, and the resultant mixing of supposedly contaminated air containing virulent strains from the patient, with the supplied air inside the chamber, are holistically analyzed in this work. A novel approach to calculate mass flow rate across a door from the measured flow velocity and time of door operation has been proposed. This work is also unique in the way of analyzing the flow characteristics near the door swing periphery and the indoor mixing of contaminated exhaust air under ventilation, due to disruptions in the principal flow direction from door operation. To observe the patterns and characteristics of indoor airflow and to quantify the volumetric air exchange, emerging from two consequent door opening and closing motions, a series of tests were conducted. To capture the flow characteristics of an indoor space of size 5.48m x 5.44m x 2.5m, at least 16 pairs of omnidirectional sensors would suffice to cover the whole space. Instead, we had 4 pairs. With the limited availability of air velocity measuring instruments, the experiments were conducted in several stages. Therefore, a set of sensing instruments were deployed to obtain near-boundary data at the proximity of the door movement periphery (Figure 1b housing the measuring instrument for 8 rounds of tests. The sensing station P 1 was closest to the door tip when fully closed and when fully opened, the closest station was P 3, with P 2 exactly in the middle. At locations P 1 and P 2, three sensors were mounted at equal distances to each other covering a third of the door height, with the bottom one being 0.66 m above the floor level. Only the bottom two sensors were mounted at location P 3, owing to the limited number of available sensors. Another set of 8 unidirectional sensors were arranged in 4 imaginary rows, designated as R1 through R4, going inside the chamber in a radial direction (Figure 1c ), at two elevation levels. The row R1 was parallel to the closed door, and the sensors were at a distance of 0.1m from the wall, whereas the row R4 was perpendicular to the closed door, with rows R2 and R3 making 30 degree and 60 degree angle with R1, respectively. The measuring instruments were mounted on tripods along each row in four locations, identified using sensor ids 1 through 4. The first sensing system was the closest to the door tip at a distance of 0.1m, and the subsequent instruments were located in 1.0m increments. Moreover, the measuring instruments at the lower elevation were 0.66 m above the floor level, which was a third of 7 J o u r n a l P r e -p r o o f the total door height. The higher-level sensors were placed at another 0.66 m from those at the lower elevation, covering two-thirds of the door height from the ground. The denotation of sensors was such that they were identified based on their elevation and location on a row. For example, the second sensor at the lower level (L) of row 3 is identified as RL32, or the third senor at the upper elevation (U) of the first row will be identified as RU 13. As mentioned previously, the test setups and the perceived analysis from the collected data were focused on understanding the three-dimensional flow fields generated from the swing door movement. The tiered arrangement of sensors provided the possible understanding at two (for radial arrangements) and three (for peripheral arrangement) levels. With the distance between the measuring stations, we were able to follow the evolution of the flow originated from the door opening at least until the middle of the room, given the limited number of sensors and restricted access to the test chamber. Different sets of experiments were defined for two different door movements and three initial conditions, provided by the amount of air inlet from the diffuser. For each experiment setup, the experiments were conducted in sets, due to limited access to multiple sensors simultaneously, as expressed in the Experiment Setup section. The two movements of the swing door that opened into the chamber, are defined as follows: 1. Opening and closing the door once in a way that the door opens in the first second of every trial that takes two seconds to complete and stays open for a second before the closing movement completes by another two seconds, a total opening cycle of 5 seconds. This represents a typical door opening by a healthcare professional. 2. Opening and closing the door twice with the first cycle finished by second 5, then the door is kept shut for two seconds before replicating the first cycle, i.e. opening through two seconds, keeping ajar for one second and closing for two seconds. This scenario could represent a case of quick supply run to the operating room with two immediate door operations. During both of these settings, each trial of experiments was run for a duration of 60 seconds while each test was repeated 60 times to ensure statistical consistency. For every set of experiment, the door opening 8 J o u r n a l P r e -p r o o f was initiated at the first second, and it was closed at the end of ∼ 5s (for opening once) or ∼ 12s (for opening twice). The sensors started recording air velocity from the start of door opening at second 1 and continued for a minute. The door was again opened at the first second of the next minute, and these repetitions continued for 60 minutes. With the absence of any automatic door controlling device, the opening and closing, as well as the timekeeping was done manually. Owing to this reason, the time required for the first cycle to complete was not exactly 5 seconds and for double operation, not 12 seconds. The associated deviations for all 60 repetitions of each test based on door operation and initial conditions, are tabulated in Table 1 . Three different flow regimes were identified, according to the volumetric air flow through the diffuser, which are described below. • Still air -With the absence of airflow, as the fan and the air handling unit (AHU) responsible for air supply to the chamber were not operating, the initial steady state condition inside the experiment chamber under this scenario was quiescent, and the supply diffuser was shut off. • 70% fan -The supply fan and the AHU were throttled to operate at 70% of the full capacity. With the exfiltration through the gaps around the door frame, the manometer reading indicated a positive pressure differential of 10 Pa between the room and outside at steady state condition was reached inside the chamber. • 100% fan -During this flow regime, the supply fan and AHU operated in full capacity. With 190 cfm (90 L/s) [Bauman et al., 1995] air inlet, the steady state reading of the positive differential pressure between the chamber and outside was measured to be 20 Pa. J o u r n a l P r e -p r o o f Two different types of sensors were used for the experiments. The omnidirectional sensors recorded only the velocity magnitude, whereas the ultrasound sensors logged the components of velocity in three Cartesian coordinates, where the x-axis was along the tangent of the arc made during door opening, y-axis was along the radial of that arc, and z-axis was along the normal to the floor plane. The omnidirectional sensing system is a hot-wire anemometer type velocity measurement transducer known as AirDistSys 5000, As explained earlier, the sensing instruments recorded time-averaged values of velocity magnitudes for 60 seconds in each experiment, which was repeated 60 times. Those data points were averaged to obtain temporal trends and transient velocity profiles. The collected data demonstrated consistency at each point in time. The consistency was assessed by relative standard error (RSE), defined as percentage of data standard error over the mean velocity. Depicted in Figure 2 , the solid lines portray the mean velocity for each set of experiment and the surrounding shaded region displays the standard error bounds. It is noteworthy that the maximum distance between the bounds are associated to the time of door movement cycle, probably due to the stochastic patterns in the turbulent flow. J o u r n a l P r e -p r o o f Placement of sensors brought about the opportunity to calculate air-mixture at the door due to door opening for various pressurization scenarios. The ultrasound sensors placed immediately around the opening radius of the door were used to measure the three dimensional velocity of air around the door. The results of velocity measurements by the ultrasound sensors were reported in the global Cartesian coordinates shown in Figure 3 . A conversion of these values to a cylindrical coordinate was convenient in order to measure the mass flow of air through the radius of opening. Formally, the rate of mass transfer on the door swing surface (let's denote this surface by S throughout the paper) isṁ = dm dt . Assuming a constant density of air in ambient temperature, we have: It must be noted that the tangential (ds) and vertical (dz) differential elements do not change with time where the change of the radial term (dr) with time is velocity v r . Therefore, Equation 1 will take the following form.ṁ = S ρv r ds dz Knowing that ds = Rdθ where R is the radius of the door, one can write v r based on its v x and v y components, which is what was measured by the ultrasound sensors( Figure 4 ). Thus Equation 2 will turn to:ṁ Ideally, the radial component of velocity (v r ) varies as function of θ and z, and the integral in Equation 3 can be numerically calculated to find the rate of mass transfer through S. In our test setting however, we only had measurements of air velocity in eight fixed points. Thus to solve Equation 3 we assumed that velocities measured by each sensor embodied the region around it, as demonstrated by Figure 3 . The ultrasound sensors collected 6 data points per second, that is 12 data points from a fully-closed to The temporal patterns of air movement at the sensing stations near the door swing periphery were analyzed using the Cartesian velocity components, obtained from the ultrasound sensors. These sensors reported 6 data points of velocity components per second at every location. During Test 1, when the existing initial condition was quiescent air, and there was no other movement than the door movement, changes in three-dimensional air velocities were recorded. The transient pattern is depicted in Figure 5 . At the onset of door opening motion, the sensing station at P 1 recorded an increase in air speed with a 1-s lag. The highest magnitude was recorded at 2.1 s, as the air with high magnitude of velocity followed the moving door. Sensing station at P 2 began logging an increase in air speed from second 3.5, reaching max during opening at second 4.5 and again peaked during closing at second 5.3. It is noteworthy that the magnitude was higher during closing compared to opening motion. During the opening motion, the initial condition is still air. But while closing, the air in the chamber had a presupposed motion resulting from door opening. Closing the door created a motion, reversing the direction of the previous one, probably affecting the change in velocity. At location P 3, there is an initial surge, possibly due to the impetus exerted by the door opening that carried the previously stagnant air quickly to the wall. During closing, the moving door is extracting the air inside the chamber, and the wakes following the closing door were recorded at location P3, which showed a peak quickly after closing motion was complete. Figure 5 demonstrates these changes in velocity magnitude plotted against time. Even though the magnitude of air had significant patterns that corresponds to the door opening and closing duration, the velocity components obtained from the ultrasound sensors led to a deep analysis of door movement. At the beginning of door opening, the moving door was pushing the still air inside the chamber, which was recorded as a surge in velocity in the positive x-direction (as shown in Figure 3 ) and for a small duration, a negative y-component (normal to the door opening direction at t = 0 s) The experiments that consisted of two consecutive opening and closing cycle, the first cycle of door opening, and closing was analogous to those of the experiments involving single door opening and closing. For the test with no ventilation (Test 2), the sensor at location P1 recorded the increase in velocity instantaneously, peaking at close to 3 seconds for the first time opening. Instruments at location P 2 also recorded the surge for opening and then a higher magnitude during closing at around 3.5 s and 5.3 s, respectively, for the first round of door operation. But, during the second cycle of door openingclosing, the speed recorded was higher compared to the first cycle, owing to reasons attributable to the interaction of the repeated motion with the the residual movement from the first cycle. Figure 7 shows 17 J o u r n a l P r e -p r o o f the immediate rise in air velocity, recorded by the measuring device in location P 1, followed by P 2 and P 3. The closing motion that followed the door opening, and then another set of consecutive opening and closing for the second cycle stirred the stagnant air, that resulted in higher velocities. The surge in velocity magnitude for the second time door operation was apparent visible for both Tests 4 and 6, as depicted in figure 7 for Test 4. Interestingly, significant changes in velocity magnitude was recorded up to 10 seconds for Test 2, and 15 seconds for Test 4 and 6 after the door movement was stopped. As detailed earlier, The opening of door had significant effects on air mixing across the door. In the absence of pressure differentials across the door, air mixing took place both ways. Initially, air entered the room following the inward door swing (< 1.0s). Immediately after, the room air made up for the temporary vacuum created by the large boundary movement by leaving the room and creating vertices at the tip of the door (∼ 1.5s). Then air from the outside began to entrain into the room until the closing cycle started (∼ 3.5s). Then the closing door pushed air out of the room (∼ 3.5 − 5.0s) (Figure 8 ). Air velocities inside the room approached background values nearly 10s after the door was completely shut. This intermittent pattern of mass flow rate was observed in all three cases, namely when the door was opened once, and both laps of opening twice. Slight differences in air velocities right before door opening started (i.e., slightly different initial conditions) resulted in respective variations in the data, yet the overall pattern indicated that the effect of door opening could prevail these small differences in the flow. Furthermore, the absence of pressure differential facilitated the mixing of air both ways, though the total air exchange was nearly zero. These patterns changed dramatically by introducing positive pressure as the inward patterns followed by the door opening (2 − 3.5s) where suppressed by the positive pressure. In the presence of positive pressure, the 'balancedmixing' across the door was changed to a 'directional pathway' from inside the room outward (i.e., negative mass flow rate values). Increasing pressure differential resulted in more pronounced directional pathways. Areas under the curves shown in Figure 8 indicate the total transport of mass (kg) across the door (Table 2 ). To put this in context, for ∆P = 20Pa nearly 8.5kg of air leaves room per door opening, which is equivalent to 7.5m 3 of air when divided by the density of air (ρ = 1.125kg/m 3 ). Literature shows that, on average, the operating room door is operated once every three minutes [Mousavi et al., 2018] . Therefore, during one hour of an average surgery 20 × 7.5 = 150m 3 of air can leave the operating room. The data obtained from the peripheral ultrasound sensors indicated the behavior of the flow fields near the movement zone. The radial arrangement of the omnidirectional sensors provided the data to analyze spatial distribution of the wakes inside the chamber. The dissipation of velocity fields showed the impact of the door movement could last long after the door movement ceased. Figure 9 compare the velocity fields in the test chamber for standalone and consecutive door opening exercises, with the supply fan on working mode. For Test 3, at the initial periods of door opening, the isometric lines with higher velocity fields are concentrated in the movement zone and spread through the space with time. Two seconds after the door closure for Test 3, areas with significant velocity magnitude (> 0.1 m/s) were found up to 2 m from the tip of the door into the chamber. By 10 seconds after door closure, this field with velocities > 1 m/s penetrated 4.5 m inside the chamber. During Test 5, when the supply fan was operating at the full capacity, the interaction between the external movement generated wakes and the high-velocity supply air resulted in a rise in the air speed, more than all the previous tests. Nearly everywhere in the chamber recorded velocity magnitudes greater than 1 m/s after 14 seconds of door closure, at which time, the maximum air speed recorded was 0.5 m/s. At second 23, 4 m inside the chamber, a maximum air speed 0.25 m/s were present. Starting from second 29, the fields started to shrink and by second 39, the maximum speed reduced to 0.14 m/s. When the test setting involved movement of the door twice, for Tests 4 and 6, , the magnitude of the velocity fields was found to be slightly increased compared to Tests 3 and 5, respectively. Data obtained during Test 4 showed that the wakes with velocity up to 0.12 m/s was present nearly 4 m inside the chamber. Even after 23 seconds since the first door opening began, > 1 m/s magnitude of velocity was measured at a distance of 4.75 m from the door. During Test 6, by second 19, the maximum velocity magnitude inside the chamber was 0.6 m/s, owing to potential turbulence during consecutive door movements. From second 29, the supplied airflow started to push the wakes towards exit, but velocity magnitudes were present deep inside the chamber even at 22 J o u r n a l P r e -p r o o f It should be noted that the heatmaps presented in Figure 9 were created considering zero slip condition at the walls. The known location and magnitudes of velocity, obtained from the radially arranged omnidirectional sensors, were interpolated to find the velocity values in the chamber that was discretized in a grid of size 110 x 109, where a square grid dimension was 5cm. This paper aims to study the impacts of door opening in a positively pressurized chamber, which was hypothesized as an operating room where a COVID patient is to be receiving surgical intervention. Air mixing across a swing door and the resultant alterations in velocity field inside the chamber have been studied. It must be noted that the chamber used in this study was significantly smaller than a typical OR and the positive pressure magnitudes were higher than those recommended by Standards. Several previous studies have investigated the volumetric exchange between spaces separated by a door, ensuring differential pressures at the two compartments from numerical simulation approach Grosskopf, 2016a, Lee et al., 2016] and experimental approach [Gustavsson, 2010 , Kalliomäki et al., 2016 . Experiments were repeated 60 times to ensure consistency and repeatability of the outcomes. Due to the large number of tests and restricted availability of the test facility, only two-scenarios of the door opening and closing cycles could be defined. At the time of these experiments, the ultrasound sensors were not fully commercialized and hence very few (17 out of 900 data points) unreasonable data logs (velocities greater than 2.5 m/s) were recorded, which were discarded during data analysis. As discussed before, the possibility of a virus growth can be related to the humidity level in an indoor environment. In these sets of experiments, we the relative humidity levels inside the test chamber was not measured, as the purpose of the study was to quantify the flow properties and understand their patterns. Future studies on the alterations of the relative humidity ratio could provide meaningful understanding of how SARS-CoV-2's viability alters with the flow properties. J o u r n a l P r e -p r o o f This experimental study was conducted in a sealed chamber with the capabilities of fresh air inlet at rates that generated sufficient positive pressure required for spaces like operating room. This study indicated that the transient change in the velocity field from door opening and closing were location specific -the points closest to the door tip responded to the changes quicker than those located farther, e.g. point 1 of the radial arrangements recorded changes quicker than point 4. Different points (P 1, P 2, and P 3) in the vicinity of door swinging radius were also found to respond according to the door's position while opening or closing. Emulating the opening and closing movement twice resulted in further increase of the flow velocity. During opening the door for the first time, disturbances are introduced to the quiescent air inside the chamber. While closing, more disturbances are introduced to an existing velocity field, that resulted in increased the velocity components. For Tests 3 and 5, i.e. one-cycle of door opening under ventilated condition, lower magnitudes of velocity were observed when compared to Test 1. The existing airflow suppressed the effect of door opening on the indoor flow fields. The second cycle of door movement interacted with the flow field under an existing motion exerted by the first cycle of door operation. Hence higher magnitude velocity components were recorded during Tests 2, 4, and 6, compared to Tests 1,3, and 5. The spatial distribution had provided insights about unwanted air mixing due to secondary velocity fields originating from door movement. The increase in air velocity inside the chamber was due to the wakes carried by the moving door in the background air. These wakes dissipate through the chamber and as they penetrate further into the chamber, the velocity field continued to decrease, due to the lost momentum during transfer between air molecules. But with supply fan working, the interaction between the primary flow field due to inlet air and the secondary flow fields were higher and reached very far inside the chamber. Results from door opening twice indicated that with increased number of door operation, the secondary fields were stronger, and the increased interaction resulted in deeper penetration of wakes inside the chamber. These results suggested that even with high quantity of supplied airflow, the door operation can disrupt the predominant flow pattern and the perturbation is capable to sustain long after the door was closed carrying high velocity air deep into the chamber. In a positively pressurized operating room with a contagious patient, this kind of air mixing is undesirable as the directional airflow from positive pressure differential is aimed to carry the contaminated air out of the facility. A large proportion of this work was aimed at quantifying the air escape from the positively pressurized operating room due to door opening in order to gain insights about risks of air potentially contaminated with SARS-COVID-2 putting healthcare providers at risk. This study found that with inlet air flow rate of 190 cfm (90 L/s), 7.5 m 3 of air can leave for every time the swing door is operated. This translates to almost 2 ACH of air escaping during a typical surgical procedure, carrying contagions to the adjacent spaces. The future research would focus on utilizing the results of this study these results to imitate real-time operating procedure involving sporadic door opening, for further validation. Optimization of positive pressurization and exhaust locations for such sensitive procedures involving pathogens such as SARS-COV-2 is also one of the main future research directions. We are thankful for the funds from US National Science Foundation under the Grant Number 2012827. The help and assistance from the faculty and staff at the Center for Built Environment in University of California, Berkeley are truly appreciated. 3713 dynamics of laboratory pressurization Traffic flow in the operating room: an explorative and descriptive study on air quality during orthopedic trauma implant surgery Measuring 3d indoor air velocity via an inexpensive low-power ultrasonic anemometer Standard 170-2013: Ventilation of healthcare facilities. Ventilation of Health Care Facilities Presumed asymptomatic carrier transmission of covid-19 Assessing the effects of sliding doors on an operating theatre climate Testing and optimizing the performance of a floor-based task conditioning system The ventilation of multiple-bed hospital wards: review and analysis The effect of boundary conditions on transient airflow patterns: A numerical investigation of door operation Particle dispersion in a cleanroom-effects of pressurization, door opening and traffic flow Three-dimensional analysis of the effect of human movement on indoor airflow patterns Air flow characteristics of a room with air vortex diffuser The appropriate airflow rate for a nozzle in commercial aircraft cabins based on thermal comfort experiments Movement of airborne contaminants in a hospital isolation room An outbreak of multidrug-resistant tuberculosis among hospitalized patients with the acquired immunodeficiency syndrome An inexpensive low-power ultrasonic 3-dimensional air velocity sensor Measuring air speed with a low-power mems ultrasonic anemometer via adaptive phase tracking Dispersion of small particles into operating rooms due to door openings Experimental and modelling investigations of air exchange and infection transfer due to hinged-door motion in office and hospital settings Laboratory space pressurization control systems Measurements of air flow characteristics in a full-scale clean room Numerical and experimental analysis of the air stream generated by square ceiling diffusers Airborne transmission of nosocomial varicella from localized zoster Airflow patterns through single hinged and sliding doors in hospital isolation rooms-effect of ventilation, flow differential and passage Thermal management in healthcare facilities: Computational approach Combining door swing pumping with density driven flow Numerical evaluation of influence of door opening on interzonal air exchange Study on dynamic thermal performance and optimization of hybrid systems with capillary mat cooling and displacement ventilation Role of ventilation in airborne transmission of infectious agents in the built environment-a multidisciplinary systematic review Effect of door opening on the performance of displacement ventilation in a typical office building Measurement of foot traffic in the operating room: implications for infection control Impact of moving objects oncontaminant concentration distributions in an inpatient ward with displacement ventilation The flow physics of covid-19 Airborne transmission of sars-cov-2: The world should face the reality Academic research to support facility guidelines institute ansi/ashrae/ashe standard 170-2013 Airflow patterns due to door motion and pressurization in hospital isolation rooms Secondary exposure risks to patients in an airborne isolation room: Implications for anteroom design An observational study of door motion in operating rooms An experimental study of the flow induced by the motion of a hinged door separating two rooms Operating room traffic: is there any role of monitoring it Transmission routes of 2019-ncov and controls in dental practice An outbreak of airborne nosocomial varicella Airborne transmission route of covid-19: why 2 meters/6 feet of inter-personal distance could not be enough