key: cord-0686333-5ph3pf33 authors: Borro, L.; Mazzei, L.; Raponi, M.; Piscitelli, P.; Miani, A.; Secinaro, A. title: The Role of Air Conditioning in the Diffusion of Sars-CoV-2 in Indoor Environments: a First Computational Fluid Dynamic Model, based on Investigations performed at the Vatican State Childrens Hospital. date: 2020-08-31 journal: nan DOI: 10.1101/2020.08.25.20181420 sha: 18e8aa346bf9fda18e26a69bbb5ad15a2dff4a1a doc_id: 686333 cord_uid: 5ph3pf33 Background: About 15 million people worldwide were affected by the Sars-Cov-2 infection, which already caused 600,000 deaths. This virus is mainly transmitted through exhalations from the airways of infected persons, so that Heating, Ventilation and Air Conditioning (HVAC) systems might play a role in spreading the infection in indoor environments. Methods: We modelled the role of HVAC systems in the diffusion of the contagion through a Computational Fluid Dynamics (CFD) simulations of cough at the Vatican State childrens hospital Bambino Gesu. Both waiting rooms and hospital rooms were modeled as indoor scenarios. A specific Infection-Index parameter was used to estimate the amount of contaminated air inhaled by each person present in the simulated indoor scenarios. The potential role of exhaust air ventilation systems placed above the coughing patients mouth was also assessed. Results: Our CFD-based simulations show that HVAC air-flow remarkably enhance infected droplets diffusion in the whole indoor environment within 25 seconds from the cough event, despite the observed dilution of saliva particles containing the virus. In the waiting room simulation, Infection-Index parameter increases the faster the higher the HVAC airflow. Greater flows of air conditioning correspond to greater diffusion of the infected droplets. The proper use of Local Exhaust Ventilation systems (LEV) simulated in the hospital room was associated to a complete reduction of infected droplets spreading from the patient s mouth in the first 0.5 seconds following the cough event. In the hospital room, the use of LEV system completely reduced the index computed for the patient hospitalized at the bed next to the spreader, with a decreased possibility of contagion. Conclusions: CFD-based simulations for indoor environment can be useful to optimize air conditioning flow and to predict the contagion risk both in hospitals/ambulatories and in other public/private settings. Both waiting and hospital rooms were modeled as indoor scenarios. A specific Infection-Index (η) parameter was used to estimate the amount of contaminated air inhaled by each person present in the simulated indoor scenarios. The potential role of exhaust air ventilation systems placed above the coughing patient's mouth was also assessed. Results: Our CFD-based simulations of the waiting room show that HVAC air-flow remarkably enhances infected droplets diffusion in the whole indoor environment within 25 seconds from the cough event, despite the observed dilution of saliva particles containing the virus. At the same time also their number is reduced due to removal through the HVAC system or deposition on the surfaces. The proper use of Local Exhaust Ventilation systems (LEV) simulated in the hospital room was associated to a complete reduction of infected droplets spreading from the patient's mouth in the first 0.5 seconds following the cough event. In the hospital room, the use of LEV system completely reduced the η index computed for the patient hospitalized at the bed next to the spreader, with a decreased possibility of contagion. the continents most affected by the pandemic. The Sars-Cov-2 can spread through the air over large distances [1] and viral particles have also been found on particulate matter [2] . The airways are, therefore, the primary way of transmission through the droplets and aerosol dispersion in the environment [3] . A less critical way of transmission is direct contact with hands and contaminated objects [4] . To make clear the scientific treatment of the contagion transmission in epidemic contexts, some relevant articles about the nomenclature have been published over the years concerning the definition of droplets and droplets nuclei. All these particles can be expelled from the mouth or the nose through sneezing, coughing and talking. Droplet transmission is a way of contagion consisting in expelled particles from the mouth that quickly settle to the ground under the gravity force. The droplets nuclei transmission is the transmission that occurs by expelled particles smaller in size compared to the droplets. The World Health Organization has established that particles with diameters less than 5 μm are called droplets nuclei, while particles with diameters greater than 5 μm are called droplets [5] . The large particles typically settle within 1 meter of the source but this value depends on several external dynamic factors that make it susceptible to changes. The smaller particles instead remain suspended in the air for varying periods and evaporate much more quickly. Nicas and Jones 2010 [6] have proposed a useful classification dividing the particles into "Respirable Particles" and "Inspirable Particles". The respirable particles have a diameter of 10 μm or less and deposit throughout the respiratory tract, including the alveolar region, whereas inspirable particles with a diameter between 10 μm and 100 μm deposit in the upper airways and tracheobronchial regions only [7] . All previous experimental studies on this topic give us much complete information about the physical-mechanical characterization of cough and free breathing. The dispersion of droplets and aerosols indoors is the main responsible for respiratory viral infections and its control is crucial for public health, especially in public settings such as hospitals, offices and recreational places. The purpose of this work is to analyze the influence of Heating, Ventilation and Air Conditioning (HVAC) systems on the air-dispersion of aerosols generated by a cough within a closed environment. The simulation consists in two differents cases: Case 1 and Case 2. Case 1 consists of a waiting room with a surface of 65 m 2 , in which the air is assumed to be at a temperature of 26 °C and a relative humidity of 50%. The ground, ceiling are lateral walls are treated as adiabatic. For Case 1 (Figure 1 ), we produced three different scenarios, considering no HVAC (Scenario A) and an active HVAC system with two different levels of volume flow rate: nominal flow rate (Scenario B) and double flow rate (Scenario C). The simulation involving a two-fold increase in volume flow rate is aimed at verifying its effect on the spreading of contaminated air and droplets within the room. The general assumption is that this effect reduces their concentration of droplets by ensuring a greater air recirculation in less time than the HVAC system at a nominal flow rate [11] . The objective of this analysis is to investigate the role played by the HVAC system and its intensity on the spreading. In all the scenarios of Case 1 the simulations include six adult men and six young childrens sit on benches modelled with manikins obtained by 3D online library [12] [13], with a body temperature of 31 °C [14] . The six pairs of men and children were tagged with a letter from A to F, where the child E represents the spreader subject that triggers the cough event. All people sit opposite each other and the distance from one person to another is about 1.70 m. The spreader is represented by kid E. The Case 2 ( Figure 2) consists of a children's hospital room with two hospitalized patients at body temperature of 31 °C [14] . The room is assumed to be at a temperature of 26 °C and a relative humidity of 50%. The ground, ceiling and lateral walls are adiabatic. The distance between the two patients is 1.90 m. All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint Figure 2 : Case 2, an hospital recovery room with two beds and two pediatric patients. The LEV system acts directly above the spreader subject (Kid B). For Case 2, two different scenarios were considered. Scenario A represents the baseline situation, in which the subject B is the spreader, whereas contaminated air and droplets are diffused and convected due to buoyancy, gravity and the HVAC system. In the additional Scenario B, a Local Exhaust Ventilation (LEV) system was placed above the spreader's face. It consists of a tube connected to an air treatment unit equipped with different types of highgrade air filters. The LEV system is commonly employed in the industry to ensure and improve the air quality of workspaces. The objective of this analysis is to analyze the change in spreading due to the presence of the local exhaust system. In our scenario a simplified LEV system was modeled considering a circular section tube with a diameter of 20 cm and an inlet area of 300 cm 2 . The Local Exhaust system has an inlet air flow of 1080 m 3 /h [15] and is positioned on the bed at about 43 cm above the spreader patient's mouth ( Figure 2 ). Additionally, an HVAC system is present in the room, with an inlet air flow of 480 m 3 /h and an outflow through the return grille of 420 m 3 /h [16] . Considering the CFD setup, the simulations were carried out with the commercial CFD solver ANSYS Fluent release 2019 R3. The medium was modeled as an incompressible ideal gas with constant properties calculated at ambient conditions. The gravity was included to account for the effects of buoyancy due to the temperature difference among ambient, manikins superficial temperature and sneezed air. All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . As far as the coughing process goes, it is worth underlining how appropriate modeling of the droplet transport plays a key role in determining the consequences of the coughing event. For this purpose, a literature review was carried out to determine the most reliable setup for the scope of work, in terms of both modeling approach and boundary conditions. Coupled Eulerian-Lagrangian simulations represent for at least 15 years the state-of-the-art for the computational study of the aerial dispersion of contaminants [17] [18] [19] [20] [21] [22] [23] . An unsteady particle tracking was used, to include the effect of secondary break-up through a TAB model. The evaporation was also accounted for, considering a volatile component fraction of 94% [24] . The effects of the turbulent flow on the droplets are with Discrete Random Walk approach. A poly-dispersed droplet population was considered to make the most of the capabilities of the Lagrangian approach. Among the many possible size distribution reported in the literature for a coughing event, it was decided to exploit the setup described by Bi et al., 2018 [22] , who used the size distribution from Duguid, 1946 (see Table 1 ). Such a population was modeled by fitting the data with a Rosin-Rammler distribution. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint The population is injected in the time range of 0.042-0.136 s, which represents only a fraction of the temporal velocity profile applied to the eulerian phase at the mouth of the spreader subject via a velocity-inlet condition ( Figure 3 ). The droplets have velocity and temperature of the consistent with the contaminated air injected (35 °C). The boundary conditions for the discrete phase were set to let the droplet escape when inhaled from the noses or extracted for the HVAC grilles, whereas they are trapped (i.e. eliminated from the domain) when touching a manikin or a surface. For what concerns the Eulerian phase, most of the studies in the literature deals with RANS turbulence models to account for the turbulence effects on the flow and droplets, in both a steady (RANS) or unsteady (URANS) fashion. The exploitation of a direct solution of the turbulent flow, or at least of the largest scales, (as done in LES) showed some promising improvements (see for example [22] ), but it is still not widespread due to computational effort involved. Also in this work, the URANS approach was chosen due to the complexity of the cases investigated. The turbulence effects were modeled with a k-ε RNG model (as already done in previous works [19] , [25] [26] [27] ) and scalable wall functions. The inhalation/exhalation of the "target" manikin was modeled with pressure-outlet boundary conditions with a target mass flow rate. The literature contains much information, even though scattered, about the transient respiration process, usually described as a sinusoidal function [19] [20] [21] . All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint However, the approach proposed by Gao et al. [25] was followed, who modeled it as steady inhalation with a flow rate of 0.14 l/s. The overall opening area of the nose is 0.56 cm 2 . For the sake of simplicity, such flow rate was kept equal for both men and kids. To track the dispersion of the contaminated fluid, a passive transported scalar was added to the simulations, with a mass diffusivity ρD equal to 2.5e-5 kg/m s. In terms of boundary conditions, a value of 1 was applied to the mouth of the spreader subject, whereas a zero-flux condition was applied to all the outlets. In an attempt to provide a more quantitative characterization of the results in the different scenarios, the approach proposed by Gao et al. [25] was followed. They described the fraction of the sneezed air in the inhaled air using the Infection Index η, described by the equation: Where V is the inhalation rate [m 3 /s], ρin is the inhalated air density [kg/m 3 ] and C the mass fraction of the coughed air in the inhaled air. The parameter provides a representation of the integral amount of contaminated air inhaled by the subjects during the temporal evolution of the event. The computational grid was generated in ANSYS Meshing and consisted of a tetrahedral mesh with a 5 prismatic layers on the walls, which is adequate given the limited role played by viscous effects on the flow. Then the mesh was converted in polyhedra in ANSYS Fluent, resulting in 3.87 million polyhedrons. The mesh is depicted in Figure 4 , where only the Case 1 is reported for the sake of brevity. All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint The solution was obtained with a pressure-based solver and a SIMPLE algorithm with a Second Order scheme for pressure, Second Order Upwind for all variables (except for turbulence quantities), while time was treated with a Bounded Second Order Implicit scheme. A constant time step of 10 -2 s was chosen, with 10 sub-iterations, which are appropriate to achieve a sufficient reduction in the residuals within the time step. The process was solved with a transient simulation of the overall duration of 60 seconds for both the waiting room (Case 1) and the recovery room (Case 2). The quantitative results of the simulations for the waiting room are plotted in Figure 5 . perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint Looking at the charts it is possible to notice that in absence of HVAC airflow the contaminated air coughed by the spreader subject reaches only the subject in front (Kid D), at least in the time interval considered (60 s). When the HVAC system is considered the stronger the intensity of the airflow, the lower the concentration that affects the Kid D with a percentage reduction of -99.6% of concentration in Scenario C respect to Scenario A. Nonetheless, the increase in HVAC flow rate (thus in flow velocity) leads to a greater dispersion of the contaminated air far from the spreader subject. It is the Scenario C in which η reaches relevant values before the other. This is indicative of a more intense turbulent transport throughout the room. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . The development over time of the situation is visible at t=5 s, for which in the Scenario A heaviest droplets are progressively dragged to the ground while the lightest droplets (diameter approximately lower than 10 µm) continue their travel unhindered until they will reach the subject in front (Kid D). In presence of an HVAC (Scenario B), as anticipated, the coughed stream loses rapidly its momentum and is captured by a recirculation zone created by the HVAC between the spreader subject and the lateral wall (see supplementary materials: "Case 1 Video" and "Contaminant Recirculation Video"). Interestingly, for the Scenario C the further increase in the HVAC airflow promotes the turbulent transport, resulting in a complete disruption of the droplet cloud and an enhancement of its dispersion within the room. To provide additional evidence of the impact of the HVAC airflow on the droplet dynamics, the temporal evolution of their total mass in the room was calculated and plotted in Figure 7 . All the curves start from the same condition of 0.72 g, as prescribed in the setup of the discrete phase injection. Then, the mass suddenly drops by 2 orders of magnitude in the 5 s All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint following the start of the event. Such a significant reduction is associated to the droplets of large diameter (and thus large mass), which are more influenced by the gravitational force. Interestingly, negligible differences are present between Scenario A and B, confirming that the HVAC has a minimal effect in the first phase of the event. On the contrary, the Scenario C returns a more significant reduction in mass. This effect may be ascribed to the HVAC airflow that pushes the droplets back to the spreader subject, where they are trapped on its surface. In the second phase of the simulation (5 s ≤ t ≤ 60 s) the evolution shows a It is reasonable to think that in absence of HVAC the smallest droplets survive only thanks to buoyancy, whereas the largest one are progressively dragged to the ground. On the contrary, the reduction rate in presence of HVAC is reduced by the turbulent transport throughout the room, which is far more intense than buoyancy and gravitational effects, preventing also the large droplets to fall down. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint reached by the droplet cloud and two columns of droplets are formed above Kid E and D as a consequence of the temperature-driven buoyancy, which is associated to very low-speed motion. In the Scenario B and C, where the HVAC system is activated, the cloud of droplets covers considerable distances inside the room and reaches all the people inside. In these two scenarios, all the people in the room come into contact with the dispersed airborne contaminant and the droplets cloud assumes a turbulent motion relatively of the HVAC airflow settings. As highlighted by the figures, the droplet spreading is more intense as the HVAC flow rate increases. All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint In Case 2 a time interval of 60 s was simulated to allow the contaminated air to reach the other subject in the room (Kid A). Unlike the waiting room (Case 1), the propagation speed of both contaminated air and droplets is significantly reduced due to the presence of LEV system and for different trajectory of the coughing event, which is directed towards the ceiling. It is worth underlining that, contrary to Case 1, HVAC is present in both scenarios, but with a smaller flow rate entering from the diffuser (approximately a quarter of the previous nominal condition). In Case 2 we studied two different conditions: Scenario 0, where only the HVAC system is present, and Scenario 1, which also considers a LEV system positioned directly above the face of the spreader subject (Kid A). By analyzing the simulations, it is possible to appreciate immediately the advantage of equipping the recovery room with a LEV system. A more quantitative comparison is reported in Figure 9 , which describes the temporal evolution of the Infection index. Considering that the same range of Case 1 was used, it is possible to notice that the amount of contaminated air inhaled is significantly lower than what observed in the waiting room. As already mentioned, this can be ascribed to the different trajectory of the coughed stream as well as the lower HVAC flow rate. More importantly, the LEV system provides a virtually complete abatement of contamination. A more qualitative description of the results of the coughing event is reported in Figure 10 where the two scenarios are compared similarly to what already done for the Case 1. In the absence of any LEV system (Scenario A), the contaminated air and the droplets are transported at first by a combination of cough and temperature-driven buoyancy. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08. 25.20181420 doi: medRxiv preprint The effectiveness of the LEV system is confirmed also by the temporal evolution of the droplet mass in the room (reported in Figure 11 ). As already showed, in the Scenario B almost all the droplets are extracted within 2 s, while in the Scenario A are free to propagate throughout the room. Unfortunately the analysis of contagion risk from the airborne contaminants within hospital's rooms through the CFD approach is no generalizable as it is dependent on numerous specific factors such as the room layout, the HVAC diffusors and return grilles position, the people position in the room and their dynamic physical activities. However the CFD is a very useful tool for assessing and predicting the viral infection risk within closed places by running a customized CFD project based on each specific room. Our study shows us that the HVAC system in a closed waiting room generates a marked space diffusion of droplets from a chough event. Although the doubling of HVAC's air flow allows for a marked reduction in the airborn contaminant concentration this also leads to a substantial increase of turbulent air motions resulting in an increased and faster long-range spreading of droplets and air contaminants in the room. In indoor environment, the doubling of the air conditioned flow allows a relevant (up to 77%) reduction in droplets mass concentration within the room compared to nominal air flow. In the first 5 seconds from the cough event, no particular differences in droplets concentration are detectable in the room, while the relevant differences occur within 25 seconds due to the air conditioned systems that induce droplets air dispersion. In absence of air conditioning, larger particles more easily settle on the ground, while for nominal or doulbe-flow HVAC air-flow even the largest particles are subjected to turbulent phenomena and follow the air conditioned flow remaining All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint suspended for longer time. Despite that the calculation of Infection Index for all the subjects in the room proved that a higher air exchange allows to reduce in the long term the overall amount of inhaled contaminated air. Further studies are needed to deepen the contribution of natural ventilation to the scenarios analysed to understand if this can contribute to contaminants exposure reduction for the people inside the rooms. In the simulations performed in recovery rooms, the first 40 seconds from the cough event are not sufficient to allow both droplets and contaminated air to reach the Kid A. After that, in the absence of a Local Exhaust Ventilation system, the HVAC air-flow favours their turbulent dispersion within the room. The presence of a LEV unit placed above the patient's face shows a very high capacity to reduce droplets and contaminated air in the room, ensuring a total absence of exposure to contagion risk for the patient A. In our simulations based on quantitative CFD data, LEV system is able to remove both droplets and contaminated air in the first seconds immediately following the cough event. The development of CFD 3D simulations in healthcare environments can provide a qualitative and quantitative prediction of contagion risk and valuable help in optimizing the prevention processes aimed at minimizing infectious risk for patients and healthcare professionals during a pandemic. Aknowledgments: Authors are grateful to the RESCOP study group established to analyse the possible link between indoor/outdoor air pollution and COVID-19 outbreaks. The Italian Society of Environmental Medicine (SIMA) is grateful to Falck Renewables for its support. All rights reserved. No reuse allowed without permission. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. All the authors contributed to write and revise the manuscript. perpetuity. preprint (which was not certified by peer review) is the author/funder, who has granted medRxiv a license to display the preprint in The copyright holder for this this version posted August 31, 2020. . https://doi.org/10.1101/2020.08.25.20181420 doi: medRxiv preprint «Airborne Transmission Route of COVID-19: Why 2 Meters/6 Feet of Inter-Personal Distance Could Not Be Enough» «SARS-Cov-2 RNA Found on Particulate Matter of Bergamo in Northern Italy: First Preliminary Evidence», Infectious Diseases (except HIV/AIDS), preprint Natural Ventilation for Infection Control in Health-Care Settings «Transmission of Influenza A in a Student Office Based on Realistic Person-to-Person Contact and Surface Touch Behaviour» World Health Organization, Pandemic and Epidemic Diseases, e World Health Organization, Infection prevention and control of epidemic-and pandemic-prone acute respiratory infections in health care: WHO guidelines «Relative Contributions of Four Exposure Pathways to Influenza Infection Risk», Risk analysis : an official publication of the Society for Risk Analysis, set «Aerosol Technology: Properties, Behavior, and Measurement of Airborne Particles «Detection of airborne severe acute respiratory syndrome (SARS) coronavirus and environmental contamination in SARS outbreak units Aerodynamic analysis of SARS-CoV-2 in two Wuhan hospitals | Nature «The Size and Concentration of Droplets Generated by Coughing in Human Subjects Atkinson e World Health Organization, A c. di, Natural ventilation for infection control in health-care settings. Geneva: World Health Organization «Transient CFD simulation of the respiration process and inter-person exposure assessment «CFD Analysis of the Performance of a Local Exhaust Ventilation System in a Hospital Ward «la-corretta-ventilazione-per-il-controllo-degli-ambienti-sanitari-un-caso-studio 2006 -Study on transport characteristics of saliva dropl 2010 -Characterizing exhaled airflow from breathing and .pdf». Consultato: mag 2010 -CFD Simulation of Human Coughs and Sneezes A Stud 2017 -Numerical Simulation of Coughed Droplets in Confer A Numerical Investigation of Human Cough Jet Devel.pdf». Consultato: mag. 20 Towards aerodynamically equivalent COVID19 1.5 m s.pdf CFD Simulation of Human Coughs and Sneezes: A Study in Droplet Dispersion, Heat, and Mass Transfer «Transient CFD simulation of the respiration process and inter-person exposure assessment «Dispersion of coughed droplets in a fully-occupied high-speed rail cabin Numerical Simulation of Coughed Droplets in Conference Room», Procedia Eng «Characterizing exhaled airflow from breathing and talking A CFD analysis of different human breathing models and its influence on spatial distribution of indoor air parameters | Request PDF