key: cord-0229737-uoj4222k authors: Cai, Hanmin; Heer, Philipp title: Experimental implementation of an emission-aware prosumer with online flexibility quantification and provision date: 2021-10-25 journal: nan DOI: nan sha: e06231bc40286ba42797402f5867035edca9a135 doc_id: 229737 cord_uid: uoj4222k Emission-aware and flexible building operation can play a crucial role in the energy transition. On the one hand, building operation accounts for a significant portion of global energy-related emissions. On the other hand, they may provide the future low-carbon energy system with flexibility to achieve secure, stable, and efficient operation. This paper reports an experimental implementation of an emission-aware flexible prosumer considering all behind-the-meter assets of an actual occupied building by incorporating a model predictive control strategy into an existing building energy management system. The resultant can minimize the equivalent carbon emission due to electricity imports and provide flexibility to the energy system. The experimental results indicate an emission reduction of 12.5% compared to a benchmark that maximizes PV self-consumption. In addition, flexibility provision is demonstrated with an emulated distribution system operator. The results suggest that flexibility can be provided without the risk of rebound effects due to the flexibility envelope self-reported in advance. It is estimated that 28% of the global energy-related CO 2 emissions are attributed to the operation of buildings [1] . Notably, indirect emissions due to the power generation for the consumption of electricity and commercial heat account for around 67% of total building-related emissions. Moreover, as the share of intermittent Renewable Energy Sources (RES) increases and conventional power plants are gradually phased out, there is an increasing need for flexible demand to maintain security of supply [2] . Additionally, active utilization of buildings' flexibility is also a cost-efficient alternative to traditional distribution network expansions [3] when addressing voltage stability issues introduced by simultaneous Electric Vehicle (EV) charging and surplus Photovoltaics (PV) output. There is, therefore, an increasing need for realistic Demand Side Management (DSM) strategies, which can reduce emission and provide flexibility without pronounced rebound effects or compromising occupants' comfort. loop fashion and in a simulated environment. This study significantly extends the previous work with an automated optimization-based flexibility quantification and exemplify flexibility provision in a real-life building. The mentioned works and the current study are further compared and summarized in Table 1 with respect to the main focus, testbed, resources and whether flexibility is quantified online for real-time control. The main contributions of this paper are threefold. Firstly, we present an emission-aware MPC as the base strategy for a prosumer. The emission reduction and occupants' comfort levels are quantified in realistic conditions. Secondly, online flexibility quantification and provision are formulated as optimization problems that can be automated with commercial solvers. Lastly, the framework is demonstrated with an emulated DSO and risk of rebound effects is assessed. [5] Economic MPC and cost benefit analysis Occupied office building HVAC, Blind - [6] Frequency regulation service Two experimental rooms HVAC - [7] Frequency regulation service Five-room office building HVAC - [8] Economic MPC Three lecture rooms HVAC - [9] Energy-efficient MPC Experimental building HVAC - [10] Economic and energy-efficient MPC Three open-plan offices HVAC - [11] Energy-efficient and emission-aware MPC Battery and RTDS HVAC and Battery - [12] Multimode HVAC system Solar Decathlon house HVAC and PCM - [14] [15] Data predictive control Two occupied rooms HVAC - [16] Data-driven energy-efficient MPC Two-story building HVAC - [17] [18] Machine learning-based MPC Office and lecture theater HVAC - [19] Flexibility market 121 households HVAC Offline [21] Composable smart grid control Campus building Generic Online [22] Aggregate power flexibility Simulation Generic Online [23] Power flexibility band Simulated residential HVAC, DHW, PV and battery Online [24] Flexibility characterization Simulated commercial and residential buildings HVAC Offline [25] Flexibility characterization Simulated office building HVAC Online [26] Flexibility quantification and provision Simulated campus building HVAC Online [27] Flexibility potential quantification 186 households Wet appliances, DHW buffers and EV Offline [28] MPC applications and flexibility quantification The remainder of the paper is organized as follows: Section 2 presents the methodological framework of controller design, flexibility quantification and provision. Section 3 describes the experimental setup and Section 4 presents the results of a week-long experiment, whose real-world implications are critically discussed in Section 5. Finally, Section 6 gives a brief summary and areas for further research are identified. This section first describes models used in the MPC controller and operating constraints of all the assets. Then the Optimal Control Problem (OCP) formulation of the MPC controller is provided using the obtained models. Following this, the flexibility envelope calculation and an interaction scheme between the building and the DSO are unified with the mentioned MPC. Behind-the-meter assets including HPs for Space Heating (SH) and Domestic Hot Water (DHW), a stationary battery, an EV with bidirectional charging, uncontrolled loads and a rooftop PV installation are considered in the current study. Their models and operating constraints for real-time control are elaborated below. Models with more complex structures require additional measurements or first principles-based modeling, which will hinder scaling up due to high engineering efforts and/or lack of transferability of modeling results. Thus, simplified models are adopted in this work with their parameters identified from commonly available measurements. Additionally, more complex models are associated with higher computational burdens in real-time control. Hence, models with simple structures are desired in real field applications and experimental results presented in Section 4 indicate that these models are suitable for our tasks. Throughout the paper, we use(·) to denote forecast values and use t as the time index. We focus on controlling the active power of behind-the-meter assets neglecting the reactive power that is in general not available to control for residential loads. Power consumption is treated as positive, which leads to PV power output and battery/EV discharging power being negative. Lastly, we use R + and R − to refer to the set of non-negative and non-positive real values respectively. In general, thermal dynamics are highly nonlinear processes. However, when room temperature in buildings is actively controlled within a limited range, the dynamics of each zone can be approximated with an affine model to use in closed-loop control. Experimental studies also show that high-order models tend to perform worse than low-order models [29] , as unobserved states such as wall temperature have to be estimated in real-time control. The current study considers each room i ∈ I as one zone, and indoor temperature is given by: where T sh i,t is the room temperature, φ sh i,t is the thermal power input,T amb t ,φ irrd t are the ambient temperature and the solar irradiance forecast respectively, H is the time horizon, i is the room index and I is the set of rooms. Since only weather forecast is available in real-time control,T amb t andφ irrd t are used directly. In addition, we consider continuous thermal power to the rooms and the equivalent thermal power output can be obtained by modulating an HP operating on ON/OFF mode with a pulse width modulation strategy. The corresponding electrical power consumption of the HP is given by: where COP m denotes the COP of the HP for SH. The corresponding constraints are given by: sh- i,t are the slack variables introducing soft constraints to ensure feasible solutions, and P sh,max is the electrical power capacity of the HP. DHW is supplied by a fixed-speed HP operating on ON/OFF mode with a buffer tank. Stratification effects within the tank are neglected, and the average tank temperature is given by: where T dhw, avg t is the volume-weighted average tank temperature, φ dhw t is the thermal power input and m draw t is the amount of water draw. The corresponding electrical power consumption of the HP can be given by: where COP h is used to differentiate from the above-mentioned SH HP. This is because SH and DHW typically have different inlet temperatures. Average tank temperature constraints are given by: where T dhw,max t and T dhw,min t are the predefined time-varying upper and lower average tank temperature limits respectively, dhwt and dhw+ t are the slack variables enforcing soft constraints. The ON/OFF operating mode is modeled with a binary variable z dhw t : P dhw t = P dhw,max z dhw t , ∀t ∈ H (10) where P dhw,max is the electric power capacity of the DHW HPs. A model that captures battery self-losses, charging/discharging efficiencies is given by: where SOC ebat t is the battery State-Of-Charge (SOC), P ebat, ch t ∈ R + and P ebat, ds t ∈ R − are the battery charging and discharging power respectively. The mutual exclusiveness of P ebat, ch t and P ebat, ds t is enforced with a binary variable z ebat t as follows. where ebat t is the slack variables introducing soft constraints to ensure feasible solutions and SOC ebat,min is the minimum SOC. Similar to the stationary battery model, the EV battery is modeled as follows: where C is the set of time steps when the EV is connected to the charger at home. Constraint (21) indicates EV is not available for control when absent. Constraint (22) ensures minimum departure state-of-charge SOC ev,min sup C with sup C being the departure time instant or supremum of the set C. PV power output is predicted based on weather forecast and the formulation is given by: whereP pv t ∈ R − is the predicted PV output. PV power forecast {P pv t |t ∈ H} within the prediction horizon H is additionally combined with a 15-minute ahead persistence forecast. The result is used in the predictive controller. Coefficients (α pv , β pv , γ pv ) are re-identified every day accounting for the impact of potential coverings on the installation, such as leaves and snow. The coefficients are updated if the re-identification is satisfactory. Uncontrolled loads refer to lighting, cooking and wet appliances. The current study considers an aggregated power P fix t ∈ R + of these appliances to account for their electricity consumption. The forecast is a combination of a 15minute ahead persistence forecast and a 24-hour ahead persistence forecast. The energy balance of the entire building is given by: where P btg t ∈ R − and P gtb t ∈ R + are the electricity export and import respectively. They are differentiated because the total equivalent carbon emission is calculated according to the carbon intensity of electricity imported from the grid, and it is assumed that electricity export does not offset building's carbon footprint. To ensure the mutual exclusiveness of P btg t and P gtb t , a binary variable z grid t is introduced. The full OCP formulation of the MPC is given by: In addition, a set of inequidistant sampling time is used to reduce the number of decision variables as shown in Figure 1 . Larger sampling time are assumed for the time instants further in the optimization horizon, as forecast and modeling errors increase as well. The horizon is chosen to be 24 hours to include future knowledge such as PV power output and EV usage patterns. Flexibility envelope is empirically introduced in our previous work [28] and this section first briefly summarizes it. Afterward, the original qualitative definition is formulated as optimization problems and extended to consider the flexibility from batteries, EVs with bidirectional charging, and curtailable PV. Note that, the following flexibility definition does not assume any knowledge of baseline power, as it cannot be reliably estimated to establish a consensus between the service provider and the receiver and baseline-based approaches are vulnerable to manipulation [30] . The concerns can be more pronounced at the building level. The flexibility envelope identification starts with identifying the energy bounds by energizing flexible appliances to their extremes. The upper energy bound is identified by setting all devices to consume as early and as much as possible and full curtailment of PV output. To identify the lower energy bound, all the loads are set to consume as late and as little as possible. Simultaneously, the stationary and EV batteries are set to discharge as early and as much as possible without curtailment of PV output. The upper and lower energy bounds are illustrated as the red and blue curves in Figure 2 . Formally, the above-mentioned notion can be formulated as optimization problems by modifying the OCP formulation in Eq. (27) . Initially, solving the original OCP gives {X t ,Ũ t ,Ṽ t |∀t ∈ H}, in which {X t |∀t ∈ H} are the optimal state trajectories. The cost functions for deriving the upper and the lower energy bounds are defined as is an exponentially decaying weighting factor. Moreover, these optimization problems are initialized using the optimal state trajectoriesX t . Solving the OCP with the new cost functions, we have in which H is the optimization horizon for energy bounds identification and it might be different from H. Denote the aggregate power of all assets except uncontrolled loads as P t ∈ R and we further have P ↑ t and P ↓ t as the aggregated power calculated from U ↑ t and U ↓ t respectively. With pv k ∆τ k |∀n ∈ H } respectively. Finally, we can obtain the energy bounds of the entire building combining the above-mentioned bounds. To ease the computational efforts, power of all assets are relaxed to continuous variables, which admittedly introduces biases. Essentially, the energy bounds are determined by system dynamics and operation limits, and they define all feasible which is an infinite set due to continuously controllable set points of the components. To ease representation, we consider only power trajectories with invariant power levels as the dashed line in Figure 2 shows with the slope indicating the power. The corresponding available duration is limited by the second endpoint of the line. Denote a future time instant as τ ∈ T + and feasible power level as P ∈ P τ . The mentioned available duration is represented as an implicit function of power level and time f : R × T + − → R + . To summarize, the flexibility envelope is a three-dimensional surface consisting of all the points in the set {(τ , P , f (τ, P ))|τ ∈ T + , P ∈ P τ }. The proposed flexibility envelope can capture the thermal inertia of a building, the storage of a domestic hot water tank, the bidirectional charging of a stationary electric battery and/or an EV, and the curtailable PV power. When such a flexibility envelope is self-reported in advance, a DSO obtains a comprehensive overview of the available flexibility at a given building. The interaction between the building and the DSO is further described as follows. Upon receiving the flexibility envelope, the DSO can notify flexibility provision by sending a message (τ s , τ e , P ) to the building, where τ s and τ e denote the starting time and the ending time of flexibility provision respectively, and P ∈ P τ denotes the power level that needs to be tracked. By definition, there is τ e − τ s ≤ f (τ, P ). Upon receiving (τ s , τ e , P ), the cost function of the OCP is extended to include the cost of tracking errors with the weighting factor ω 4 and the resultant is The overall two-stage framework is further illustrated in Figure 3 . With this framework, the DSO can precisely address local network issues with local flexibility resources. When there is a sufficient number of buildings supporting this framework, the DSO can even steer the load to follow the expected supply of the system. In this section, the experimental setup is first summarized and interested readers are referred to [31] for comprehensive description of test specifications, experiment plans as well as appliance specifications. Except for the EV, all of the assets are real physical components that are directly controlled in the experiment. The EV with bidirectional-charging was simulated with an identical model for both the emulator and the controller. This is equivalent to assuming perfect modeling of the EV battery and charging/discharging process. These assets are from the NEST demonstrator at Empa in Switzerland [32] , as Figure 4 shows. The hardware is distributed around the research infrastructure, but time-stamped measurements allow us to emulate the actual operation of a prosumer equipped with all the aforementioned assets with the exception of the simulated EV. The total power of the whole emulated building is obtained by summing all respective power measurements and adding the simulated EV charging/discharging power. The SH and DHW of the "Urban Mining and Recycling" (UMAR) residential unit, as marked in the white box, were controlled. Uncontrolled loads were also located at the same unit. Therefore, we have consistent occupancy patterns for all the assets. More specifically, the layout of the three-room unit is shown in Figure 5 and each room is treated as one zone. The UMAR unit is equipped with water-based ceiling panels for heating. The room temperature comfort zone of the whole unit was set as [22°C, 23°C], which was relaxed to [21°C, 25°C] between 8 am and 8 pm when the occupants are likely not present. In principle, occupants can directly configure the comfort zone without affecting the generality of the presented method. As for the DHW, the average tank temperature limits were set to [45°C, 60°C]. The lower limit is boosted to [59°C, 60°C] at least once a week to avoid Legionella contamination [33] . In our experiment, this timing was manually chosen to be Sunday morning between 4 am and 6 am. A Lithium-ion battery of 17.5 kWh with bi-directional charging/discharging power of ±5 kW is operated 2 . On the other hand, an EV of 50 kWh with bi-directional charging/discharging power of ±7 kW is included as a simulated system component and was simulated in the experiment. PV electricity output is considered emission-free, but the power exported to the grid does not offset the building's carbon footprint. Measurements and weather forecasts [34] were queried from a server hosted at Empa. The weather forecast is updated every 12 hours. The OCP was formulated with CVXPY [35] in Python 3 and solved using MOSEK [36] . Communication with the actuators in the building is established via a Python-OPC UA client. For the sake of brevity, a full description of the facility is not provided here. Interested readers are referred to [37] for more details about the demonstrator. The electricity carbon intensity was queried externally. Interested readers are referred to [38] for more details about the calculation based on data retrieved from ENTSO-E Transparency Platform [39] . This section summarizes the field experiment carried out in the research facility shown in Figure 4 . The MPC controller was implemented by solving the OCP formulated in Section 2.2 every 15 minutes. The optimal values of all the control variables over the 24h horizon are thus obtained. Only the decision values for the next time step are sent to the actuators via the Python-OPC UA client. All the hardware is equipped with dedicated meters and all the measurements are registered in the NEST database [37] . Since the actuators cannot perfectly execute the set points, we distinguish between the measured power and the power set point planned by the controller in the following results. Model parameters are identified using data collected in 2019 with the prediction error method [40] . The models are then re-sampled according to the set of inequidistant sampling time intervals shown in Figure 1 . The strategy assumes the same power set point during a sample time interval. The accuracy of each individual appliance is not presented here. However, additional experiments were carried out, where energy input for SH and DHW are minimized and their temperature are shown to stay close to their lower limits [38] . We note that this is a common experimental design for validating modeling accuracy, as used in [14] and [41] . Additionally, the following experimental results further confirm modeling accuracy, as both SH and DHW temperatures stay within predefined limits while optimizing according to carbon intensity, except for dramatic disturbances. The remainder of this section is structured as follows. First, closed-loop control results of a week-long experiment applying the framework illustrated in Figure 3 are presented on an individual appliance basis. Afterwards, the controller's performance in reducing equivalent carbon emission of the entire building is evaluated by comparing to a benchmark controller that maximizes PV self-consumption. Lastly, the flexibility quantification and provision are demonstrated with an emulated DSO. Overall, the presented results demonstrate that the controller operates with emission-aware MPC as base strategy and can deviate from the optimal trajectory to provide flexibility upon request. In the week-long experiment, power set points of all controllable assets were obtained by solving the OCP formulated in Eq. (27) and the OCP with modified objective function during flexibility provision. Controller decisions, realized power input and responses of all the assets are presented in this part and the results are first presented on an individual appliance basis. Afterwards, the net power exchange with the grid is summarized in Figure 9 . The temperatures of all three rooms are shown to approach their upper temperature limits in Figure 6 (a). This is because the controller attempted to use as much electricity as possible when carbon intensity was low, and tried to avoid electricity consumption when carbon intensity was high. There were recurrent large temperature drops below the lower temperature limit in Room 273 (marked by the grey periods 1 -5 in the figure). They occurred because windows were opened for an extended period for hygienic reasons due to Covid. Apart from that, indoor temperature stays within the comfort zone most of the time. By comparing Figure 6 (b) and Figure 6 (c), we can observe that although mismatches exist, actuators mostly follow the controller decisions. Figure 6 (d) shows that temperatures within Room 272 and Room 274 are mostly within the limits, whereas the accumulated temperature deviation reached around 4 Kh in Room 273 by the end of the experiment due to dramatic disturbances. We can also observe from Figure 6 (a) that indoor temperature occasionally exceeds the upper temperature limit such as the grey period 7 . In general, such behaviour can be attributed to high solar irradiance, modeling errors, and internal gains that are not entirely captured. However, the solar irradiance as shown in the grey period 10 in Figure 6 (e) is not substantially higher than other days. Additionally, the measurements of the grey period 8 in Figure 6 (b) and the grey period 9 in Figure 6 (c) show that the controller decision and actual power input to Room 272 and Room 273 were close to 0 kW during the same period. Hence, the overshoot is more likely caused by dramatic internal gains. We can observe from Figure 7 (a) that the temperature is always within the predefined limits indicating sufficient hot water for occupants. Right before the boost of the lower temperature limit, energy is actively used during the low carbon intensity period. Additionally, we can observe from Figure 7 (b) that the power consumption is not entirely the inverse of carbon intensity. Occasionally, power is used at the peak carbon intensity period (marked by the grey period 1 in Figure 7 ). This power usage is likely caused by unexpected large water draws. Additionally, the net power exchange with the grid shown in Figure 9 does not show a peak at this time (marked by the grey period 1 in Figure 9 ), implying that the power was supplied internally. We can also observe that the measured power input mostly follows control decisions, with exceptions such as that marked by the grey period 2 in Figure 7 , which is a result of actuation errors. Additionally, thermal power inputs are dependent on the difference between tank temperature and inlet temperature. Hence, the measured power input varies over time. The planned and realized thermal power input into the tank are summarized in (b), in which the thermal power is normalized with a thermal power capacity inferred from historical data. For the sake of brevity, the results of all non-thermal loads are summarized in Figure 8 . Note that the bidirectionalcharging EV was not present and the results in Figure 8 (b) and (c) are simulated SOC and charging/discharging power. The net electric power exchange with the grid aggregating all the assets is summarized in Figure 9 together with electricity carbon intensity. We can observe that the net power shows an inverse pattern to that of the carbon intensity profile. A grid export can be observed in the grey period 2 . This occurred due to the forecast error of uncontrolled load profile. To evaluate the controller performance on emission reduction, we compare the results presented earlier with a virtual experiment on a virtual testbed. Notably, SH demand contributes to a sizable portion of the overall energy consumption, but its dynamics are highly nonlinear. Although a simplified model is used in the closed-loop control, it is not accurate enough as a virtual testbed to emulate the physical system over one week. Hence, the digital twin in [42] , which is benchmarked with the full-year data of 2019 at 1-minute temporal resolution with a CV-RMSE of 0.09, is included in our virtual experiment. Compared with other frequently used methods such as reference day, the proposed virtual experiment captures the high-resolution variation of carbon intensity profile. In the virtual experiment, SH and DHW are controlled with a hysteresis controller, which is common in the current industry. More specifically, the average water tank temperature limits are [55°C, 60°C] and the comfort zone of SH is the same as the physical experiment. DHW is treated differently to ensure a sufficient temperature level to eliminate Legionella, which also replicates the existing industry practice. The EV is charged at full power right after being connected to the charger, and a hysteresis controller is applied afterward to ensure the minimum SOC level. Currently, there are no standard industrial practices as to design energy management systems covering all flexible devices. A self-consumption-oriented strategy is considered for the battery in addition to the hysteresis controllers mentioned above. It stores all PV production; for the rest of the time, it only discharges to cover the demand of other appliances. Note that the same carbon intensity profile is used in both the control and the impact evaluation. This is equivalent to assuming a perfect carbon intensity forecast. Interested readers are referred [38] for the forecast accuracy. We can observe that the total emission and the average carbon footprint of the consumed electricity are reduced by 12.5% and 16.5%, respectively. The reduction is realized by avoiding electricity imports during high carbon intensity periods. An example is marked by the grey period 1 in Figure 10 and Figure 7 . The reduction is not pronounced, which indicates that the benchmark control strategy mentioned above already reduce carbon footprint by promoting self-consumption. An example of online flexibility envelope quantification is provided in Figure 11 , which shows that flexibility potential considerably vary within the 24 hour horizon. Results of the flexibility provision are given in Figure 12 with an emulated DSO. We consider a scenario in which the DSO experiences network congestion due to low ambient temperature. More specifically, load peaks may be exacerbated due to simultaneous consumption from newly adopted HPs, which the distribution system may not be planned for. Thus, additional flexibility from buildings is needed to mitigate the issue. As per industry practice, ripple control [20] has been used for decades for direct load control by broadcasting radio signals to cease operation of devices such as HPs within a target group. However, ripple control represents unidirectional communication and addresses limited types of flexible devices. In the rest of this section, we demonstrate the proposed framework with an emulated DSO. More importantly, we show similar performance, namely keeping total power exchange with the grid close to 0 kW, can be achieved from the perspective of the DSO, while comfort levels and preferences of end users are shown to be respected. In the experiment, a building self-reports its flexibility envelope to the DSO, who in turn remains idle until flexibility needs are foreseen according to the weather forecast. The DSO examines the reported flexibility envelope shown in Figure 11 and notifies flexibility provision to the building via (τ s , τ e , P ) := (2020-11-21 21:00:00+01:00, 2020-11-22 06:30:00+01:00, 0 kW) at the time marked by the vertical line 1 in Figure 12 . Importantly, (τ s , τ e , P ) needs to match the self-reported flexibility envelope (marked by the red box in Figure 11 ). Within the flexibility provision period (marked by the period between vertical lines 2 and 3 ), the building tracks the set point. The results show that the total power exchange with the grid is reduced to a marginal level, although not strictly zero. This can be attributed to the actuation errors as observed in , Figure 7 and Figure 8 . Besides, we can observe that the energy states of all devices are comfortably away from their lower limits (as seen at the end of the grey area 11 in the first plot of Figure 6 , and the end of the grey area 3 in the first plot of Figure 7 ). This indicates that there are no immediate needs for electricity imports from the grid. Therefore, there is no risk of rebound effects. While the building activates its flexibility, the DSO continuously monitors the building and remunerates the service provider afterwards. A full discussion of the remuneration scheme lies beyond the scope of this study, but this remains an important issue for future research. Bacher et al. [43] present a grey-box modeling approach of building thermal dynamics, which excites the system with a pseudo-random binary sequence (PRBS). Although their parameter identification shows a good match between model and historical data, the performance in real-time control is unclear. One major drawback of this approach is that it is intrusive for occupied buildings and the controlled heat input may significantly compromise occupants' comfort, as [44] shows. Simplified SH models extracted from historical data yielded sufficiently satisfactory results in emission reduction and maintaining comfort levels in our implementation. A probable explanation might be that the whole unit is heated with water-based ceiling panels, which have slower dynamics than forced air heating [43] . Another possible explanation for this is that the temperature is controlled within a small range. Apart from the presented quantitative assessment, qualitative assessment of thermal comfort by the occupants was also collected via online feedback form throughout the experiments [31] . For DHW, all feedback shows "very satisfied". As for the bedrooms, 37.5% of the time, the occupants indicated slightly cool indoor temperature in the 7-scale rating (cold, cool, slightly cool, neutral, slightly warm, warm, hot) matching low comfort violations. For the rest of the time, occupants gave neutral opinions toward the indoor temperature. We experienced users' fatigue in responding to survey requests. Hence, the current survey is very limited. This suggests that the feedback strategy in the future needs to take a different form, especially for real-time control. As the bi-directional EV was emulated, no assessment was collected in this regard. The study is subject to at least two limitations. Firstly, the OCP formulation in Eq. (27) does not account for uncertainties associated with forecast and model errors. Secondly, although the flexibility provision experiment shows comfort satisfaction without pronounced rebound effects, we cannot rule out the possibility when the maximum duration of flexibility provision is requested or when a DSO requests flexibility with a different lead time. Future research includes examining more scenarios to assess the robustness of flexibility quantification and provision. Alternatively, probabilistic flexibility representation could be established to account for uncertainties. Compared with the traditional ripple control scheme [20] , the main advantage of the presented framework is that it allows DSOs to obtain a comprehensive overview of available flexibility, which effectively combines all flexibility resources. The high-resolution flexibility supports them to address potential network issues precisely without compromising end users' comfort levels and preferences. However, concerns over reliability may arise because the reliability decreases as the number of elements increases for any series system. The proposed prosumer is an example of such series systems. Additionally, ripple control is implemented in an open-loop fashion and the response can be expected within 7s [20] , whereas the proposed framework would take longer to quantify flexibility envelope and establish flexibility provision agreements. Lastly, communicating the flexibility envelope still comprises significant communication efforts and further simplification may be necessary to mitigate that. All in all, the existing ripple control scheme is favorable when it comes to simplicity and responsiveness. In contrast, the presented framework is favorable when a DSO needs to utilize a significant number of resources and requires automated and optimization-based approach to handle the complexity. Last but not least, the stated equivalent emission reduction of 12.5% has to be understood as a result specific to the presented system configuration, weather condition, carbon intensity profile, user interactions, and accuracy of the digital twin. The number can also be impacted by the sizing of each devices, forecast and modeling uncertainties. The benefits of the proposed framework lie in the combination of emission reduction and flexibility provision. To support the energy transition, the current study demonstrates an Model Predictive Control (MPC)-based emissionaware and flexible prosumer. Both emission reduction and flexibility provision are investigated considering all behindthe-meter assets of an actual occupied building. The results show that the total equivalent emission reduction of 12.5% is achieved during a week-long experiment compared with a benchmark controller that maximizes PV self-consumption. Meanwhile, measurements indicate that end users' comfort levels are improved. The proposed flexibility provision framework is demonstrated with an emulated distribution system operator. A scenario where flexibility is requested to mitigate network congestion under cold weather is considered. In the current study, the system operator is provided with a precise overview of available flexibility due to the flexibility envelope communicated in advance. All flexible resources are shown to be coordinated to provide flexibility upon notification. The experimental results also suggest that flexibility can be provided without the risk of rebound effects. Furthermore, measurements confirm that user comfort levels and preferences are maintained. The current study opens for future research and development at the district and the system level. We will also extend our work by considering the uncertainties due to modeling and forecast errors. Additionally, we will investigate flexibility envelope approximations with data-driven approaches to address aforementioned shortcomings. Last but not least, a proper remuneration scheme can further be jointly considered with the design of flexibility services. 2020 global status report for buildings and construction: Towards a zero-emission, efficient and resilient buildings and construction sector Energy security through demand-side flexibility: The case of denmark Optimization problem for meeting distribution system operator requests in local flexibility markets with distributed energy resources Energy flexibility of residential buildings: A systematic review of characterization and quantification methods and applications Model predictive climate control of a swiss office building: Implementation, results, and cost-benefit analysis Experimental demonstration of frequency regulation by commercial buildings-Part II: Results and performance evaluation Experimental demonstration of buildings providing frequency regulation services in the Swiss market The imbpc hvac system: A complete mbpc solution for existing hvac systems Model predictive control of a thermally activated building system to improve energy management of an experimental building: Part ii-potential of predictive strategy A model predictive control strategy to optimize the performance of radiant floor heating and cooling systems in office buildings Model predictive control for optimizing the flexibility of sustainable energy assets: An experimental case study Hybrid model predictive control of a residential hvac system with on-site thermal energy generation and storage Data-driven model predictive control using random forests for building energy optimization and climate control Experimental demonstration of data predictive control for energy optimization and thermal comfort in buildings Input convex neural networks for building mpc Neuropt: Neural network based optimization for building energy management and climate control Model predictive control with adaptive machine-learningbased model for building energy efficiency and comfort optimization Experiment study of machine-learning-based approximate model predictive control for energy-efficient building control EcoGrid 2.0: A large-scale field trial of a local flexibility market Demand matching wind power generation with wide-area measurement and demand-side management A composable method for real-time control of active distribution networks with explicit power setpoints. part i: Framework Aggregate power flexibility in unbalanced distribution systems Quantification of load flexibility in residential buildings using home energy management systems Towards standardising market-independent indicators for quantifying energy flexibility in buildings Quantification of flexibility in buildings by cost curves-Methodology and application Model predictive control approach to online computation of demand-side flexibility of commercial buildings hvac systems for supply following Demand response flexibility and flexibility potential of residential smart appliances: Experiences from large pilot test in Belgium Predictive energy management of residential buildings while self-reporting flexibility envelope Model Predictive Control for energy optimization in an occupied apartment Why baselines are not suited for local flexibility markets Test specifications and experiment plans Nest-una plataforma para acelerar la innovación en edificios Technical assessment of electric heat boosters in low-temperature district heating based on combined heat and power analysis Meso-gamma scale forecasts using the nonhydrostatic model lm CVXPY: A Python-embedded modeling language for convex optimization Mosek APS Nest wiki aliunid -versorgung neu: Feldtest 1.1.2019 -30.6.2020 System identification: theory for the user Adaptive robust data-driven building control via bi-level reformulation: an experimental result Temporal resolution of measurements and the effects on calibrating building energy models Identifying suitable models for the heat dynamics of buildings Reducing transient and steady state electricity consumption in hvac using learning-based model-predictive control The project was funded by the Swiss Federal Office of Energy (Section: Energy Research and Cleantech) under the project SI/501841 "aliunid -Versorgung 'neu': Feldtest 1.1.2019 -30.6.2020". We would like to thank Reto Fricker, Sascha Stoller and Benjamin Huber for their support. We would also like to thank Charalampos Ziras for discussions and reviewing the draft.